  • Honeywell PCR-300 RC - page 1

    PCR -300 PCR -300 RC Installation and Oper ating Instructions Electronic refrigeration contr ol EB-PCR-04 EN 1H-1924GE23 R 1207 ...

  • Honeywell PCR-300 RC - page 2

    2 T ABLE OF C ONTENTS 1 1 Unpac king t he unit and conditions of use 3 1 2 Gener al instructions 3 1 3 Use and function 3 3. 1 Use for the purpose int ended 3 3.2 Function 4 1 4 Safety 4 4. 1 Sources of danger 4 4.2 Safety precautions 5 1 5 Installation and commissioning 5 5. 1 Mechanical installation 5 5.2 Electrical installation 6 5.3 Setting the ...

  • Honeywell PCR-300 RC - page 3

    3 1 Un packing t he unit and conditions of use Before and when unpacking the unit, mak e a visual inspection to identify any possible damage which may ha ve occurred during transportation. Please look for loose par ts, dents, scratches, etc. Report any damage immediately to the freight company . (Please see “Conditions if damage has occurred”.) ...

  • Honeywell PCR-300 RC - page 4

    I The controller must not be used as a safety cut-out device or e xcess temper ature limiter . If the controller is used for purposes other t han those stated here, it shall not be considered to be use for the purpose intended. I Only connect sensors supplied with the unit. If a replacement sen- sor is required, only use sensors of the same type (p ...

  • Honeywell PCR-300 RC - page 5

    I Never e xpose the unit to ex cessive heat, dust and vibrations. A void knocks and pressure loads. If the housing is damaged, there is a risk of an electric shock causing death or injur y . I If the unit cannot be operat ed without the risk of dang er , it must be tak en out of ser vice and precautions taken so that it cannot be switched on again ...

  • Honeywell PCR-300 RC - page 6

    6 a) housing with 2 mounting tabs: open out the later al mounting tabs; clip the unit on the 35 mm rail and press tabs in again. b) housings with 1 mounting tab: put housing on the upper 35 mm rail. Clip the unit on the 35 mm rail, lo wer tab clips on the rail aut omatically. T o remove the unit from the rail pr ess in lower mounting tab with a scr ...

  • Honeywell PCR-300 RC - page 7

    7 T erminal: Description: 1 - 2 T1 = Cold store sensor 3 - 4 T2 = Evapor ator sensor 1 0 - 1 2 Mains = Pow er supply 1 3 - 1 5 V = Compressor contactor (cooling) 1 7 - 18 Ev = Evapor ator fan (contactor) 20 - 2 1 Alarm = Remot e alarm indicator; indicat or lamp or contactor (with R C-element) 23 - 24 Def = Defrost heating (contactor) or hot gas v a ...

  • Honeywell PCR-300 RC - page 8

    8 5.3 Setting the DIP switc h for the emergency setpoint and t he clock bac k-up battery Carefully lif t the housing cover off the side, using your fingers. I Selection of the emergency setpoint for the cold store temper ature: This will be activat ed if the data in the memor y is los t and alarm AL1 is activat ed. This se ts all progr am paramet e ...

  • Honeywell PCR-300 RC - page 9

    ☛ Note: It tak es approximately 2 4 hour s for the battery to achiev e its full back -up capacity . The battery will provide cov er for a power failure of appr oximat ely 1 month. 6 Operation of the controller Fr ont view of controller: 6. 1 Switching on t he operating v oltage The controller is star ted by means of a contr ol switch provided b y ...

  • Honeywell PCR-300 RC - page 10

    Three spot indicators show the switching status of the rela ys during operation: Pos. 1: On : Compr essor relay on. Of f: Compressor relay off. Flashes: Compressor star t-up delay E05 activ e. Pos. 2: On : Ev aporator f an relay on. Of f: Evapor ator fan rela y of f. Pos. 3: On : Defr ost relay on. Of f: Defrost relay off. Flashes: Drain time E09 i ...

  • Honeywell PCR-300 RC - page 11

    1 1 u Access the first programming le vel by pressing the and k eys at the same time for 5 seconds. u Then use the and k eys to access the paramet er s to be changed. u Access the second programming le vel by pressing the and and k eys simultaneously for 5 seconds. I T o exit from the progr amming levels and sav e the data, press the ke y af ter th ...

  • Honeywell PCR-300 RC - page 12

    If the set temper ature dif ference E03 is negativ e, an alarm is given if it is too cold in the refriger ated area, e.g. E03 = –1 0 K, cold s tore setpoint = –1 8 °C ➝ alarm at –28 °C in refrigerat ed area. If the set temper ature dif ference E03 is positiv e, the alarm is given if it is too w arm in the refrigerated area, e.g. E03 = +1 ...

  • Honeywell PCR-300 RC - page 13

    6.7 Manual defrosting Press and hold down the k ey for 5 seconds. The manual defrosting process will be initiated. 7 Progr amming Access to the second programming le vel: I Press and hold down the , and k eys at the same time for approx. 5 seconds (Display: E01 f or PCR -300, E00 for PCR-300RC). I Use or k ey to select paramet er s. I Setting: Pres ...

