Manual Lindy Carbon Monoxide Alarm

60 pages 1.98 mb
Download

Go to site of 60

Summary
  • Lindy Carbon Monoxide Alarm - page 1

    User Manual for Rack Monitoring System Monitoring System Rack Monitoring System ...

  • Lindy Carbon Monoxide Alarm - page 2

    SAFE WORKING Important passages which must be observed are highlighted with the following symbols: Danger Calls attention to safety measures to pr event personal injury Note Recommends actions and provides tips for trouble-free operation Caution! Highlights what must be done or not done in order not to damage material assets. Attention The Rms LITE ...

  • Lindy Carbon Monoxide Alarm - page 3

    C ONTENTS 3 C ONTENTS This user manual applies exclusively to the RMS Rack Monitoring System. Software version: 2.0 – Illuminated LCD display for plain text displays – 4 keys on the front of the device – Measurement and monitoring of temperatur e, humidity , door contact (access), vibration, movement (infrared r oom surveillance), smoke, main ...

  • Lindy Carbon Monoxide Alarm - page 4

    C ONTENTS C ONTENTS 1 1 1 3 Please note T echnical description Installation and commissioning Operation Example configuration Malfunctions T echnical data Glossary Appendices 1.1 General information 05 1.2 Safe working 06 1.3 W arranty 06 1.4 Service 07 1.5 Standards, r egulations and licence 07 2.1 Rack monitoring 08 2.2 Sensors 09 3.1 Preparation ...

  • Lindy Carbon Monoxide Alarm - page 5

    5 P LEASE NOTE P LEASE NOTE 1.1 GENERAL INFORMA TION Normal use Copyright T echnical status Liability SAFE WORKING Danger Cauntion Note Attention 0The RMS is supplied in flawless condition in terms of safety . LINDY can only guarantee the safety , reliability and performance of the device if: • modifications, conversions or repairs ar e carried o ...

  • Lindy Carbon Monoxide Alarm - page 6

    1 Rack P LEASE NOTE P LEASE NOTE 1.2.2 1.2.3 1.3 General Saftey Information Disposal W ARRANTY Lapse of warranty For safe operation of the RMS please ensure you r ead all of this user manual and that you observe the instructions and information contained in it. Please also observe other documentation by manufacturers of connected devices. • Alway ...

  • Lindy Carbon Monoxide Alarm - page 7

    7 1 P LEASE N OTE P LEASE N OTE 1 Monitoring System Rack Monitoring System 1.4 1.5 SERVICE HOTLINE E-MAIL ST ANDARDS, REGULA TIONS AND LICENCE LICENCE In the event of malfunction, please first follow the instructions in the relevant section (> 5). For all other questions, please do not hesitate to contact LINDY technical support.  DE: 0621 / ...

  • Lindy Carbon Monoxide Alarm - page 8

    Rack 2.1 RACK MONITORING Sensors Display Inputs and outputs Operation and configuration Software The RMS monitors, protects and contr ols all the installations in net- work, switch cabinet and server racks and their environment. Local ambient conditions (for example, temperature or humidity) or operational status (for example fluctuations in mains ...

  • Lindy Carbon Monoxide Alarm - page 9

    9 1 Monitoring System Rack Monitoring System T ECHNICAL D ESCRIPTION T ECHNICAL D ESCRIPTION 2 2.2 Connection options SENSORS T emperature (digital) Humidity (digital) Combined Humidity and T emperature sensor (digital) Vibration Smoke alram The RMS has a wide variety of connection options ( > 3.3.1): A Three mains monitoring connections (6-pole ...

  • Lindy Carbon Monoxide Alarm - page 10

    T ECHNICAL D ESCRIPTION T ECHNICAL D ESCRIPTION 2 Rack Door Contact Chipcard r eader Infrared r oom surveillance Extension cable W ater sensor Mains Power Strips Note Monitors access using a magnetic bridge sensor which responds to any magnetic material (no contact requir ed). – Also for monitoring side panels or cover – Cable length: 4 m – M ...

