    www.rosemount.com ¢00825-0100-4716/¤ Quick Installation Guid e 00825-0100-4716, Rev DA October 2009 Rosemount 3095 MultiV ariable Sta r t End Step 1: Mount the T ransmitter Step 2: T ransmitter Installation Step 3: Sof tware Installation Step 4: Connect the Wiring and Power Up ( HART or Fieldbus) Step 5: Configure the T ransmitter ( HART or Field ...

  • Emerson 00825-0100-4716 - page 2

    Quick Installation Guide 00825-0100-4716, Rev DA October 2009 Rosemount 3095 MultiV aria ble 2 © 2009 Rosemo unt Inc. All rights re served. All marks property o f owner. Rosemount and the Rosemount logotype are registered trad emarks of Rosemount Inc. Rosemount Inc. 8200 Market B oulevard Chanhassen, M N USA 55317 T (US) (800) 999 -9 30 7, F (952) ...

  • Emerson 00825-0100-4716 - page 3

    Quick Installation Guid e 00825-0100-4716, Rev DA October 2009 Rosemount 3095 MultiV ariable 3 T RANS MITTER E XPLODED V IEW Housing O-ring Cover Housing Locking Screw RTD Connector Process Adapter O-ring Electronics Board Nameplate Module O-ring Sensor Module Drain/V ent Valve Flange Adapter O-ring Optional Flange Adapters Bolts Coplanar Flange Ce ...

  • Emerson 00825-0100-4716 - page 4

    Quick Installation Guide 00825-0100-4716, Rev DA October 2009 Rosemount 3095 MultiV aria ble 4 S TE P 1: M OUNT THE T RANSMITTER Figure 1. Using a Mounting Bracke t Liquid Flow Application s 1. Place taps to the side of the line. 2. Mount beside or below the taps. 3. Mount the transmitter so that the drain/vent valves are oriented upwar d. Gas Flow ...

  • Emerson 00825-0100-4716 - page 5

    Quick Installation Guid e 00825-0100-4716, Rev DA October 2009 Rosemount 3095 MultiV ariable 5 S TE P 2: T RANSMITT ER I NS TALLATIO N Consider Housin g Rotation T o improve field access or to better view the optional LCD displa y: 1. Loosen the housing rotation set screw . 2. Rotate the housing clockwise to the desired position – up to 180° fro ...

  • Emerson 00825-0100-4716 - page 6

    Quick Installation Guide 00825-0100-4716, Rev DA October 2009 Rosemount 3095 MultiV aria ble 6 S TE P 2 CONTI NUED ... 3. Set the Failure Mode Alarm (HART devices), which is located on the front of the electronics board inside the electronics housing cover . T he Alar m Jumper position determines if the output is driven high or lo w when a failur e ...

  • Emerson 00825-0100-4716 - page 7

    Quick Installation Guid e 00825-0100-4716, Rev DA October 2009 Rosemount 3095 MultiV ariable 7 S TE P 2 CONTI NUED ... • Installing a Shielded 3095 RTD Cable (See Figure 4) Note: Shielded cable is intended for use in a conduit. a. Fully engage the black cable connector to the 3 095 R TD Connector. b. T i ghten the cable adapter until metal cont a ...

  • Emerson 00825-0100-4716 - page 8

    Quick Installation Guide 00825-0100-4716, Rev DA October 2009 Rosemount 3095 MultiV aria ble 8 S TE P 2 CONTI NUED ... Bolting Considerations If the transmitter installation requires assembly of the process flanges , manifolds, or flange adapters, follow these assembly guidelines to ensure a tight seal for optimal performance characteristics of the ...

  • Emerson 00825-0100-4716 - page 9

    Quick Installation Guid e 00825-0100-4716, Rev DA October 2009 Rosemount 3095 MultiV ariable 9 S TE P 2 CONTI NUED ... Figure 7. T orque values for the flange and flan ge adapter bolts O-rings with Flange Adapters W ARNING Whenever the flanges or adapters are removed, vi su ally inspect the o-rings. Replace them if there are any signs of damage, su ...

