    www.rosemount.com ¢00825-0100-4360N¤ Quick Installation Guid e 00825-0100-4593, Rev BA July 2009 Rosemount 1 151 Step 1: Mount the T ransmitter Step 2: Consider Housing Rotation Step 3: Connect the Wiring and Power Up Step 4: Set Switches Step 5: Configuration Step 6: T rim the T ransmitt er Product Certifications Sta r t End Rosemount 1 151 Pres ...

  • Emerson 00825-0100-4593 - page 2

    Quick Installation Guide 00825-0100-4593, Rev BA July 2009 Rosemount 1 151 2 W ARNING Explosions could result in death or serious injury: Installation of this tr ansmitter in a n explosive env iron ment must be in accordan ce wit h t he approp riat e local, national, and inter national st andards, code s, and pract ices. Please review the approval ...

  • Emerson 00825-0100-4593 - page 3

    Quick Installation Guid e 00825-0100-4593, Rev BA July 2009 Rosemount 1 151 3 S TE P 1: M OUNT THE T RANSMI TTER A. Applications Liquid Flow Application s 1. Place taps to the side of the line. 2. Mount beside or below the taps. Gas Flow Applicatio ns 1. Place taps in the top or side of the line. 2. Mount beside or above the taps. Steam Flow Applic ...

  • Emerson 00825-0100-4593 - page 4

    Quick Installation Guide 00825-0100-4593, Rev BA July 2009 Rosemount 1 151 4 S TE P 1 CONTI NUED ... B. Optional Mounting Brackets When installing the transmitter to one of the optional mounting brackets, torque the bracket bolts to 125 in.-lbs. (0,9 N-m). Pipe Mount Panel Mount (1) (1) Panel bolts are customer supplied. Flat Mount 4593_Rev_BA.fm P ...

  • Emerson 00825-0100-4593 - page 5

    Quick Installation Guid e 00825-0100-4593, Rev BA July 2009 Rosemount 1 151 5 S TE P 1 CONTI NUED ... C. O-rings with Flange Adapters W ARNING Whenever the flanges or adapters are removed, vi su ally inspect the o-rings. Replace them if there are any signs of damage, such as nicks or cuts. If you replace the o-rings, re-torque the flange bolts and ...

  • Emerson 00825-0100-4593 - page 6

    Quick Installation Guide 00825-0100-4593, Rev BA July 2009 Rosemount 1 151 6 S TE P 2: C ON SIDER H OUSING R OT ATION T o improve field access or to better view the optional LCD d isplay: 1. Loosen the housing lock nut. 2. Rotate the housing clockwise to the desired posit ion – up to 90° from its o riginal position. Over rotating will damage the ...

  • Emerson 00825-0100-4593 - page 7

    Quick Installation Guid e 00825-0100-4593, Rev BA July 2009 Rosemount 1 151 7 S TE P 3: C ON NECT THE W IRING AND P OWER U P Use the following steps to wire the transmitter: 1. Remove the housing cover on the side marked TERMINALS on the namepla te. 2. Connect the positive lead to the “+” termin a l and the negative lead to the “–” termin ...

  • Emerson 00825-0100-4593 - page 8

    Quick Installation Guide 00825-0100-4593, Rev BA July 2009 Rosemount 1 151 8 S TE P 3 CONTI NUED ... Power Supply The dc power supply should provide power with less than tw o percent ripple. The total resistance load is the sum of the resistance of the signal leads and the load resistance of the controller , indicator , and related pieces. Note tha ...

  • Emerson 00825-0100-4593 - page 9

    Quick Installation Guid e 00825-0100-4593, Rev BA July 2009 Rosemount 1 151 9 S TE P 4: C ON FIGURE THE T RANSMITTER Failure Mode Alarm Switch 1. Remove the housing cover . 2. Locate the failure mode switch (see Figure 3). 3. Move the switch to the desired alarm setting. T o set the failure mo de to high alarm, position the switch toward “HI.” ...

  • Emerson 00825-0100-4593 - page 10

    Quick Installation Guide 00825-0100-4593, Rev BA July 2009 Rosemount 1 151 10 S TE P 5: C AL IBRATE THE T RANSMITTER V erify T ransmitter Configuration NOTE: A check ( ✓ ) indicates the basic configuration para meters. At minimum, these parameters should be verified as part of the configuration and startup procedure. T able 1. HART Communicator F ...

  • Emerson 00825-0100-4593 - page 11

    Quick Installation Guid e 00825-0100-4593, Rev BA July 2009 Rosemount 1 151 11 S TE P 5 CONTI NUED ... Configure LCD Displa y Figure 4. Sample 1 151 LCD Display NOTE The LCD display time-out is approximately 16 se conds. If keys ar e not pressed within this period, the indicator reverts to reading the signal. Position the Decimal Point and Select t ...

  • Emerson 00825-0100-4593 - page 12

    Quick Installation Guide 00825-0100-4593, Rev BA July 2009 Rosemount 1 151 12 S TE P 5 CONTI NUED ... Set the Display Equivalent to a 4 mA Sign al 1. Unscrew the retaining ring shown in Figure 4 and remove the LCD display cover . 2. Press the left button for two seconds. 3. T o decrement the display numb ers, press the le ft configuration button an ...

  • Emerson 00825-0100-4593 - page 13

    Quick Installation Guid e 00825-0100-4593, Rev BA July 2009 Rosemount 1 151 13 S TE P 6: T RIM THE T RANSMITTE R NOTE T ransmitte rs are shipped fully calibrated per reques t or by the factory d efault of full scale (span = upper range limit). Full T rim A full trim is a two-point sensor calibrat ion where two end- point pressures are applied, and ...