  • Lindy Carbon Monoxide Alarm - page 11

    I NST ALLA TION AND COMMISSIONING I NST ALLA TION AND COMMISSIONING 3 11 Monitoring System Rack Monitoring System 3.1 3.1.3 3.1.2 PREP ARA TIONS Check the supplied items T ransport Damage Danger Necessary Accessories Note Necessary T ools – RMS – Power cable (for the country in question) – User‘s Manual – 6 plug connectors If the device h ...

  • Lindy Carbon Monoxide Alarm - page 12

    I NST ALLA TION AND COMMISSIONING I NST ALLA TION AND COMMISSIONING 3 Rack 19'' installation Caution! Note When installing the RMS in a rack, the additional requir ements in accordance with IEC 950 must be observed and complied with! • Determine the position in which the RMS is to be located within the 19" rack. Observe the existin ...

  • Lindy Carbon Monoxide Alarm - page 13

    I NST ALLA TION AND COMMISSIONING I NST ALLA TION AND COMMISSIONING 3 13 Monitoring System Rack Monitoring System 3.3.1 3.3 ELECTRICAL INST ALLA TION Connections and cabling Connection Cabling Mains montoring Digital Out 1 Fuse plug > 3.3.3 2 Mains Connections > 3.3.2 3 MAINS MONITORING Mains monitoring connections 4 DIGIT AL OUT Digital swit ...

  • Lindy Carbon Monoxide Alarm - page 14

    I NST ALLA TION AND COMMISSIONING I NST ALLA TION AND COMMISSIONING 3 Rack DIGIT AL IN Note ALERT IN TEMPERA TURE/HUMIDITY UPS IN 10BASET – 8 terminal groups (of 4 terminals) for connecting 'br eak contact/make contact' type devices, or devices with switching output – Potential-free, digital – Left terminal pair “IN+” AND “IN- ...

  • Lindy Carbon Monoxide Alarm - page 15

    I NST ALLA TION AND COMMISSIONING I NST ALLA TION AND COMMISSIONING 3 15 Monitoring System Rack Monitoring System COM AUX Cable protection (optional) • Mount the cable clamp bracket • Fix the cables with suitable aids (cable binders, etc.) to the sheet metal lugs (serves as a cable grip). • Insert the cover in the slots on the device, close t ...

  • Lindy Carbon Monoxide Alarm - page 16

    I NST ALLA TION AND COMMISSIONING I NST ALLA TION AND COMMISSIONING 3 Rack 3.3.2 3.4 Fuses Double -pole fuse / fuse of the neutral wire Caution! Danger! Fuse for the auxiliary voltage supply COMMISSIONING Mains Socket Fire risk. Only replace fuses with fuses of the same type (250 V , 1 A, slow-acting, high switching • Switch off the device and un ...

  • Lindy Carbon Monoxide Alarm - page 17

    1 Reset Resets the RMS to a defined standard state ( > 5 ). 2 LED "Fault" (red) lights, up in connection with reset,overload or a serious sys- tem fault. “W ar ning“ (yellow) lights up if the conditions of an appropriately configured filter apply (> 4.9 ), when booting and in connection with Reset. “Power“ (green) lights up ...

  • Lindy Carbon Monoxide Alarm - page 18

    Rack 4.3 OPERA TION VIA KEYS ON THE FRONT OF THE DEVICE Selecting a menu item The functions accessible via the keys are mainly displays, i.e. curr ent statuses are displayed without the possibility of entering data. Exception: menu items under “Network – Interface”.” • Change from the initial state to the menu level using the MENU key . ? ...

  • Lindy Carbon Monoxide Alarm - page 19

    19 Monitoring System Rack Monitoring System Filter messages Display in the “Confirm“ menu Entering network parameters Filter messages are displayed on the LCD display as follows: <Message number> (2-digit) blank <Time> (2-digit) <Unit of time> (s; m = min; h; d) Blank <Filter -designation> (9-digit) • Confirm filter me ...

  • Lindy Carbon Monoxide Alarm - page 20

    O PERA TION O PERA TION 4 Rack 4.4 OPERA TION VIA TELNET OR SERIAL INTERF ACE COM Note Note All the settings in the RMS can easily be made via T elnet or via the serial interface (COM). COM parameters: 9600 baud, 8 data bits, no parity , 1 stop bit, soft- ware handshake. Never connect both COM interfaces at the same time! Create a T elnet connectio ...

