  • Trane 750 CFM - page 1

    UV -S VN03D-EN Oct ober 20 07 Models “ A ” and later Design Sequence Installation Owner Maint enance V er tical Unit V entilat or Classr oom Unit V entilat or Model VUV VUVE 750 CFM – 15 00 CFM ...

  • Trane 750 CFM - page 2

    © 2007 American Standard All rights reserved. UV-SVN03D-EN Notice NO TICE: W arnings and Cautions appear at approp riate sections throughout this manu al. Re ad these carefully . WARNING – Indicates a p otentiall y hazardous situation whic h, if not av oided , could r esult in death or serious injur y . CA UTION – Indicates a potenti all y haz ...

  • Trane 750 CFM - page 3

    UV-SVN03D-EN 3 Contents Installation/Star tup/Commissioning 4 Pre-installation Chec klist 4 General Information 5 Dimensions/W eights 7 Installation Instructions 14 Electrical Requirements 24 Pre-Star tup Chec klist 26 Maintenance 27 W arranty Information 30 T r oubleshooting Chec klist 31 Unit Wiring 33 ...

  • Trane 750 CFM - page 4

    4 UV-SVN03D-EN Jobsite Inspection Always perform the following ch ec ks before accepting a unit: 1 . V erify that the nameplate data matc hes the da ta on the sales or der and bill of lading (including electrical data). 2. V erify that the power supply complies with the unit nameplate specifications. 3. Visually inspect the exterior of th e unit, f ...

  • Trane 750 CFM - page 5

    UV-SVN03D-EN 5 Unit Nameplate The unit nameplate is located in the left hand end pocket, beh ind the con - trol box. It include s the unit model number, serial numb er, electrical char - acteristics, and othe r pertinent unit da - ta. Factory Shipment Before shipment, each unit is leak test - ed, and run tested for proper control operation. Access ...

  • Trane 750 CFM - page 6

    6 UV-SVN03D-EN OA/RA Actuator (Option) The OA/RA actuator provides true spring return opera tion for positive close-off of the OA /RA damper. The spring return system of the actuator closes the outsid e damper if power is lost to the bu ilding. When ordered with factory controls , the actuator is a 3-point floating desi gn. A 2 to 10 VDC actuator i ...

  • Trane 750 CFM - page 7

    UV-SVN03D-EN 7 Table G1: VUVE genera l data Unit Location and Clearances Locate the un it in an indoor area. The ambient temperature surrounding the unit must not be less than 45°F . Do not locate the unit in areas subject to freezing. Attenti on should be given to service clearance and tec hnician safety . The unit should contain enou gh space fo ...

  • Trane 750 CFM - page 8

    8 UV-SVN03D-EN Dimensions Standard Depth Unit ...

  • Trane 750 CFM - page 9

    UV-SVN03D-EN 9 Dimensions F alsebac k Unit ...

  • Trane 750 CFM - page 10

    10 UV-SVN03D-EN Dimensions Dynamic Air Barrier Unit ...

  • Trane 750 CFM - page 11

    UV-SVN03D-EN 11 Dimensions End Co v er s ...

  • Trane 750 CFM - page 12

    12 UV-SVN03D-EN Dimensions W all Bo x es ...

  • Trane 750 CFM - page 13

    UV-SVN03D-EN 13 Dimensions Cr ossov er Piping FLUSH FLUSH 1 1/2" 1 1/4" 3" 24" 19 3/8" 3 5/8" 5 3/8" RETURN 7/8" I.D. FIELD CONN. W/ SHUT OFF V AL VE 7/8" I.D. FIELD CONN. W/ SHUT OFF V AL VE RETURN T OP VIEW SIDE VIEW T OP VIEW SIDE VIEW 16 5/8" DEPTH UNIT 21 1/4" DEPTH UNIT SUPPL Y 3" 24 ...

  • Trane 750 CFM - page 14

    14 UV-SVN03D-EN Grout W eep Holes Rubber Seals Unit Outside W all Floor W eep Holes Caulking Outside W all Interior W all w/ sheetroc k W ater dam sloped toward exterior Rubber Seals Unit Interior W all w/ sheetroc k W ater dam sloped toward exterior Flanged wallbox Wall Box Installation The following i nstructions are general recommendation s fo r ...

  • Trane 750 CFM - page 15

    UV-SVN03D-EN 15 General Installation Checks The checklist below is a summary of the steps required to successful ly in - stall a unit. Thi s checklist is intended to acquaint the installing personnel wi th procedures r equired in the installation process. It does not replace the de - tailed instructions ca lled out in the ap - plicable section s of ...

  • Trane 750 CFM - page 16

    16 UV-SVN03D-EN A B C D E F C B Installation Figure 3: Mounting hole location ABCDE F 075 Standard Unit (no Falsebac k) 1 .31 13.50 2.75 66.39 1 0.38 45.64 Standard falsebac k 1 .0 0 2.13 26.0 0 67 .0 0 10.00 47 .0 0 29" stepdown falsebac k 1 .0 0 2.13 24.44 67 .0 0 1 0.0 0 4 7 .0 0 28" stepdown falsebac k 1 .0 0 2.13 23.44 67 .0 0 1 0.0 ...

