Manual Emerson LTM-300

20 pages 5.22 mb
Download

Go to site of 20

Summary
  • Emerson LTM-300 - page 1

          MAIL :         ...

  • Emerson LTM-300 - page 2

    L TM-300 Magnetostrictive Level T ransmitter Instruction and Maintenance Manual T able of Contents Section 1. T ransmitter Overview Page 1.0 General Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 1.1 Level T ransmitter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ...

  • Emerson LTM-300 - page 3

    The L TM-300 is an elec tronic field instrument, suitable for installation i n h a z a r d o u s a n d n o n - h a z a r d o u s i n d u s t r i a l a r e a s . Te s t i n g a n d certification has been obtained from different agencies for installation in specific areas. This instrument is a two wire , loop powered smart transmitter , designed ...

  • Emerson LTM-300 - page 4

    The L TM -300 is an assembly of two major components: • The S ensor T ube Assembly . This a 5/8” diameter stainless steel probe, sealed on one end, with the magnetostri ctive wavegui de in its center . In addition to the magnetostrictive wa veguide, the tube also houses the optional temperature sensor and the detec tor electronics. The tube is ...

  • Emerson LTM-300 - page 5

    Level/Interface. A second float ma y be added below the first one, and the second output will be calibrated automa tically. The second time interval is measured in the same manner as the first and added to the first to derive the position of the heavier floa t. The same six inch dead zone applies to the measur ement of the second level althoug ...

  • Emerson LTM-300 - page 6

    Ambient T emp. Range -20°C ... +40°C (-4°F ... 104°F) Humidity Limits: SAMA PMC 31.1-5.2 Vibration Limits: SA MA PMC 31.1-5.3 RFI Limits: SAMA PMC 31.1-20 t o 1000 MHz up to 30V/m Material: 316ss standard, optional Hastalloy , Monel, Kynar c oated Operating T emperature: -50 to 302°F (-50 t o 150°C ) Maximum Pressur e: 2000 psig @ 300°F Rang ...

  • Emerson LTM-300 - page 7

    Displays Level Measur ement Display - in inches Level measur ement Display - in centimeters Level Measur ement Display - in millimeters Level Measur ement Display - in feet Level Measur ement Display - in meters Inter face Measurements - same decimal positions as L evel Only if configuration set to L evel+Inter face or All T emperature Measurement ...

  • Emerson LTM-300 - page 8

    6.4 Star t-Up f or Gage -M ounted L TM T ransmitters If the transmitter does not appear to calibrate properly, or has an erratic output, check the deadband of the sensor tube and ensure that the float is within the active region of the probe. The active region of the sensor tube is t ypically mar ked with 20mA and 4mA stickers when the unit is cal ...

  • Emerson LTM-300 - page 9

    All MagT ech produc ts are warran ted against defects in materials and workmanship of one year from date of shipment. The level gage chamber and process connections are guaran teed for the life of the tank or vessel to which it is attached . Floats are guarant eed for two years . MagT ech will repair or r eplace at its discretion those products tha ...

  • Emerson LTM-300 - page 10

    When the HART Communicator is connected to the transmitter and turned on, the first screen that is seen by the user is the root menu screen. If the transmitter is configured as L evel Only or Level plus T emperature, the scr een to the left shows the information displayed to the user . However if the tr ansmitter is configured as L evel plus Int ...

  • Emerson LTM-300 - page 11

    If the user selects Operation Status from the Diagnostics screen, he is able to view all of the status bits indicating the health of the transmitter operation. If the entry is labeled OFF , that means that the entr y is in normal operating conditions. If the entr y is labeled ON, that means that the transmitter diagnostics has detected an abnormal ...

  • Emerson LTM-300 - page 12

    The HART Communicator inf orms the user that the maintenance flags have been r eset when the transmitter has replied to the reset command. The user must acknowledge this information by pressing OK to continue . The user is then notified that the loop may now be returned to automatic contr ol. After the user presses OK the HART Communicator r etur ...

  • Emerson LTM-300 - page 13

    If it is desired to trim the digital level value, he may selec t a single point zero trim or a full level trim that requires the input of both the zer o l e v e l v a l u e a n d s o m e o t h e r l e v e l value preferably near the end of the level measurement tube . If the transmitter is configured with temperature measur ement, he may select a ...

