Siemens 6DS2-510-0xx00-0xa0 - page 1
s Program Libr ary Karlsr uhe Product Informatio n BRIDGE CS-L2 Var. V02.01 Issue: Februa ry, 1999 Descriptors TELEPERM M , BRIDGE CS-L2 , UPGRADE , UPDATE Summary The present Pro duct Informati on relates to the System Softwa re Package: Name Variant Product no. ( MLFB) BRIDGE CS-L2 V02.01 6DS2 510-0XX00 -0XA0 BRIDGE CS -L2 upgrade/upda te V02.01 ...
-
Siemens 6DS2-510-0xx00-0xa0 - page 2
Product Information February, 1999 BRIDGE CS-L2 Copyright © SIEM ENS AG 1996-1999. All R ights Reserved. S79220-A 0978-A-05-7637 Page 2 of 20 1 Scope The product informatio n for the system software V02.00 remains valid. The following information represents a supp lement. The delivery consists of: 6DS2 510-0XX00-0XA0 6DS2 510-0XX00 -0XB1 (Upgrade/ ...
-
Siemens 6DS2-510-0xx00-0xa0 - page 3
Product Information February, 1999 BRIDGE CS-L2 Copyright © SIEM ENS AG 1996-1999. All R ights Reserved. S79220-A 0978-A-05-7637 Page 3 of 20 2 Commissioning The Memory Ca rd contains th e entire system so ftware for the Bridg e (version V02.01) . To perform an upg rade or updat e from diskette, a BRIDGE CS-L2 memory ca rd must be available. The u ...
-
Siemens 6DS2-510-0xx00-0xa0 - page 4
Product Information February, 1999 BRIDGE CS-L2 Copyright © SIEM ENS AG 1996-1999. All R ights Reserved. S79220-A 0978-A-05-7637 Page 4 of 20 2.2 Procedure for Upgrade to V02. 01 wi th Programmi ng Device PG740 Switch o ff the pow er supply of the BR IDGE CS-L2 before pu lling th e memory card ! For the upgra de, insert the memor y card into the M ...
-
Siemens 6DS2-510-0xx00-0xa0 - page 5
Product Information February, 1999 BRIDGE CS-L2 Copyright © SIEM ENS AG 1996-1999. All R ights Reserved. S79220-A 0978-A-05-7637 Page 5 of 20 2.3 Procedure for Update V01.05 to V01.06 2.3.1 Update by Co mmissioning Terminal You will find t he files listed be low in the directory A: UPDATE.106 on the UPDATE disket te delivered to you. Copy th ese ...
-
Siemens 6DS2-510-0xx00-0xa0 - page 6
Product Information February, 1999 BRIDGE CS-L2 Copyright © SIEM ENS AG 1996-1999. All R ights Reserved. S79220-A 0978-A-05-7637 Page 6 of 20 2.3.2 Update by Programming Device PG740 Before start ing the UPDATE activities (pulling the memory card ), please ensure that a current back up of any f iles that are t o be modified exists. This will allow ...
-
Siemens 6DS2-510-0xx00-0xa0 - page 7
Product Information February, 1999 BRIDGE CS-L2 Copyright © SIEM ENS AG 1996-1999. All R ights Reserved. S79220-A 0978-A-05-7637 Page 7 of 20 3.1 Removed Errors (a lready with V02.00) • F: Time synchronization A: Time telegrams were not always tra nsmitted at high pri ority. In exceptio nal circumstances several time telegrams w ith differen t t ...
-
Siemens 6DS2-510-0xx00-0xa0 - page 8
Product Information February, 1999 BRIDGE CS-L2 Copyright © SIEM ENS AG 1996-1999. All R ights Reserved. S79220-A 0978-A-05-7637 Page 8 of 20 Caution: When upgrading the bridge syst em software care must be ta ken that the bus coupling module TPM47 8 is version 5 or later, ot herwise all error co rrections will not be ef fective. 4 Extended Functi ...
-
Siemens 6DS2-510-0xx00-0xa0 - page 9
Product Information February, 1999 BRIDGE CS-L2 Copyright © SIEM ENS AG 1996-1999. All R ights Reserved. S79220-A 0978-A-05-7637 Page 9 of 20 4.1 Configurat ion of the BRIDGE CS-L2 w ith CPU 486-3 and IF964-DP As the CPU 488-4 is re placed by the CPU 486-3 and the CP54 12-A1 is replace d by the IF964-DP inter face module, t here are the f ollowing ...
-
Siemens 6DS2-510-0xx00-0xa0 - page 10
Product Information February, 1999 BRIDGE CS-L2 Copyright © SIEM ENS AG 1996-1999. All R ights Reserved. S79220-A 0978-A-05-7637 Page 10 of 20 4.2 Instruct ions on installi ng the CPU 486-3 • The hardware ve rsion of the CPU 486-3 mu st be at least 2. Earlier v ersions can cause serious error s in the functions that use an interface module. • ...