  • Emerson 00825-0100-4716 - page 10

    Quick Installation Guide 00825-0100-4716, Rev DA October 2009 Rosemount 3095 MultiV aria ble 10 S TE P 3: S OFTWARE I NSTALLATION The 3095 Engineering Assistant (EA) for HA RT and 3095 Engineering Assistant (EA) for FOUNDA TION Fieldbus software programs can be installed on the same computer . The applications cannot be open simultaneously . 3095 E ...

  • Emerson 00825-0100-4716 - page 11

    Quick Installation Guid e 00825-0100-4716, Rev DA October 2009 Rosemount 3095 MultiV ariable 11 S TE P 3 CONTI NUED ... Installing the HART Modem After installing the 3095 Engineering Assist ant, the HAR T mo dem configuration window automatically appears when the 3095 Engineering Assistant is opened. If this window is canceled, the HART modem may ...

  • Emerson 00825-0100-4716 - page 12

    Quick Installation Guide 00825-0100-4716, Rev DA October 2009 Rosemount 3095 MultiV aria ble 12 S TE P 4: C ON NECT W IRING AND P OWER U P (HART) S TE P 4: C ON NECT W IRING AND P OWER U P (HART) Use the following steps to wire the transmitter: 1. Remove the housing cover on the side marked FIELD TERMINALS. 2. Connect the signal leads to the termin ...

  • Emerson 00825-0100-4716 - page 13

    Quick Installation Guid e 00825-0100-4716, Rev DA October 2009 Rosemount 3095 MultiV ariable 13 S TE P 4: C ON NECT W IRING AND P OWER U P (F IELDBUS ) Use the following steps to wire the transmitter: 1. Remove the housing cover labeled “Field T erm inals.” T erminals are no t polarity sensitive. 2. Connect the signal leads to the te rminals la ...

  • Emerson 00825-0100-4716 - page 14

    Quick Installation Guide 00825-0100-4716, Rev DA October 2009 Rosemount 3095 MultiV aria ble 14 S TE P 5: C ON FIGURE THE T RANSMITTER (HART) Setting the Lo op to Manu al Set the process application loop to manual when preparing to send or request data that would disrupt the loop or change the output of the tra nsmitter . A prompt will appear remin ...

  • Emerson 00825-0100-4716 - page 15

    Quick Installation Guid e 00825-0100-4716, Rev DA October 2009 Rosemount 3095 MultiV ariable 15 DP Sens T rim 1, 2, 2, 1, 1 DP Snsr Range 1, 3, 5, 1 DP URV 5 DP units 1, 3, 2, 1 Date 1, 3, 4, 4 Descri ptor 1, 3, 4, 2 Diff p res damp 1, 4, 2, 4 Diff pres 1, 1, 1 Diff pres 2 Fld dev rev 1, 3, 4, 9, 2 Flo rate 1, 1, 4, 5 Flow Rate S pecial Units 1, 4, ...

  • Emerson 00825-0100-4716 - page 16

    Quick Installation Guide 00825-0100-4716, Rev DA October 2009 Rosemount 3095 MultiV aria ble 16 S TE P 5: C ON FIGURE THE T RANSMITTER (F IELDBUS ) Each F OUNDATION fieldbus host or configuration tool has a different way of displaying and performing configuratio ns. Some use Device Descriptions (DD) or DD methods for configuration and to display da ...

  • Emerson 00825-0100-4716 - page 17

    Quick Installation Guid e 00825-0100-4716, Rev DA October 2009 Rosemount 3095 MultiV ariable 17 S TE P 6: T RIM THE T RANSMITTE R NOTE T ransmitte rs are shipped from Emerson Process Management fully calibrated and configured for the application when C2 Option is ordered. Without C2 Option, configuration will be by the factory default (span = upper ...