  • Trane 750 CFM - page 17

    UV-SVN03D-EN 17 Unit Mounting Note: All wall intake boxes should be installed prior to m ounting the unit ventilator. Refer to Page 14 for wall box installation instructions. The 1/2” mounting or anch oring holes are located on th e back of the unit on each end. See Figure 3 . 1 Note: All mounting fasteners are to be provided by the installer. Ch ...

  • Trane 750 CFM - page 18

    18 UV-SVN03D-EN Piping Installation Before installati on of piping pac k age, the shipping brac k et holding the pi p - ing in place, mu st be removed. Proper installation of pi ping is neces - sary to provide ef ficient coil operation and to prevent damage during opera - tion. Foll ow standard piping practices and include all accessories as neces ...

  • Trane 750 CFM - page 19

    UV-SVN03D-EN 19 Split System Units The following re frigerant piping and interconnecting wiring instructi ons apply to unit ventila tors with direct ex - pansion type coo ling coils used in con - junction with air-cooled co ndensing units. Reference must a l s o b e m a d e t o the condensing unit installatio n and wiring manual s which are shipped ...

  • Trane 750 CFM - page 20

    20 UV-SVN03D-EN Modulating Water Valves (Option) The actuator on the valve is a 24V, 3- point floating valve. The actuator can be easily removed from the valv e body by pressing in on the lo cking tab and rotating the actu ator 45° counter- clockwise (See Figure 6a) . The 2-way valves are bi-directional flow. The 3- way valves can be mixing or div ...

  • Trane 750 CFM - page 21

    UV-SVN03D-EN 21 Manually Opening Valve The manual open er can be manipulat - ed only when in the up po sition. The A port can be manually opened by firmly pushing the white manual lever down to the midway p osition and pushing the lever in. In this position, both A and B ports are open. This “manual open” position may be used for filli ng, vent ...

  • Trane 750 CFM - page 22

    22 UV-SVN03D-EN Soldering procedures are as follows: 1 Remove actuator as stated earlier. 2 Place valves on the pipe. Rotat e valve stem so the sh aft slot po ints at the notch in the side of the body (90° to flow direction). This pr o - tects the plug insi de the valve by removing it from the seat , Figure 14 . 3 Sweat the joints , keeping outer ...

  • Trane 750 CFM - page 23

    UV-SVN03D-EN 23 WA RN I NG Hazardous V oltage! Disconnect all electric pow er , in - cluding remote disconnects be - fore servicing. Follo w proper loc kout/tagout p rocedures to en - sure the pow er can not be inad - vertentl y energized. F ailure to disconnect pow er before servic - ing could result in death or seri - ous injur y . Wiring (contin ...

  • Trane 750 CFM - page 24

    24 UV-SVN03D-EN Electrical Req uirements Table E1: VUV 075-150, Electrical Perform ance Blower Blower Number of Electric Electric Minimum Overcurrent Unit Motor Motor No. of Heating Heat Heat T otal Circuit Protective Model No. V o l tage FLA (ea) HP F a n Motor Elements kW Amps FLA Amp acity Device VUVE075 1 15/60/1 3.0 1/4 1 0 0.0 0 0.00 3.00 3.8 ...

  • Trane 750 CFM - page 25

    UV-SVN03D-EN 25 Electrical Req uirements Table E1: VUV 075-150, Electrical Perform ance (continued) Blower Blower Number of Electric Electric Minimum Overcurrent Unit Motor Motor No. of Heating Heat Heat T otal Circuit Protective Model No. V oltage FLA (ea) HP Fan Motor Elements kW Amps FLA Amp acity Device VUVE125 1 15/60/1 2.0 1/10 2 0 0.00 0.00 ...

  • Trane 750 CFM - page 26

    26 UV-SVN03D-EN P re-Star t Chec klist Pre-Start-u p Checklist Before energi zing the unit, the following syste m devices must be checked: ____ Is the high voltage power supply correct and in accordan ce with the nameplate ratings? ____ Is the field wiring and circ uit protection the correct size? ____ Is the low voltage control circuit wiri ng cor ...

  • Trane 750 CFM - page 27

    UV-SVN03D-EN 27 WARNING Hazardous S er vice P rocedures! The maintenance and trouble - shooting procedures recommend - ed in this section of the manual could result in exposure to electri - cal, mechanical or other potential safety hazards. Always refer to the safety wa rnings provided throughout this manual concern - ing these procedures. When pos ...

  • Trane 750 CFM - page 28

    28 UV-SVN03D-EN WARNING Hazardous S er vice P rocedures! The maintenance and trouble - shooting procedures recommend - ed in this section of the manual could result in exposure to electri - cal, mechanical or other potential safety hazards. Always refer to the safety wa rnings provided throughout this manual concern - ing these procedures. When pos ...

