    Micro Motion ® F-Series Sensor Inst allation Manual Inst allation Manual P/N 20002298, Rev . C September 20 07 ...

  • Emerson F-SERIES SENSOR - page 2

    ...

  • Emerson F-SERIES SENSOR - page 3

    Sensor In stallation: F-Series 1 Before Y ou Begin Before Y ou Begin This manual describes ho w to install a Micro Motion ® F-Series sensor . The follo wi ng information is provided in this manual: Customer service For technical assistance, phone the Micr o Motion Customer Service depa rtment: • In the U.S.A., phone 800-522-MASS (800-522-6277) ( ...

  • Emerson F-SERIES SENSOR - page 4

    2 Sensor In stallation : F-Series Before Y ou Begin Specifications Full product specif ications can b e found in the F-Seri es Product Data Sheet, which is a v ailable from the Micro Motion web site at www .micromotion.com . Definitions The term MVD ™ transmitt er refers to the follo wing transmitter models: • Models 1500, 170 0, 2500, and 2700 ...

  • Emerson F-SERIES SENSOR - page 5

    Sensor In stallation: F-Series 3 Before Y ou Begin Figure 1 F-Series sensor with core p rocessor Approv al tag Flow direction arrow Core processor housing Calibration tag Process connection Approv al tag Calibration tag Core processor housing Purge fitting Purge fitting Sensor with purge fitt ings ...

  • Emerson F-SERIES SENSOR - page 6

    4 Sensor In stallation : F-Series Before Y ou Begin Figure 2 F-Series sensor with integrally mounted Model 1700/2700 transmitter Model 1700/2700 transmitter Approv al tag Flow direction arrow Core processor housing Calibration tag Process connection Calibration tag Approv al tag Purge fitting Purge fitting Model 1700 or 2700 transmitter Sensor wi t ...

  • Emerson F-SERIES SENSOR - page 7

    Sensor In stallation: F-Series 5 Before Y ou Begin Figure 3 F-Series sensor with junction box Junction bo x Approv al tag Flow direction arro w Approv al tag Process connection Calibration tag Purge fitting Purge fitting Junction bo x Sensor with purge fitt ings Calibration tag ...

  • Emerson F-SERIES SENSOR - page 8

    6 Sensor In stallation : F-Series Before Y ou Begin Figure 4 F-Series sensor with integra lly mounted IF T 9701 transmitter Calibration tag Flow direction arrow Model IFT9701 transmitter Approv al tag Process connection Model IFT9701 transmitter Approv al tag Calibration tag Purge fitting Purge fitting Sensor with purge fitt ings ...

  • Emerson F-SERIES SENSOR - page 9

    Sensor In stallation: F-Series 7 Before Y ou Begin Figure 5 High-temperature or extreme high-te mperature F-Series sensor with flexible conduit Flow direction arrow T ransmitter , core processo r , or junction box (core processor shown) Calibration tag Process connection Flex ible conduit Approv al tag ...

  • Emerson F-SERIES SENSOR - page 10

    8 Sensor In stallation : F-Series Determining a Location Step 1 Determining a Location Choose a location for the sensor based on the requirements descri bed in th is section. The foll o wing general guidelines can help you select an appropriate location fo r the sensor . Full flow tubes For op timal performance, the sensor tube s should remain full ...

  • Emerson F-SERIES SENSOR - page 11

    Sensor In stallation: F-Series 9 Determining a Locati on Figure 6 F-Series sensor ambie nt and process temperature limits (all models except high-temperature and extreme hig h-temperature models) Maximum process temperature in °F (°C) Mount electronics remote ly; use junction box –148 (–100) –112 (–80) –76 (–60) –40 (–40) –4 (? ...

  • Emerson F-SERIES SENSOR - page 12

    10 Sensor In stallation : F-Series Determining a Location Figure 7 F-Series sensor ambient an d process temperature limits (high-tempera ture and extreme high-temperature mo dels) Hazardous area approv als may impose additional limits on ambient and process temperature. For the A TEX “T” rating, refer to the A TEX documentation shipped w ith th ...