  • Emerson 00825-0100-4716 - page 18

    Quick Installation Guide 00825-0100-4716, Rev DA October 2009 Rosemount 3095 MultiV aria ble 18 P RODUCT C E RTIFICATIONS Rosemount 3095 with HART Approved Manufacturi ng Locations Rosemount Inc. — Chanhassen, Minnesota USA Emerson Process Management GmbH & Co. — Wessling, Germany Emerson Process Management Asia Pa cific Private Limited — ...

  • Emerson 00825-0100-4716 - page 19

    Quick Installation Guid e 00825-0100-4716, Rev DA October 2009 Rosemount 3095 MultiV ariable 19 Canadian St andards A ssociation (C SA) C Explosion Proof for Class I, Divi sion 1, Groups B, C, and D. Dust-Ignition Proof for Class II/Class III, Division 1, Groups E, F , and G . CSA enclosure T ype 4X suitable for indoor and outdoor hazardous locatio ...

  • Emerson 00825-0100-4716 - page 20

    Quick Installation Guide 00825-0100-4716, Rev DA October 2009 Rosemount 3095 MultiV aria ble 20 G A TEX Type n Certificate Number: BAS98A TEX3360X II 3 G Ex nL IIC T5 (T amb = –45 °C to 40 °C) Ex nL IIC T4 (T amb = –45 °C to 70 °C) U i = 55V The apparatus is designed for connect ion to a remote temperature sensor such as a resistance temper ...

  • Emerson 00825-0100-4716 - page 21

    Quick Installation Guid e 00825-0100-4716, Rev DA October 2009 Rosemount 3095 MultiV ariable 21 The capacitance and either the Induct ance or the Induct ance to Resistance Ratio ( L/R) of the load connected to the 4-pin connecto r must not exceed the following values: NOTE 1. The external circuit contains no comb ined lumped inductance and capacita ...

  • Emerson 00825-0100-4716 - page 22

    Quick Installation Guide 00825-0100-4716, Rev DA October 2009 Rosemount 3095 MultiV aria ble 22 China (NEPSI) Certifications 2 China Intrinsic Safety Ex ia IIC T4 Special conditions for safe use (x): 1. 3095 Series transmitter with temperature sensor h ave not been certified. 2. The temperature of process medium should be less than 121 °C. 3. The ...

  • Emerson 00825-0100-4716 - page 23

    Quick Installation Guid e 00825-0100-4716, Rev DA October 2009 Rosemount 3095 MultiV ariable 23 1 1. When inst allation, use and maintenance transmitter , observe the f ollowing st andards GB3836.13-1997 “Electrical apparatus for explosive gas atmospheres Part 13: Repair and overhaul for apparatus us ed in explosive gas atmospheres” GB3836.15-2 ...

  • Emerson 00825-0100-4716 - page 24

    Quick Installation Guide 00825-0100-4716, Rev DA October 2009 Rosemount 3095 MultiV aria ble 24 Combinations of Certifications S tainless steel certification t ag is provided when optional appr oval is specified. Once a device labeled with multiple approval types is installed, it shou ld not be r einst alled using any other approval types. Permanen ...

  • Emerson 00825-0100-4716 - page 25

    Quick Installation Guid e 00825-0100-4716, Rev DA October 2009 Rosemount 3095 MultiV ariable 25 Rosemount 3095 Fieldbus Hazardou s Lo ca ti ons Certifications North American Cert ifications FM Approvals A Explosion Proof for Class I, Divi sion 1, Groups B, C, and D. Dust-Ignition Proof for Class II/Class III, Division 1, Groups E, F , and G . Enclo ...

  • Emerson 00825-0100-4716 - page 26

    Quick Installation Guide 00825-0100-4716, Rev DA October 2009 Rosemount 3095 MultiV aria ble 26 Special conditions for safe use (x): V ersions of the apparatus fitted with the transient protected terminals are not capable of withstanding the 500 volts insulation test required by Clause 6.4.12 of EN 50020:2002. This must be taken into account when i ...