  • Trane 750 CFM - page 29

    UV-SVN03D-EN 29 WARNING Hazardous S er vice P rocedures! The maintenance and trouble - shooting procedures recommend - ed in this section of the manual could result in exposure to electri - cal, mechanical or other potential safety hazards. Always refer to the safety wa rnings provided throughout this manual concern - ing these procedures. When pos ...

  • Trane 750 CFM - page 30

    30 UV-SVN03D-EN Warranty Information Standard Warranty The standard unit vent ilator warranty is Trane’s parts- only warranty, running 12-months from startup , not to exceed 18-months from shipment. Extended Warranty The optional extended warranty is a second through f ifth year warranty. The time starts at th e end of standard 1-year coverag e t ...

  • Trane 750 CFM - page 31

    UV-SVN03D-EN 31 T r ouble Shooting Chec klist WARNING Hazardous S er vice P rocedures! The maintenance and tr ouble shooting pr ocedures recommended in this sectio n of the manual could result in exposure to electrical, mec hanical or other potentia l safety hazards. Al wa ys refer to the safe ty warnings pr o- vided throughout this manual concerni ...

  • Trane 750 CFM - page 32

    32 UV-SVN03D-EN T r ouble Shooting Chec klist Problem Heating Cooling Cause Correction Room too cool X Room sen sor is not properly set Reset room senso r temperature X Clogged filter Replace filt er X Face and byp ass damper , or coil valve is malfunctioning. Replace malfunctioning compo ne nt, or contact the control’s contractor , o r if Trane ...

  • Trane 750 CFM - page 33

    UV-SVN03D-EN 33 Unit Wiring Field Installed Wiring 120V/1 PH - 3-Speed ...

  • Trane 750 CFM - page 34

    34 UV-SVN03D-EN Unit Wiring End De vice Contr ols 120V/1 PH - 3-Speed, D X/Hot Water ...

  • Trane 750 CFM - page 35

    UV-SVN03D-EN 35 Unit Wiring End De vice P ac kage 480V/3 PH - 3-Speed, Chilled Wa ter/Electr ic He at (6-Element) -page 1 ...

  • Trane 750 CFM - page 36

    36 UV-SVN03D-EN Unit Wiring End De vice P ac kage 480V/3 PH - 3-Speed, Chilled W a ter/Electric He at (6-Element) -page 2 ...

  • Trane 750 CFM - page 37

    UV-SVN03D-EN 37 Unit Wiring End De vice P ac kage 120V/1 PH - 3-Speed, 4 -Pipe Hot Water/Chilled W ater ...

  • Trane 750 CFM - page 38

    38 UV-SVN03D-EN Unit Wiring T racer ZN520 120V/1 PH - 3-Speed, 4- Pipe Hot Water/Chilled W ater ...

  • Trane 750 CFM - page 39

    UV-SVN03D-EN 39 ...

  • Trane 750 CFM - page 40

    T rane has a policy of con t inuous product and data impro vement and reserves the right to c hange design and specifications without n otice. Literature Order Number UV-SVN03D-EN Date Octobe r 2007 Supersedes UV-SVN03C-EN May 2006 T rane A business of American Standard Companies www .trane.com For more information, contact your local district offi ...

Manufacturer Trane Category Ventilation Hood

Documents that we receive from a manufacturer of a Trane 750 CFM can be divided into several groups. They are, among others:
- Trane technical drawings
- 750 CFM manuals
- Trane product data sheets
- information booklets
- or energy labels Trane 750 CFM
All of them are important, but the most important information from the point of view of use of the device are in the user manual Trane 750 CFM.

A group of documents referred to as user manuals is also divided into more specific types, such as: Installation manuals Trane 750 CFM, service manual, brief instructions and user manuals Trane 750 CFM. Depending on your needs, you should look for the document you need. In our website you can view the most popular manual of the product Trane 750 CFM.

Similar manuals

A complete manual for the device Trane 750 CFM, how should it look like?
A manual, also referred to as a user manual, or simply "instructions" is a technical document designed to assist in the use Trane 750 CFM by users. Manuals are usually written by a technical writer, but in a language understandable to all users of Trane 750 CFM.

A complete Trane manual, should contain several basic components. Some of them are less important, such as: cover / title page or copyright page. However, the remaining part should provide us with information that is important from the point of view of the user.

1. Preface and tips on how to use the manual Trane 750 CFM - At the beginning of each manual we should find clues about how to use the guidelines. It should include information about the location of the Contents of the Trane 750 CFM, FAQ or common problems, i.e. places that are most often searched by users in each manual
2. Contents - index of all tips concerning the Trane 750 CFM, that we can find in the current document
3. Tips how to use the basic functions of the device Trane 750 CFM - which should help us in our first steps of using Trane 750 CFM
4. Troubleshooting - systematic sequence of activities that will help us diagnose and subsequently solve the most important problems with Trane 750 CFM