    All information contained herein is subject to change without notice. I NST ALLA TION I NSTRUCTIONS F OR C OMMERCIAL H EA TING & C OOLING 15 & 20 T ON P ACKAGE G AS S ERIES CPG S ERIES RECOGNIZE THIS SYMBOL AS A SAFETY PRECAUTION. A TTENTION INST ALLING PERSONNEL Prior to installation, thoroughly familiarize yourself with this Installation ...

  • Goodman Mfg ANSI Z21.47CSA-2.3 - page 2

    2 REPLACEMENT PARTS O RDERING P ARTS When reporting shortages or damages, or ordering rep air part s, give the complete unit model and serial numbers as stamped on the unit’ s nameplate. Replacement parts for this appliance are available through your contractor or local distributor . For the location of your nearest distributor , consult the whit ...

  • Goodman Mfg ANSI Z21.47CSA-2.3 - page 3

    3 T HIS  PRODU CT  CO NTAI N S  OR  PRODU CES  A  CHEM IC AL  OR  CHEM IC ALS  WHICH  MAY  CA US E  SERIO US  ILLNESS  OR  DEATH  AND  WHICH  ARE  KNO WN  TO  THE  S TATE  OF  C ALIFORNIA  TO  CA US E  CA N CER ,  BIR TH  DEFECT S  OR  OT HER  RE PR OD U ...

  • Goodman Mfg ANSI Z21.47CSA-2.3 - page 4

    4 System design and installation should also, where applicable, follow information presented in accepted industry guides such as the ASHRAE Handbooks. The manufacturer assumes no responsibility for equipment installed in violation of any code or regulation. The mechanical inst allation of the packaged roof top units consist s of making final connec ...

  • Goodman Mfg ANSI Z21.47CSA-2.3 - page 5

    5 • The combustion air inlet and flue outlet on the unit must never be obstructed. If used, do not allow the economizer/manual fresh air damper/ motorized fresh air damper to become blocked by snow or debris. In some climates or locations, it may be necessary to elevate the unit to avoid these problems. • When the unit is heating, the temperatu ...

  • Goodman Mfg ANSI Z21.47CSA-2.3 - page 6

    6 LIFT OVE R APPROXIMA TE CENTER OF UN IT SPREADER BA RS MUST BE USED WIT H LIFT ING ST RAPS THAT ARE LESS THAN 16 FEET L ONG RE MO VE 2 BRAC KE T S ON EACH EN D T O REMOVE WOO DEN ST RU TS RE MO VE 2 BRAC KE T S ON EACH EN D T O REMOVE SH IPP I NG BR AC E 3. Lift unit per the “Rigging Details” section of this manual, observing all warnings and ...

  • Goodman Mfg ANSI Z21.47CSA-2.3 - page 7

    7 removal, to allow service access and to insure proper venti- lation and condenser airflow . The unit must not be installed beneath any obstruction. The unit should be inst alled re- mote from all building exhausts to inhibit ingestion of exhaust air into the unit fresh air intake. INS ULA TED PA N E L S ROOF CURB INSTALLATION ROOF CURB POST -INST ...

  • Goodman Mfg ANSI Z21.47CSA-2.3 - page 8

    8 W HEN  UNIT  IS  SU SPE NDE D ,  BOARDS  AND  SHI PPI NG  BRACE  WILL  DROP  WHEN  SC REW S  ARE  REMO VED .  T O  PREVENT  PERSONAL  INJ URY ,  ST AND  CL EAR . R EM OVE  FORK  HOLE  BR ACKETS ,  BOARDS  AND  SHI PPI NG  BRACE  FR OM  BOTTOM OF  UNIT  BE ...

  • Goodman Mfg ANSI Z21.47CSA-2.3 - page 9

    9 All line voltage connections must be made through weather- proof fittings. All exterior power supply and ground wiring must be in approved weatherproof conduit. The main power supply wiring to the unit and low voltage wiring to accessory controls must be done in accordance with these instructions, the latest edition of the National Electrical Cod ...

  • Goodman Mfg ANSI Z21.47CSA-2.3 - page 10

    10 ELECTRICAL ENTRANCE LOCATIONS Unit is equipped with a Low V oltage T erminal Block and has Single Point wiring to the contactor . L OW V OLTAGE C ONTROL W IRING 1. A 24V thermost at must be installed for unit operation. It may be purchased with the unit or field -supplied. Thermostat s may be programmable or electromechanical as required. 2. Loc ...