-
Siemens 6DS2-510-0xx00-0xa0 - page 11
Product Information February, 1999 BRIDGE CS-L2 Copyright © SIEM ENS AG 1996-1999. All R ights Reserved. S79220-A 0978-A-05-7637 Page 11 of 20 5 Limited operating performance No safety-r elevant f aults are currently known; t he known fault s are assigned t o fault class 3 and lower. • W hen using the loa d RAM funct ion of PROGRAF AS+ by means ...
-
Siemens 6DS2-510-0xx00-0xa0 - page 12
Product Information February, 1999 BRIDGE CS-L2 Copyright © SIEM ENS AG 1996-1999. All R ights Reserved. S79220-A 0978-A-05-7637 Page 12 of 20 6 Configuration of the bus con nections The paramete rs for th e BRIDGE CS-L2 ar e set in the configuration files BR_SYS.INI, DOS_CONF.DAT (or L2AMPRO.INI) and SYS_PAR.I NI . ) Subsequent paramete rs for BR ...
-
Siemens 6DS2-510-0xx00-0xa0 - page 13
Product Information February, 1999 BRIDGE CS-L2 Copyright © SIEM ENS AG 1996-1999. All R ights Reserved. S79220-A 0978-A-05-7637 Page 13 of 20 6.1 Parameter of configuration file BR_SYS.INI Parameter ADR=xxxx Address of th e Dual-Port- RAM of the TPM 478 C600 = standard system setting (hex adecimal) Parameter DPR=xx Addre ss of the register of the ...
-
Siemens 6DS2-510-0xx00-0xa0 - page 14
Product Information February, 1999 BRIDGE CS-L2 Copyright © SIEM ENS AG 1996-1999. All R ights Reserved. S79220-A 0978-A-05-7637 Page 14 of 20 6.2 Parameter of configuration file DOS_CONF.DAT for CP5412-A1 The configu ration file DOS_CONF.DAT includes the PROFIBUS- TM bus paramete rs. A specificat ion of slot co ordinates is not necessary. Bus par ...
-
Siemens 6DS2-510-0xx00-0xa0 - page 15
Product Information February, 1999 BRIDGE CS-L2 Copyright © SIEM ENS AG 1996-1999. All R ights Reserved. S79220-A 0978-A-05-7637 Page 15 of 20 Example of a configuration file DOS_CONF.DAT: ___________ ___________ ____________ ___________ ______ # FILE FOR INSTALLING TF/IHI DRIVER # INSTTOOL VERSION = V 2.20 02.11.93 numboards = 1 boardtyp = 5412 S ...
-
Siemens 6DS2-510-0xx00-0xa0 - page 16
Product Information February, 1999 BRIDGE CS-L2 Copyright © SIEM ENS AG 1996-1999. All R ights Reserved. S79220-A 0978-A-05-7637 Page 16 of 20 The parameter assignmen ts 'int_vector=12' an d 'dpram_adr=0x D0000', with w hich the interru pt and DPRAM addre ss range are set, agree with the default set tings of the bridge s and th ...
-
Siemens 6DS2-510-0xx00-0xa0 - page 17
Product Information February, 1999 BRIDGE CS-L2 Copyright © SIEM ENS AG 1996-1999. All R ights Reserved. S79220-A 0978-A-05-7637 Page 17 of 20 according to the following equat ion and entered : l2_ttr = 9000 * [number of a ctive PROFIB US-TM station s]. Note: Th e factor 9000 in th e equation only applies to a baud rate of 1.5 MBaud. All bus param ...
-
Siemens 6DS2-510-0xx00-0xa0 - page 18
Product Information February, 1999 BRIDGE CS-L2 Copyright © SIEM ENS AG 1996-1999. All R ights Reserved. S79220-A 0978-A-05-7637 Page 18 of 20 6.4 Parameter of configuration file SYS_PAR.INI The configuration file SYS_PAR.INI includes the parameter fo r inverting o f the DIO- In/Outpu ts. If the file SYS_PAR.INI is not present, the operation syste ...
-
Siemens 6DS2-510-0xx00-0xa0 - page 19
Product Information February, 1999 BRIDGE CS-L2 Copyright © SIEM ENS AG 1996-1999. All R ights Reserved. S79220-A 0978-A-05-7637 Page 19 of 20 7 Connector Pin Assignment IF961-DIO Following I & C Signals are available on IF961-DI O module: Function Assignment of the Outputs Output Pin Root 0V Signalling output Use Remark DO 0 DO 1 10 13 Common ...
-
Siemens 6DS2-510-0xx00-0xa0 - page 20
Product Information February, 1999 BRIDGE CS-L2 Copyright © SIEM ENS AG 1996-1999. All R ights Reserved. S79220-A 0978-A-05-7637 Page 20 of 20 8 Status displa y and error messag es • The lamp tes t (all LEDs on) is not activated whe n switching on the net work, but only with master-reset a nd soft-reset. • If the memory card is pull ed during ...
Do you have a question concerning Siemens 6DS2-510-0xx00-0xa0?
Use the form below
If you did not solve your problem by using a manual Siemens 6DS2-510-0xx00-0xa0, ask a question using the form below. If a user had a similar problem with Siemens 6DS2-510-0xx00-0xa0 it is likely that he will want to share the way to solve it.