  • Lindy Carbon Monoxide Alarm - page 21

    O PERA TION O PERA TION 4 21 Monitoring System Rack Monitoring System M AIN MENU From the main menu it is possible to switch to the various submenus. References to sub-menus ar e marked with “>” [N] N ETWORK C ONFIGURA TION Network and SNMP settings (> 4.5 ). [S] S YSTEM C ONFIGURA TION AND U PDA TE Load and save system configuration and ...

  • Lindy Carbon Monoxide Alarm - page 22

    O PERA TION O PERA TION 4 Rack Block diagram The signals applied at the physical input terminals (left) ar e combined in a complex filter structure (centr e). The resulting filter result can then be supplied for switching and signalling purposes at physical output termi- nals (right) or be used to influence other filters (feedback). Method of opera ...

  • Lindy Carbon Monoxide Alarm - page 23

    O PERA TION O PERA TION 4 23 1 Monitoring System Rack Monitoring System 4.5 Network Configuration Note Central input mask for settings for the Ethernet interface. References to sub-menus ar e marked with “>”. The Ethernet interface makes it possible to integrate the RMS into a local network (10 Mbit Ethernet), thus making the following funct ...

  • Lindy Carbon Monoxide Alarm - page 24

    Rack 4.5.1 (SNMP CONFIGURA TION) Complete control of the RMS via SNMP with alarm (trap function) and support of separate communities for read and write operations. SNMP V1 in accordance with RFC 1213 is implemented. MIB-II including RMS private MIB is supported. The complete MIB file of the RMS is on the supplied CD-ROM. Explanation of the MIB vari ...

  • Lindy Carbon Monoxide Alarm - page 25

    25 Monitoring System Rack Monitoring System O PERA TION O PERA TION 4 4.5.2 4.6 L OG S ERVICE Specify receivers of log messages in the network which support the standardised syslog service (UNIXServer). T wo types of messages can be logged via the syslog service: – Filter results similar to the displays under [M] Message Log in the main menu (> ...

  • Lindy Carbon Monoxide Alarm - page 26

    Rack 4.6.1 4.6.2 CONFIGURA TION VIA TFTP T ool for saving the system configuration in the network and thus capturing it in a central data backup. The loading allows rapid startup without reparameterisation, for example after a system failure. This requir es that the TFTP service is running on the computer stated (TFTP server). • Please contact yo ...

  • Lindy Carbon Monoxide Alarm - page 27

    27 Monitoring System Rack Monitoring System O PERA TION O PERA TION 4 4.7 User Administration Input mask to set up users with access rights. All users are displayed with their user names, passwords and rights as well as their chipcard code, if applicable. Note [A] A DD U SER Add new user . [D] D ELETE U SER Delete selected user (-->) [-] P REVIO ...

  • Lindy Carbon Monoxide Alarm - page 28

    Rack 4.8 I/O C ONFIGURA TION Input mask for the digital input and output settings. References to sub-menus ar e marked with “>”. [O] D IGIT AL O UTPUTS Configure digital outputs. [I] D IGIT AL I NPUTS Configure digital inputs. [T] T EMPERA TURE I NPUTS Configure temperatur e (sensor) inputs. [H] H UMIDITY I NPUTS Configure humidity (sensor) ...

  • Lindy Carbon Monoxide Alarm - page 29

    29 Monitoring System Rack Monitoring System O PERA TION O PERA TION 4 4.8.1 DIGIT AL OUTPUTS Input mask for the DIGIT AL OUT digital outputs settings. Digital outputs are displayed with the number , description, combi- ned filters, logic operation and effect. F OR CONFIGURA TION WITH THE CHIPCARD READER ONL Y If the chipcard r eader has been activa ...

  • Lindy Carbon Monoxide Alarm - page 30

    Rack 4.8.2 4.8.3 DIGIT AL INPUTS Displays the DIGIT AL IN, ALERT IN and UPS IN digital inputs with the number , description, status (on/off), number of status chan- ges and time of the last change. TEMPERA TURE INPUTS Displays the TEMPERA TURE/HUMIDITY digital temperature inputs with the number , description and current value. [D] D ESCRIPTION Desc ...