  • Goodman Mfg ANSI Z21.47CSA-2.3 - page 11

    11 Natural Gas Connection Len g th of Pipe in F eet 1/2 3/4 1 1 1/4 1 1/2 10 132 278 520 1050 1600 20 92 190 350 730 1100 30 73 152 285 590 980 40 63 130 245 500 760 50 56 115 215 440 670 60 50 105 195 400 610 70 46 96 180 370 560 80 43 90 170 350 530 90 40 84 160 320 490 100 38 79 150 305 460 Pressure = .50 P SIG or le ss and Pressu re Drop of 0. ...

  • Goodman Mfg ANSI Z21.47CSA-2.3 - page 12

    12 G AS P IPING C HECKS T O  PREVEN T  PROP ER TY  DAMAGE  OR  PER SONAL  INJURY  DUE  TO  FIRE ,  THE  FOLL OWI NG  INS TRUCTIONS  MUST  BE  PERF ORME D  RE GA R D I N G  GAS  CONNECTIONS  AND  PRE SSUR E  TESTI N G :  •   T HE  UNIT  AND  ITS  GAS  CONNECT ...

  • Goodman Mfg ANSI Z21.47CSA-2.3 - page 13

    13 NOTE: The gas connection size at the unit does NOT establish the size of the supply line. 3. These units are designed for either natural or prop ane (LP) gas and are specifically constructed at the factory for only one of these fuels. The fuels are NOT interchangeable. However , the furnace can be converted in the field from natural gas to LP ga ...

  • Goodman Mfg ANSI Z21.47CSA-2.3 - page 14

    14 ST ARTUP , ADJUSTMENTS, AND CHECKS HIG H  VO L T AG E ! T O  AVOID  PER SONAL  INJURY  OR  DEATH  DUE  TO  ELECT RICAL  SHOCK ,  BOND  THE  FRAM E  OF  THI S  UNIT  TO  THE  BUI LDI NG  ELECTR ICAL  GROUND  BY  USE  OF  THE  GROUNDING  TERM IN AL  PROV IDE D  ...

  • Goodman Mfg ANSI Z21.47CSA-2.3 - page 15

    15 System V olt age - That nominal voltage value assigned to a circuit or system for the purpose of designating its volt age class. Nameplate V olt age - That voltage assigned to a piece of equipment for the purpose of designating its voltage class and for the purpose of defining the minimum and maximum voltage at which the equipment will operate. ...

  • Goodman Mfg ANSI Z21.47CSA-2.3 - page 16

    16 Check tension frequently during the first 24 hours of opera- tion. Subsequent retensioning should fall between the mini- mum and maximum force. T o determine the deflection dis- tance from the normal position, use a straightedge or stretch a cord from sheave to sheave to use as a reference line. On multiple belt drives, an adjacent undeflected b ...

  • Goodman Mfg ANSI Z21.47CSA-2.3 - page 17

    17 With Power And Gas On: 2. Put unit into heating cycle and turn on all other gas consuming appliances. NATURAL M in . 5. 0" W . C . , M ax . 10 .0" W . C . PR OP A N E M in . 11. 0" W . C . , M ax . 14 . 0" W . C . I N L ET GAS PR E S SUR E NOTE: Inlet Gas Pressure Must Not Exceed the Maximum V alue Shown. If operating pressur ...

  • Goodman Mfg ANSI Z21.47CSA-2.3 - page 18

    18 4. The belt drive blower contactor closes it s contact s L1, L2 and L3 to T1, T2 and T3 to provide power to the supply fan motor . 5. Check supply fan rotation. If the supply fan is rot ating in the wrong direction, disconnect and lock off Single Point Power Block. Do not attempt to change load side wiring. Internal wiring is set at the factory ...

  • Goodman Mfg ANSI Z21.47CSA-2.3 - page 19

    19 The pressure regulator on LP gas models is adjusted for 10.0" w .c. manifold pressure and is intended to prevent over-firing only . Do not attempt adjustment of the built-in pressure regu- lator unless the supply pressure is at least 7.0" w .c. on natu- ral gas or 14.0" w .c. on propane gas. Check the location of the ignition elec ...

  • Goodman Mfg ANSI Z21.47CSA-2.3 - page 20

    20 A UTOMATIC R ESET H IGH L IMIT C ONTROL (LS) Located in the burner compartment on the heat exchanger , its sensing element project s through the blower section bulk- head and senses the temperature at the rear of the furnace. It will cycle the furnace off if the temperature exceeds 100°F plus maximum rise. A UTOMATIC R ESET H IGH L IMIT C ONTRO ...