  • Emerson 00825-0100-4593 - page 14

    Quick Installation Guide 00825-0100-4593, Rev BA July 2009 Rosemount 1 151 14 S TE P 6 CONTI NUED ... Using the T ransmitter Zero Adjustment Buttons Perform the following steps to perform a rerange using the zer o adjustment buttons (see Figure 3). 1. Apply a pressure equivalent to the lower calibra ted value on the high side of the transmitter . 2 ...

  • Emerson 00825-0100-4593 - page 15

    Quick Installation Guid e 00825-0100-4593, Rev BA July 2009 Rosemount 1 151 15 P RODUCT C E RTIFICATI ONS Approved Manufacturi ng Locations Rosemount Inc. — Chanhassen, Minnesota, USA Fisher-Rosemount Gmb H & Co. — Wessling, Germany Emerson Process Management Asia Pacific Private Limited — Singapore Beijing Rosemount Far East Instrument C ...

  • Emerson 00825-0100-4593 - page 16

    Quick Installation Guide 00825-0100-4593, Rev BA July 2009 Rosemount 1 151 16 Canadian Certifications Canadian St andards Association (CSA) Approvals E6 Explosion Proof for Class I, Division 1, Gr oups C and D; Class II, Division 1, Group s E, F , and G; Class III, Division 1 Hazardous Loc ations. Suit able fo r C la ss I , Di v is i on 2, Groups A ...

  • Emerson 00825-0100-4593 - page 17

    Quick Installation Guid e 00825-0100-4593, Rev BA July 2009 Rosemount 1 151 17 N1 A TEX T y pe N and Dust Certification Certificate Number: BAS99A TEX3293X A TEX Marking: II 3 GD Ex nL IIC T5 (-40 °C  T amb  40 °C) EX nL IIC T4 (-40 °C  T amb  80 °C) Dust Rating: T90 °C (T amb = -20 °C to 40 °C) Ui = 45 Vdc ma ximum IP66 Special ...

  • Emerson 00825-0100-4593 - page 18

    Quick Installation Guide 00825-0100-4593, Rev BA July 2009 Rosemount 1 151 18 N7 T ype N Certificate Number: Aus Ex 122X Ex n IIC T5 (T a = 80 °C) / T6 IP66 Special Conditions for safe use (x): 1. It is a condition of safe use that a nomi nal voltage of 30 V for Ex n application shall not be exceeded. 2. It is a condition of safe use that when the ...

  • Emerson 00825-0100-4593 - page 19

    Quick Installation Guid e 00825-0100-4593, Rev BA July 2009 Rosemount 1 151 19 DoC 4593_Rev_BA.fm Page 19 Friday, August 7, 2009 3:38 PM ...

  • Emerson 00825-0100-4593 - page 20

    Quick Installation Guide 00825-0100-4593, Rev BA July 2009 Rosemount 1 151 20 4593_Rev_BA.fm Page 20 Friday, August 7, 2009 3:38 PM ...

  • Emerson 00825-0100-4593 - page 21

    Quick Installation Guid e 00825-0100-4593, Rev BA July 2009 Rosemount 1 151 21 4593_Rev_BA.fm Page 21 Friday, August 7, 2009 3:38 PM ...

  • Emerson 00825-0100-4593 - page 22

    Quick Installation Guide 00825-0100-4593, Rev BA July 2009 Rosemount 1 151 22 4593_Rev_BA.fm Page 22 Friday, August 7, 2009 3:38 PM ...

Manufacturer Emerson Category Sleep Apnea Machine

Documents that we receive from a manufacturer of a Emerson 00825-0100-4593 can be divided into several groups. They are, among others:
- Emerson technical drawings
- 00825-0100-4593 manuals
- Emerson product data sheets
- information booklets
- or energy labels Emerson 00825-0100-4593
All of them are important, but the most important information from the point of view of use of the device are in the user manual Emerson 00825-0100-4593.

A group of documents referred to as user manuals is also divided into more specific types, such as: Installation manuals Emerson 00825-0100-4593, service manual, brief instructions and user manuals Emerson 00825-0100-4593. Depending on your needs, you should look for the document you need. In our website you can view the most popular manual of the product Emerson 00825-0100-4593.

Similar manuals

A complete manual for the device Emerson 00825-0100-4593, how should it look like?
A manual, also referred to as a user manual, or simply "instructions" is a technical document designed to assist in the use Emerson 00825-0100-4593 by users. Manuals are usually written by a technical writer, but in a language understandable to all users of Emerson 00825-0100-4593.

A complete Emerson manual, should contain several basic components. Some of them are less important, such as: cover / title page or copyright page. However, the remaining part should provide us with information that is important from the point of view of the user.

1. Preface and tips on how to use the manual Emerson 00825-0100-4593 - At the beginning of each manual we should find clues about how to use the guidelines. It should include information about the location of the Contents of the Emerson 00825-0100-4593, FAQ or common problems, i.e. places that are most often searched by users in each manual
2. Contents - index of all tips concerning the Emerson 00825-0100-4593, that we can find in the current document
3. Tips how to use the basic functions of the device Emerson 00825-0100-4593 - which should help us in our first steps of using Emerson 00825-0100-4593
4. Troubleshooting - systematic sequence of activities that will help us diagnose and subsequently solve the most important problems with Emerson 00825-0100-4593
5. FAQ - Frequently Asked Questions
6. Contact detailsInformation about where to look for contact to the manufacturer/service of Emerson 00825-0100-4593 in a specific country, if it was not possible to solve the problem on our own.

Do you have a question concerning Emerson 00825-0100-4593?

Use the form below

If you did not solve your problem by using a manual Emerson 00825-0100-4593, ask a question using the form below. If a user had a similar problem with Emerson 00825-0100-4593 it is likely that he will want to share the way to solve it.

Copy the text from the picture

Comments (0)