  • Lindy Carbon Monoxide Alarm - page 31

    31 Monitoring System Rack Monitoring System O PERA TION O PERA TION 4 4.8.4 4.8.5 HUMIDITY INPUTS Displays the TEMPERA TURE/ HUMIDITY digital humidity inputs with the description and current value. MAINS MONITORING Displays the MAINS MONITORING digital inputs with the number , description and current value. [D] D ESCRIPTION Description of the humid ...

  • Lindy Carbon Monoxide Alarm - page 32

    Rack 4.8.6 CONNECT EXTERNAL DEVICES VIA SERIAL INTERF ACE (AUX) Devices with a serial interface (for example chipcard r eader , UPS, etc.) can be connected to the AUX port on the rear of the RMS. Software version 1.4 can support a chipcar d reader to implement an access control system. [U] U PDA TE S CREEN Update the screen.. [D] AUX D EVICE S ELEC ...

  • Lindy Carbon Monoxide Alarm - page 33

    33 Monitoring System Rack Monitoring System O PERA TION O PERA TION 4 4.8.7 AUX DEVICE SELECTION Note [-] Previous Device Set the selection pointer to the previous device. [+] Next Device Set the selection pointer to the next device. [?] Help Explanation of the menu points. [Q] Quit Return to the previous menu. [Return] Quit With Saving Save the ch ...

  • Lindy Carbon Monoxide Alarm - page 34

    Rack 4.9 FIL TER Mode of operation The filters are the central elements of the RMS. They make it it possible to logically combine the results r ecorded at the inputs, and to supply the result to the digital outputs or to generate various signals. It is possible to configure a total of 12 filters (RMS Advanced 40) with an identical structure. In thi ...

  • Lindy Carbon Monoxide Alarm - page 35

    35 Monitoring System Rack Monitoring System O PERA TION O PERA TION 4 4.9.1 4.9.2 FIL TER SELECTION All filters are displayed with the number , description, status, result, reactivation time and confirmation status. F IL TER C ONFIGURA TION References to sub-menus ar e marked with “>”. A “(*)” before the “>” indicates that at leas ...

  • Lindy Carbon Monoxide Alarm - page 36

    O PERA TION O PERA TION 4 Rack 4.9.3 DIGIT AL/ALERT/UPS INPUTS The inputs are displayed with the type, number , description and effect. [L] LED W ARNING In connection with an event switch the LED on "W ar ning" [B] B UZZER W ARNING In connection with an event, switch on the buzzer . [M] M ESSAGE P RIORITY Characterises the priority of the ...

  • Lindy Carbon Monoxide Alarm - page 37

    O PERA TION O PERA TION 4 37 Monitoring System Rack Monitoring System 4.9.4 TEMPERA TURE/MAINS/HUMIDITY INPUTS The filter inputs for measured values are displayed with the threshold, mode and ef fect. They have a flexible structure for the creation of larger/smaller comparisons or window compari- sons. Thus the following filter conditi- ons can eas ...

  • Lindy Carbon Monoxide Alarm - page 38

    O PERA TION O PERA TION 4 Rack 4.9.5 [-] Previous Feedback Input Selection pointer to previous input. [+] N EXT F EEDBACK I NPUT Selection pointer to next input. [F] F IL TER Origin of the feedback. [D] D ELA Y T IME Set the delay time after the operation of the input event f 1 in s. [H] H OLD T IME Set the hold time of f 2 after the release of f 1 ...

  • Lindy Carbon Monoxide Alarm - page 39

    O PERA TION O PERA TION 4 39 Monitoring System Rack Monitoring System 4.10 MESSAGE LOG The messages are displayed with the number , priority , acknowled- gement, spent time and filter description. A maximum of the 15 last messages can be displayed. [A] A CKNOWLEDGE Select message acknowledged (mark with x). [-] P REVIOUS M ESSAGE Selection pointer ...