  • Goodman Mfg ANSI Z21.47CSA-2.3 - page 21

    21 Open Thermal Protection Device If the primary limit switch opens, the gas valve is immediately deenergized, the induced draft and air circulating blowers are energized. The induced draf t and air circulator blowers remain energized until the limit switch recloses. The diag- nostic fault code for an open limit is four (4) flashes. A primary limit ...

  • Goodman Mfg ANSI Z21.47CSA-2.3 - page 22

    22 for the purpose of airflow balancing, but once the balance has been achieved, fixed sheaves maintain alignment and minimize vibration more effectively . For direct drive units, move green wire for fan. MOTOR SHEA VE ADJUSTMENTS V L , V M & 2 VP V ARIABLE P ITCH K EY T YPE M OTOR S HEAVES The driving and driven motor sheaves should be in alig ...

  • Goodman Mfg ANSI Z21.47CSA-2.3 - page 23

    23 Disposable return air filters are supplied with this unit. See the unit S pecification Sheet or T echnical Manual for the cor- rect size and part number . T o remove the filters, remove the filter access panel on return side of the unit. C ABINET F INISH M AINTENANCE Use a fine grade automotive wax on the cabinet finish to maint ain the finish? ...

  • Goodman Mfg ANSI Z21.47CSA-2.3 - page 24

    24 APPENDIX A BLOWER PERFORMANCE DA T A BEL T DRIVE - ST ANDARD HORIZONT AL NOTES: High static airflow requires installation of high static kit (HSKT240), or factory-built High Static model. Unit factory shipped with sheave set at 2.5 turns open. Air flow tables represent dry coil with filters installed; SCFM correction factor for wet coil is 4%. C ...

  • Goodman Mfg ANSI Z21.47CSA-2.3 - page 25

    25 APPENDIX A BLOWER PERFORMANCE DA T A BEL T DRIVE - HIGH ST A TIC NOTES: High static airflow requires installation of high static kit (HSKT240), or factory-built High Static model. Unit factory shipped with sheave set at 2.5 turns open. Air flow tables represent dry coil with filters installed; SCFM correction factor for wet coil is 4%. CFM BH P ...

  • Goodman Mfg ANSI Z21.47CSA-2.3 - page 26

    26 APPENDIX B ELECTRICAL DA T A NOTES: See unit nameplate for proper overcurrent protection. MI N M AX Qt y R L A LR A Qt y HP R L A HP F LA 20 8/ 230 -60-3 1 87 25 3 2 33 . 3 23 9. 0 3 1 / 3 2. 40 BD ST D STAT IC 5 . 0 1 2. 7 46 0 - 60 - 3 41 4 5 06 2 1 7. 9 1 25 .0 3 1/ 3 1 . 2 0 B D S T D S T A T I C 5. 0 6 . 4 57 5 - 60 - 3 51 8 6 33 2 1 2. 8 8 ...

  • Goodman Mfg ANSI Z21.47CSA-2.3 - page 27

    27 APPENDIX C UNIT DIMENSIONS VERTICAL DISCHARGE (TOP VIEW) 21 ” 60 ” 7” 48” 22” B C D A Mo d el A BCD 15 T o n 20 T o n 133- 1/2" 88 - 7 / 3 2" 50 - 9 / 3 2" 5 - 5/ 32 " ...

  • Goodman Mfg ANSI Z21.47CSA-2.3 - page 28

    28 HIGH VOL T A GE! DISCONNECT ALL POWER BEFORE SERVICI NG OR INST A LLING THIS UNIT . M UL TIPL E POW ER SOUR CES MA Y BE P RESENT . F AILURE TO DO SO MA Y CAUSE PROP ERTY DAM AGE, PERSONAL INJURY OR DEA TH . Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring. CPG1803503B* & CPG2404003B* ...

  • Goodman Mfg ANSI Z21.47CSA-2.3 - page 29

    29 HIGH VOL T A GE! DISCONNECT ALL POWER BEFORE SERVICI NG OR INST A LLING THIS UNIT . M UL TIPL E POW ER SOUR CES MA Y BE P RESENT . F AILURE TO DO SO MA Y CAUS E PROPERTY DAMA GE, PERSONAL INJUR Y OR DEA TH. Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring. CPG1803503B* & CPG2404003B* ...