  • Honeywell PCR-300 RC - page 14

    1 4 The time is entered in increments of 1 0 minutes in each case . Impor tant : The times must be entered in ascending order . E03 Alarm temper ature dif ference –50 K to + 50 K 20 K E04 Delay time – Alarm 0 to 99 mins. 1 0 mins. E05 Compressor star t-up delay 0 to 1 5 mins. 5 mins. E06 Defrost type 1 or 2 1 1 = Electrical (compressor of f) 2 ...

  • Honeywell PCR-300 RC - page 15

    1 5 E1 5 Sensor calibration T1 –5 t o +5 K 0 K (cold store) E1 6 Sensor calibration T2 –5 t o +5 K 0 K (ev aporator) E1 7 Operation of 0 = Relay de-energizes 2 compressor relay 1 = Rela y is perma- if cold store sensor T1 nently engergized is defective 2 = Alternat ely ener- gized/de-ener- gized according to time set in E1 8 and E1 9. E1 8 “O ...

  • Honeywell PCR-300 RC - page 16

    1 6 8 Maintenance The controller does not require an y maintenance. It does not ha ve any fuses so, if brief voltage spik es occur , the refrigeration system will not stop operating f or a prolonged period. Once the disturbance has passed, the controller will automatically start up again. Cleaning the housing: Only a dr y anti-static cloth may be u ...

  • Honeywell PCR-300 RC - page 17

    Clearing alarm: Press the k ey . All alarm messages, with the exception of AL2, are also r eset by switching of f the operating v oltage. AL2 can only be reset using the ke y. 1 0 Pr oblem solving F ault Cause Remedy Evapor ator fan does not Evapor ator Refit switch on during sensor T2 has sensor . cooling when the fallen out of programmed setting ...

  • Honeywell PCR-300 RC - page 18

    1 8 1 2 T ec hnical data Mains voltage/frequency 230 V A C ± 10% / 50/60 Hz Rated w attage 2.5 w atts Display 3-digit, 7-segment, red LED, 1 4.2 mm Resolution 1 K Measuring range –55 to +50 °C Outputs 1 relay with changeo ver contact, 8 A, 230 V A C, resistive load, (cooling). 1 relay with N.O. contact, 8 A (5A PCR-300RC), 230 V A C, resistive ...

  • Honeywell PCR-300 RC - page 19

    1 9 EC Declar ation of Conformity as defined in the EMC Directives 89/336/EEC and the EC Low V oltage Directives 73/23/EEC Product : FLICA , electronic coldstore control Model designation: PRC-300, PCR-300RC has been dev eloped, designed and manufactured in accordance with the EC Standards listed abo ve. The f ollowing harmonized S tandards have be ...

  • Honeywell PCR-300 RC - page 20

    Automati on and Contro l Solution s Honeywell GmbH Hardhofweg • 74821 Mosbach / Germany Phone: +49 (0) 62 61 / 81-475 Fax: +49 (0) 62 61 / 81-461 E-Mail: Cooling.Mosbach@honeywell.com www.honeywell-cooling.com Manufactured for and on behalf of the Environment and Combustion Controls Division of Honeywell Technologies Sàrl, Ecublens, Route du Boi ...

Manufacturer Honeywell Category Refrigerator

Documents that we receive from a manufacturer of a Honeywell PCR-300 RC can be divided into several groups. They are, among others:
- Honeywell technical drawings
- PCR-300 RC manuals
- Honeywell product data sheets
- information booklets
- or energy labels Honeywell PCR-300 RC
All of them are important, but the most important information from the point of view of use of the device are in the user manual Honeywell PCR-300 RC.

A group of documents referred to as user manuals is also divided into more specific types, such as: Installation manuals Honeywell PCR-300 RC, service manual, brief instructions and user manuals Honeywell PCR-300 RC. Depending on your needs, you should look for the document you need. In our website you can view the most popular manual of the product Honeywell PCR-300 RC.

Similar manuals

A complete manual for the device Honeywell PCR-300 RC, how should it look like?
A manual, also referred to as a user manual, or simply "instructions" is a technical document designed to assist in the use Honeywell PCR-300 RC by users. Manuals are usually written by a technical writer, but in a language understandable to all users of Honeywell PCR-300 RC.

A complete Honeywell manual, should contain several basic components. Some of them are less important, such as: cover / title page or copyright page. However, the remaining part should provide us with information that is important from the point of view of the user.

1. Preface and tips on how to use the manual Honeywell PCR-300 RC - At the beginning of each manual we should find clues about how to use the guidelines. It should include information about the location of the Contents of the Honeywell PCR-300 RC, FAQ or common problems, i.e. places that are most often searched by users in each manual
2. Contents - index of all tips concerning the Honeywell PCR-300 RC, that we can find in the current document
3. Tips how to use the basic functions of the device Honeywell PCR-300 RC - which should help us in our first steps of using Honeywell PCR-300 RC
4. Troubleshooting - systematic sequence of activities that will help us diagnose and subsequently solve the most important problems with Honeywell PCR-300 RC
5. FAQ - Frequently Asked Questions