  • Lindy Carbon Monoxide Alarm - page 40

    E XAMPLE CONFIGURA TION E XAMPLE CONFIGURA TION 5 Rack Preconfigur ed filters with an example of terminal assign- ment. • Connect sensors to the suggested terminals. Example of filter configuration using filter 1 (temperature). • Activate the filter by setting the respective ef fect to “thru” or “invert” (preset: “of f”). • Make i ...

  • Lindy Carbon Monoxide Alarm - page 41

    E XAMPLE CONFIGURA TION E XAMPLE CONFIGURA TION 5 41 Monitoring System Rack Monitoring System TEMPERA TURE/HUMIDITY input 3 with window comparison: Alarm if humidity < 35 % or > 60% relative humidity . See also > 4.9.4 . MAINS inputs 1 to 3 with window comparison: Alarm if U < 200 V or U > 245 V .See also > 4.9.4. ALERT IN inputs ...

  • Lindy Carbon Monoxide Alarm - page 42

    E XAMPLE CONFIGURA TION E XAMPLE CONFIGURA TION 5 Rack DIGIT AL IN input 1: Alarm if passive infrared sensor operates. See also > 4.9.3. DIGIT AL IN input 2: Alarm if door is open for longer than 60 s. In the Filter Configuration menu, set effect to “thru” for filter 7. In the Feedback Input menu, set effect to “thru” for filter 8. See a ...

  • Lindy Carbon Monoxide Alarm - page 43

    E XAMPLE CONFIGURA TION E XAMPLE CONFIGURA TION 5 43 Monitoring System Rack Monitoring System Limited alarm duration for filter 4: Internal buzzer active for 5 seconds if filter 4 (smoke and shock sensor) is active Set input for filter 10 Effect to “thru” in the Feedback menu.. Specimen output configuration Additional fan on DIGIT AL OUT 1: act ...

  • Lindy Carbon Monoxide Alarm - page 44

    E XAMPLE CONFIGURA TION E XAMPLE CONFIGURA TION 5 Rack T wo filters are r equired for this (copy of an RS flip-flop using NOR gate array). ...

  • Lindy Carbon Monoxide Alarm - page 45

    M ALFUNCTIONS M ALFUNCTIONS 6 45 Monitoring System Rack Monitoring System Caution In the event of malfunctions System no longer starts. The “Fault” LED lights up, the sensors do not work, “Overload” is displayed in the LCD display . If the malfunction still occurs after performing the remedial measur es If, during operation, the “Power” ...

  • Lindy Carbon Monoxide Alarm - page 46

    7 TECHNICAL DA T A TECHNICAL DA T A Rack RMS dimensions Weight Rated voltage Rated frequency Rated current Protection class Rated ambient temperature External (WxDxH): 483 x 223 x 43.6mm Mounting dimensions (WxDxH): 445 x 218 x 43.6mm 3.5 kg AC 110 – 230 V 50/60 Hz 200 mA I 5 . . . 35 ° ...

  • Lindy Carbon Monoxide Alarm - page 47

    G LOSSAR Y G LOSSAR Y 8 47 Monitoring System Rack Monitoring System 19" Construction Broadcast EMC FA Q Gateway HE IP MIB Netmask RFC SNMP TFTP T rap URL VDE 19-inch construction is the common name for a standardised modular system for electronic devices and system parts. It specifies the width of the front panel of plug-in units and subracks. ...

  • Lindy Carbon Monoxide Alarm - page 48

    A PPENDICES A PPENDICES Rack A1 Conformity Manufacturer LINDY -Elektronik GmbH Markircher Str . 20 D-68229 Mannheim, Germany Product designation Data T erminal Equipment Model Remote Managment System The product conforms to the r egulations of the following EU Directive: 73/23/EEC. The conformity of the product to the r equirements of Directive 89/ ...

  • Lindy Carbon Monoxide Alarm - page 49

    A PPENDICES A PPENDICES 49 Monitoring System Rack Monitoring System A2 DOCUMENT A TION OF THE SYSTEM CONFIGURA TION • Mark the cables of your RMS at both ends clearly with meaningful markings. Use cable binders with marking areas or labels with sealing film. • The following block diagram (master) can be used for documenta- tion of the filter co ...