  • Goodman Mfg ANSI Z21.47CSA-2.3 - page 30

    30 CPG1803504B*/7B & CPG2404004B*/7B* THREE PHASE 460-575/60 HZ BELT DRIVE WIRING DIAGRAM HIGH VOL T A GE! DISCONNECT ALL POWER BEFORE SERVICI NG OR INST A LLING THIS UNIT . M UL TIPL E POW ER SOUR CES MA Y BE P RESENT . F AILURE TO DO SO MA Y CAUS E PROPERTY DAMA GE, PERSONAL INJUR Y OR DEA TH. Wiring is subject to change. Always refer to the ...

  • Goodman Mfg ANSI Z21.47CSA-2.3 - page 31

    31 HIGH VOL T A GE! DISCONNECT ALL POWER BEFORE SERVICI NG OR INST A LLING THIS UNIT . M UL TIPL E POW ER SOUR CES MA Y BE P RESENT . F AILURE TO DO SO MA Y CAUSE PROP ERTY DAM AGE, PERSONAL INJURY OR DEA TH . Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring. CPG1803504B*/7B & CPG2404004 ...

  • Goodman Mfg ANSI Z21.47CSA-2.3 - page 32

    32 © 2010 Goodman Manufacturing Company , L.P . 5151 San Felipe, Suite 500 ◊ Houston, TX 77056 www .goodmanmfg.com www .amana-hac.com ...

Manufacturer Goodman Mfg Category Gas Heater

Documents that we receive from a manufacturer of a Goodman Mfg ANSI Z21.47CSA-2.3 can be divided into several groups. They are, among others:
- Goodman Mfg technical drawings
- ANSI Z21.47CSA-2.3 manuals
- Goodman Mfg product data sheets
- information booklets
- or energy labels Goodman Mfg ANSI Z21.47CSA-2.3
All of them are important, but the most important information from the point of view of use of the device are in the user manual Goodman Mfg ANSI Z21.47CSA-2.3.

A group of documents referred to as user manuals is also divided into more specific types, such as: Installation manuals Goodman Mfg ANSI Z21.47CSA-2.3, service manual, brief instructions and user manuals Goodman Mfg ANSI Z21.47CSA-2.3. Depending on your needs, you should look for the document you need. In our website you can view the most popular manual of the product Goodman Mfg ANSI Z21.47CSA-2.3.

A complete manual for the device Goodman Mfg ANSI Z21.47CSA-2.3, how should it look like?
A manual, also referred to as a user manual, or simply "instructions" is a technical document designed to assist in the use Goodman Mfg ANSI Z21.47CSA-2.3 by users. Manuals are usually written by a technical writer, but in a language understandable to all users of Goodman Mfg ANSI Z21.47CSA-2.3.

A complete Goodman Mfg manual, should contain several basic components. Some of them are less important, such as: cover / title page or copyright page. However, the remaining part should provide us with information that is important from the point of view of the user.

1. Preface and tips on how to use the manual Goodman Mfg ANSI Z21.47CSA-2.3 - At the beginning of each manual we should find clues about how to use the guidelines. It should include information about the location of the Contents of the Goodman Mfg ANSI Z21.47CSA-2.3, FAQ or common problems, i.e. places that are most often searched by users in each manual
2. Contents - index of all tips concerning the Goodman Mfg ANSI Z21.47CSA-2.3, that we can find in the current document
3. Tips how to use the basic functions of the device Goodman Mfg ANSI Z21.47CSA-2.3 - which should help us in our first steps of using Goodman Mfg ANSI Z21.47CSA-2.3
4. Troubleshooting - systematic sequence of activities that will help us diagnose and subsequently solve the most important problems with Goodman Mfg ANSI Z21.47CSA-2.3
5. FAQ - Frequently Asked Questions
6. Contact detailsInformation about where to look for contact to the manufacturer/service of Goodman Mfg ANSI Z21.47CSA-2.3 in a specific country, if it was not possible to solve the problem on our own.

Do you have a question concerning Goodman Mfg ANSI Z21.47CSA-2.3?

Use the form below

If you did not solve your problem by using a manual Goodman Mfg ANSI Z21.47CSA-2.3, ask a question using the form below. If a user had a similar problem with Goodman Mfg ANSI Z21.47CSA-2.3 it is likely that he will want to share the way to solve it.

Copy the text from the picture

Comments (0)