  • Emerson F-SERIES SENSOR - page 13

    Sensor In stallation: F-Series 11 Determining a Locati on Maximum wiring distances If the transmitter is mounted remote ly from the sensor , the maximum di stance between the sensor and transmitter depends on cable type. See T able 2. For high-temperat ure and extreme high-tempera ture F-Series sensors, note the follo wing: • For sensors with a M ...

  • Emerson F-SERIES SENSOR - page 14

    12 Sensor In stallation : F-Series Orientin g the Se nsor Step 2 Orienting the Sensor The sensor will function prop erly in an y orientation if the sensor tubes remain f illed with process fluid. Micro Motion reco mmends or ienting F-Series sensors as sho wn in Figure 8. Figure 8 Recommended se nsor orientations Self-draining applicati ons The F-Se ...

  • Emerson F-SERIES SENSOR - page 15

    Sensor In stallation: F-Series 13 Mounting the Se nsor Step 3 Mounting the Sensor Use your common practices to minimize torque and bendi ng load on process conn ections. Figure 9 illustrates ho w to mount the sensor . T o reduce the risk of co ndensation or excessi ve mois ture, the conduit opening should not point upward (if possib le). The condui ...

  • Emerson F-SERIES SENSOR - page 16

    14 Sensor In stallation : F-Series Mounting the Sensor Mounting the electronics of high-temperature and e xtreme high-temperature se nsors High-temperature and extreme high-tempera ture F-Series sensors come with a 32 ″ (812 mm) pre-installed flexible conduit. This conduit is required for agency appro v al. A factory- supplied Model 1700/2700 tra ...

  • Emerson F-SERIES SENSOR - page 17

    Sensor In stallation: F-Series 15 Wiring Step 4 Wiring Improperly sealed housings can expose electron ics to moisture, which can cause measurement err or or flowmeter failure. Inspect and grease all ga skets and O-rings. Fully close and tighten all housing cover s and conduit openings. Installation options The sensor has one o f the follo wi ng ele ...

  • Emerson F-SERIES SENSOR - page 18

    16 Sensor In stallation : F-Series Wiring Figure 11 Micro Motion cable gland an d heat shrink 4. For conn ection at the core processor housing, pr epare shielded cable as follo ws (for armored cable, omit steps d, e, f, and g): a. Strip 4 1/2 inches ( 114 mm) of cab le jack et. b . Remo v e the clear wrap that is inside the cable jack et, and remov ...

  • Emerson F-SERIES SENSOR - page 19

    Sensor In stallation: F-Series 17 Wiring Figure 13 Applying the heat shrink g. Position gland clamping inse rt so the interior end is flush with the heat shrink. h. Fold the cl oth shield or braid and drain wires o ver the clampin g insert and approximately 1/8 inch (3 mm) past the O-ring. Figure 14 Folding the cloth shield i. Install the gland bod ...

  • Emerson F-SERIES SENSOR - page 20

    18 Sensor In stallation : F-Series Wiring Figure 16 Connecting the wires at the core processor 7. Reinstall and tighten the co re processor housing co ver . 8. Additional wiring instructions for the tran smitter can be found in the transmitter manual. Note: Never gr ound the 4-wir e cable shield an d shield drain wir e(s) at the transmitter . Junct ...

  • Emerson F-SERIES SENSOR - page 21

    Sensor In stallation: F-Series 19 Grounding Step 5 Grounding The sensor can be groun ded via the piping if the joints in the pipeline are ground- bonded. If the sen sor is not grounded via the piping, con nect a ground wire to the in ternal or exter nal grounding scre w , which is located on the core processo r housing or junction box. Improper gr ...

  • Emerson F-SERIES SENSOR - page 22

    20 Sensor In stallation : F-Series Purge Fitt ings Purge Fittings If the sensor has pur ge fittings, the y should remain seal ed at all times. After a purge plug has been remo v ed, the sensor case should b e purged w ith ar gon or nitrogen and resealed. Purging the case protects internal components. The sensor is purged of all oxygen and sealed at ...