  • Lindy Carbon Monoxide Alarm - page 50

    A PPENDICES A PPENDICES Rack A3 EXPLANA TION OF THE MIB FOR RMS Structure of the MIB Key to the following T ables: INT Integer CNT Counter DS Display String OS Octet String TT TimeT icks RO Read Only RW Read Write Objects under RMS system (1.3.6.1.4.1.1909.10.1) for example Reset RMS 1.3.6.1.4.1.1909.10.1.4.0 := 1 The RMS can be accessed under the ...

  • Lindy Carbon Monoxide Alarm - page 51

    A PPENDICES A PPENDICES 51 Monitoring System Rack Monitoring System Objects under digitalInTable (1.3.6.1.4.1.1909.10.2.1) for example: number of changes of input 9: 1.3.6.1.4.1.1909.10.2.1.1.5.9 Objects under alertInTable (1.3.6.1.4.1.1909.10.2.2) for example : Reset sensors on Alert In 2 1.3.6.1.4.1.1909.10.2.2.1.3.2 := 1 Object under ups I N T A ...

  • Lindy Carbon Monoxide Alarm - page 52

    A PPENDICES A PPENDICES Rack Objects under outputTable (1.3.6.1.4.1.1909.10.3.1) for example: Read put description DIGIT AL OUT 4: 1.3.6.1.4.1.1909.10.3.1.1.2.4 Objects under outputLogicTable (1.3.6.1.4.1.1909.10.3.2) Objects under tempTable (1.3.6.1.4.1.1909.10.4.1) for example: Read out current tempertur e of temperature sensor 1: 1.3.6.1.4.1.190 ...

  • Lindy Carbon Monoxide Alarm - page 53

    A PPENDICES A PPENDICES 53 Monitoring System Rack Monitoring System Objects under mainsTable (1.3.6.1.4.1.1909.10.6.1) Objects under filterTable (1.3.6.1.4.1.1909.10.7.1) for example: allow confirmation for filter 4 1.3.6.1.4.1.1909.10.7.1.1.9.4 := 1 Objects under filterDigitalInTable (1.3.6.1.4.1.1909.10.7.2) for examle : Make DIGTIAL INPUT 2 act ...

  • Lindy Carbon Monoxide Alarm - page 54

    A PPENDICES A PPENDICES Rack Objects under filterAlertInT able (1.3.6.1.4.1.1909.10.7.3) Objects under filterUPSInTable (1.3.6.1.4.1.1909.10.7.4) Objects under filterTempTable (1.3.6.1.4.1.1909.10.7.5) for example: Exclude TEMPERA TURE/HUMIDITY input from Filter 1 1.3.6.1.4.1.1909.10.7.5.1.3.1.2 := 0 Objects under filterHumidityTable (1.3.6.1.4.1.1 ...

  • Lindy Carbon Monoxide Alarm - page 55

    A PPENDICES A PPENDICES 55 Monitoring System Rack Monitoring System Objects under filterMainsTable (1.3.6.1.4.1.1909.10.7.7) Objects under filterFeedbackTable (1.3.6.1.4.1.1909.10.7.8) For example: Feedback input 1 of filter 8 is only to operate if the event is still applied: 1.3.6.1.4.1.1909.10.7.8.1.5.8.1 := 1 Objects under messageTable (1.3.6.1. ...

  • Lindy Carbon Monoxide Alarm - page 56

    A PPENDICES A PPENDICES Rack Objects under userTable (1.3.6.1.4.1.1909.10.9.1) Objects under aux (1.3.6.1.4.1.1909.10.20) Objects under icc (1.3.6.1.4.1.1909.10.21) V ariable T ype V alue Access 1 userEntry 1 userIndex INT RO 2 userName DS RO 3 userRight INT { readonly (1), RO read-write (2)} 4 userChipcardKey DS RO 5 userChipcardAccess INT { denie ...

  • Lindy Carbon Monoxide Alarm - page 57

    A PPENDICES A PPENDICES 57 Monitoring System Rack Monitoring System A4 GNU GENERAL PUBLIC LICENSE V ersion 2, June 1991, Copyright (C) 1989, 1991 Free Software Foundation, Inc., 59 T emple Place - Suite 330, Boston, MA 02111-1307, USA Everyone is permitted to copy and distribute ver- batim copies of this license document, but chan- ging it is not a ...