  • Emerson LTM-300 - page 14

    Starting at the Calibration screen, select the Zero L evel T rim procedure . This procedure trims the Level digital v alue measurement at the position that the user desires to be the zer o refer ence position. If the user selects Zero Level T rim from the Calibration scr een, this screen will appear reminding the user that the loop should be remove ...

  • Emerson LTM-300 - page 15

    The HART Communicator now requests that the level floa t be set to the desired level upper trim point. The second trim point can be any other level point but it is recommended that this point be as far away fr om the zero point as possible. When the float is at this position, the transmitter will alway s report the digital value entered in the us ...

  • Emerson LTM-300 - page 16

    The user is then notified that the loop may now be returned to automatic contr ol. After the user presses OK the HART Communicator r eturns to the Calibration screen. The HART Communicator is now at the starting screen for the Zero T emper T rim . F ull T emperature T rim Starting at the Calibration screen, select the F ull Level Trim procedure . ...

  • Emerson LTM-300 - page 17

    The user is then notified that the loop may now be returned to automatic contr ol. After the user presses OK the HART Communicator r eturns to the Calibration screen. The HART Communicator is now at the starting screen for the F ull T emper T rim. Basic Setup Proc edures If a transmitter has been configured to measure both L evel and Inter face , ...

  • Emerson LTM-300 - page 18

    The HART Communicator will display this screen r eminding the user that the loop should be removed fr om automatic control before pr oceeding. When this has been done, the user must press OK to continue . The user is then notified that the loop may now be returned to automatic contr ol. After the user presses OK the HART Communicator r eturns to t ...

  • Emerson LTM-300 - page 19

    The next screen gives the user a choice to set the 4mA or 20mA values or to Exit the procedur e. Here the user will select the 4mA menu position. The HART Communicator r equests the user to set the Lev el (or Inter face) to the position that is to provide the 4mA loop curr ent output. When that has been done, the user must press OK to continue with ...

  • Emerson LTM-300 - page 20

        ? ...

Manufacturer Emerson Category Laser Level

Documents that we receive from a manufacturer of a Emerson LTM-300 can be divided into several groups. They are, among others:
- Emerson technical drawings
- LTM-300 manuals
- Emerson product data sheets
- information booklets
- or energy labels Emerson LTM-300
All of them are important, but the most important information from the point of view of use of the device are in the user manual Emerson LTM-300.

A group of documents referred to as user manuals is also divided into more specific types, such as: Installation manuals Emerson LTM-300, service manual, brief instructions and user manuals Emerson LTM-300. Depending on your needs, you should look for the document you need. In our website you can view the most popular manual of the product Emerson LTM-300.

Similar manuals

A complete manual for the device Emerson LTM-300, how should it look like?
A manual, also referred to as a user manual, or simply "instructions" is a technical document designed to assist in the use Emerson LTM-300 by users. Manuals are usually written by a technical writer, but in a language understandable to all users of Emerson LTM-300.

A complete Emerson manual, should contain several basic components. Some of them are less important, such as: cover / title page or copyright page. However, the remaining part should provide us with information that is important from the point of view of the user.

1. Preface and tips on how to use the manual Emerson LTM-300 - At the beginning of each manual we should find clues about how to use the guidelines. It should include information about the location of the Contents of the Emerson LTM-300, FAQ or common problems, i.e. places that are most often searched by users in each manual
2. Contents - index of all tips concerning the Emerson LTM-300, that we can find in the current document
3. Tips how to use the basic functions of the device Emerson LTM-300 - which should help us in our first steps of using Emerson LTM-300
4. Troubleshooting - systematic sequence of activities that will help us diagnose and subsequently solve the most important problems with Emerson LTM-300
5. FAQ - Frequently Asked Questions
6. Contact detailsInformation about where to look for contact to the manufacturer/service of Emerson LTM-300 in a specific country, if it was not possible to solve the problem on our own.

Do you have a question concerning Emerson LTM-300?

Use the form below

If you did not solve your problem by using a manual Emerson LTM-300, ask a question using the form below. If a user had a similar problem with Emerson LTM-300 it is likely that he will want to share the way to solve it.

Copy the text from the picture

Comments (0)