  • Emerson F-SERIES SENSOR - page 23

    Sensor In stallation: F-Series 21 Purge Fittings 8. Make sure the pur ge f itting seals are tight so air cannot be dra wn b y suction into the sensor case. Ta b l e 4 Time re quired to purge F-Se ries sensor cases Sensor model Purge rate ft 3 /hr (l/hr) Time (1) minutes (1) If pur ge lines ar e being used, incr ease pur ge time to f ill the additio ...

  • Emerson F-SERIES SENSOR - page 24

    22 Sensor In stallation : F-Series Return Policy Return Policy Micro Motion procedu res must be followed when retu rning equipment. These procedures ensure le gal compliance with go vernment transpor tation agencies and help pro vide a safe working en vironment for Micro Motion employees. F ailure to follo w Micro Motion proced ures will result in ...

  • Emerson F-SERIES SENSOR - page 25

    ...

  • Emerson F-SERIES SENSOR - page 26

    Micro Motion Inc. USA Worldwide Headqu arters 7070 Winchester Circle Boulder , Colorado 80301 T +1 303-527-5200 +1 800-522-6277 F +1 303-530-8459 Micro Motion Europe Emerson Process Management Neonstraat 1 6718 WX Ede The Netherlands T +31 (0) 318 495 555 F +31 (0) 318 495 556 Micro Motion Japan Emerson Process Management 1-2-5, Higashi Shinagawa S ...

Manufacturer Emerson Category Home Security System

Documents that we receive from a manufacturer of a Emerson F-SERIES SENSOR can be divided into several groups. They are, among others:
- Emerson technical drawings
- F-SERIES SENSOR manuals
- Emerson product data sheets
- information booklets
- or energy labels Emerson F-SERIES SENSOR
All of them are important, but the most important information from the point of view of use of the device are in the user manual Emerson F-SERIES SENSOR.

A group of documents referred to as user manuals is also divided into more specific types, such as: Installation manuals Emerson F-SERIES SENSOR, service manual, brief instructions and user manuals Emerson F-SERIES SENSOR. Depending on your needs, you should look for the document you need. In our website you can view the most popular manual of the product Emerson F-SERIES SENSOR.

Similar manuals

A complete manual for the device Emerson F-SERIES SENSOR, how should it look like?
A manual, also referred to as a user manual, or simply "instructions" is a technical document designed to assist in the use Emerson F-SERIES SENSOR by users. Manuals are usually written by a technical writer, but in a language understandable to all users of Emerson F-SERIES SENSOR.

A complete Emerson manual, should contain several basic components. Some of them are less important, such as: cover / title page or copyright page. However, the remaining part should provide us with information that is important from the point of view of the user.

1. Preface and tips on how to use the manual Emerson F-SERIES SENSOR - At the beginning of each manual we should find clues about how to use the guidelines. It should include information about the location of the Contents of the Emerson F-SERIES SENSOR, FAQ or common problems, i.e. places that are most often searched by users in each manual
2. Contents - index of all tips concerning the Emerson F-SERIES SENSOR, that we can find in the current document
3. Tips how to use the basic functions of the device Emerson F-SERIES SENSOR - which should help us in our first steps of using Emerson F-SERIES SENSOR
4. Troubleshooting - systematic sequence of activities that will help us diagnose and subsequently solve the most important problems with Emerson F-SERIES SENSOR
5. FAQ - Frequently Asked Questions
6. Contact detailsInformation about where to look for contact to the manufacturer/service of Emerson F-SERIES SENSOR in a specific country, if it was not possible to solve the problem on our own.

Do you have a question concerning Emerson F-SERIES SENSOR?

Use the form below

If you did not solve your problem by using a manual Emerson F-SERIES SENSOR, ask a question using the form below. If a user had a similar problem with Emerson F-SERIES SENSOR it is likely that he will want to share the way to solve it.

Copy the text from the picture

Comments (0)