  • Lindy Carbon Monoxide Alarm - page 58

    A PPENDICES A PPENDICES Remo Rack under this License. Any attempt otherwise to copy , modify , sublicense or distribute the Program is void, and will automatically terminate your rights under this License. However , parties who have received copies, or rights, from you under this License will not have their licenses terminated so long as such par- ...

  • Lindy Carbon Monoxide Alarm - page 59

    ote Managemnet System Remote Management System Monitoring System Rack Monitoring System P RODUCT M A TRIX P RODUCT M A TRIX 59 T ype RMS LITE RMS ADV ANCED Feature S peed 25 mhz 33 mhz Flash 8mb 32mb Housing 19” IHE 19” IHE Front LCD Display no yes Front Keypad no yes S tatus LED’s yes yes Buzzer yes yes Power supply range 1 10/230 V AC 1 10/ ...

  • Lindy Carbon Monoxide Alarm - page 60

    Rack International & Eire LINDY International Ltd. Sadler Forster W ay T eesside Industrial Estate, Thor naby Stockton-on-T ees TS17 9JY , England T el: +44 1642 - 754020 Fax: +44 1642 - 754029 E-Mail: Postmaster@lindy .com Italia LINDY Italia S.r .l. Via V aresina, 126/B 22079 - Villa Guar dia (CO) T el: 031 48 40 11 Fax: 031 48 06 52 E-Mail: ...

Manufacturer Lindy Category Carbon Monoxide Alarm

Documents that we receive from a manufacturer of a Lindy Carbon Monoxide Alarm can be divided into several groups. They are, among others:
- Lindy technical drawings
- Carbon Monoxide Alarm manuals
- Lindy product data sheets
- information booklets
- or energy labels Lindy Carbon Monoxide Alarm
All of them are important, but the most important information from the point of view of use of the device are in the user manual Lindy Carbon Monoxide Alarm.

A group of documents referred to as user manuals is also divided into more specific types, such as: Installation manuals Lindy Carbon Monoxide Alarm, service manual, brief instructions and user manuals Lindy Carbon Monoxide Alarm. Depending on your needs, you should look for the document you need. In our website you can view the most popular manual of the product Lindy Carbon Monoxide Alarm.

Similar manuals

A complete manual for the device Lindy Carbon Monoxide Alarm, how should it look like?
A manual, also referred to as a user manual, or simply "instructions" is a technical document designed to assist in the use Lindy Carbon Monoxide Alarm by users. Manuals are usually written by a technical writer, but in a language understandable to all users of Lindy Carbon Monoxide Alarm.

A complete Lindy manual, should contain several basic components. Some of them are less important, such as: cover / title page or copyright page. However, the remaining part should provide us with information that is important from the point of view of the user.

1. Preface and tips on how to use the manual Lindy Carbon Monoxide Alarm - At the beginning of each manual we should find clues about how to use the guidelines. It should include information about the location of the Contents of the Lindy Carbon Monoxide Alarm, FAQ or common problems, i.e. places that are most often searched by users in each manual
2. Contents - index of all tips concerning the Lindy Carbon Monoxide Alarm, that we can find in the current document
3. Tips how to use the basic functions of the device Lindy Carbon Monoxide Alarm - which should help us in our first steps of using Lindy Carbon Monoxide Alarm
4. Troubleshooting - systematic sequence of activities that will help us diagnose and subsequently solve the most important problems with Lindy Carbon Monoxide Alarm
5. FAQ - Frequently Asked Questions
6. Contact detailsInformation about where to look for contact to the manufacturer/service of Lindy Carbon Monoxide Alarm in a specific country, if it was not possible to solve the problem on our own.

Do you have a question concerning Lindy Carbon Monoxide Alarm?

Use the form below

If you did not solve your problem by using a manual Lindy Carbon Monoxide Alarm, ask a question using the form below. If a user had a similar problem with Lindy Carbon Monoxide Alarm it is likely that he will want to share the way to solve it.

Copy the text from the picture

Comments (0)