  • Emerson 00825-0100-4716 - page 27

    Quick Installation Guid e 00825-0100-4716, Rev DA October 2009 Rosemount 3095 MultiV ariable 27 P A TEX Dust Certificate Number: KEMA02A TEX2321 II 1 D T90°C (-50°C  T amb  80°C) Vmax = 55 Vdc Imax = 23 mA IP66 11 8 0 IECEx Certifications (Fieldbus) 4/Y IECEx Intrinsic Safety Certificate Number: IECEx BAS05.0023X Ex ia IIC T4 (-45°C  T ...

  • Emerson 00825-0100-4716 - page 28

    Quick Installation Guide 00825-0100-4716, Rev DA October 2009 Rosemount 3095 MultiV aria ble 28 7 IECEx Flameproof Certificate Number: IECEx KEM 06.0018 Zone 0/1 Ex d IIC T6 (-20°C  T a  65°C) Zone 0/1 Ex d IIC T5 (-20°C  T a  80°C) V max = 55 Vdc I max = 23 mAdc 8 IECEx Dust Certificate Number: IECEx KEM 06.0018 Ex tD A22 T90°C IP ...

  • Emerson 00825-0100-4716 - page 29

    Quick Installation Guid e 00825-0100-4716, Rev DA October 2009 Rosemount 3095 MultiV ariable 29 ...

  • Emerson 00825-0100-4716 - page 30

    Quick Installation Guide 00825-0100-4716, Rev DA October 2009 Rosemount 3095 MultiV aria ble 30 ...

  • Emerson 00825-0100-4716 - page 31

    Quick Installation Guid e 00825-0100-4716, Rev DA October 2009 Rosemount 3095 MultiV ariable 31 ...

  • Emerson 00825-0100-4716 - page 32

    Quick Installation Guide 00825-0100-4716, Rev DA October 2009 Rosemount 3095 MultiV aria ble 32 ...

Manufacturer Emerson Category Marine Instruments

Documents that we receive from a manufacturer of a Emerson 00825-0100-4716 can be divided into several groups. They are, among others:
- Emerson technical drawings
- 00825-0100-4716 manuals
- Emerson product data sheets
- information booklets
- or energy labels Emerson 00825-0100-4716
All of them are important, but the most important information from the point of view of use of the device are in the user manual Emerson 00825-0100-4716.

A group of documents referred to as user manuals is also divided into more specific types, such as: Installation manuals Emerson 00825-0100-4716, service manual, brief instructions and user manuals Emerson 00825-0100-4716. Depending on your needs, you should look for the document you need. In our website you can view the most popular manual of the product Emerson 00825-0100-4716.

A complete manual for the device Emerson 00825-0100-4716, how should it look like?
A manual, also referred to as a user manual, or simply "instructions" is a technical document designed to assist in the use Emerson 00825-0100-4716 by users. Manuals are usually written by a technical writer, but in a language understandable to all users of Emerson 00825-0100-4716.

A complete Emerson manual, should contain several basic components. Some of them are less important, such as: cover / title page or copyright page. However, the remaining part should provide us with information that is important from the point of view of the user.

1. Preface and tips on how to use the manual Emerson 00825-0100-4716 - At the beginning of each manual we should find clues about how to use the guidelines. It should include information about the location of the Contents of the Emerson 00825-0100-4716, FAQ or common problems, i.e. places that are most often searched by users in each manual
2. Contents - index of all tips concerning the Emerson 00825-0100-4716, that we can find in the current document
3. Tips how to use the basic functions of the device Emerson 00825-0100-4716 - which should help us in our first steps of using Emerson 00825-0100-4716
4. Troubleshooting - systematic sequence of activities that will help us diagnose and subsequently solve the most important problems with Emerson 00825-0100-4716
5. FAQ - Frequently Asked Questions
6. Contact detailsInformation about where to look for contact to the manufacturer/service of Emerson 00825-0100-4716 in a specific country, if it was not possible to solve the problem on our own.

Do you have a question concerning Emerson 00825-0100-4716?

Use the form below

If you did not solve your problem by using a manual Emerson 00825-0100-4716, ask a question using the form below. If a user had a similar problem with Emerson 00825-0100-4716 it is likely that he will want to share the way to solve it.

Copy the text from the picture

Comments (0)