EMC 4K VA 20K VA UPS - page 1
4K VA – 20K VA UPS ■ User’s and Installation Manual ■ I EMC St atements CISPR 22 NOTICE: Pursuant to CISPR 22 rules, this product has been tested and thereby complies with the conditions of a Class A digital devi ce, which have been established for offering sufficient protection against dan gerous interference for installation in a reside n ...
-
EMC 4K VA 20K VA UPS - page 2
II CONTENTS 1. Introduction ...........................................................................................1 2. System desc ription...............................................................................1 2.1 General de scription......................................................................................1 2.2 System con ...
-
EMC 4K VA 20K VA UPS - page 3
IV The instructions contained with in this safety manual are d eemed important and should be closely followed at all t imes during installa tion and follow-up maintenance of the UPS and batteries. CAUTION The unit has a dangerous amount of voltage . If the UPS indicator is on, the unit’s outlets may have a dangerous amount of vo ltage even when n ...
-
EMC 4K VA 20K VA UPS - page 4
2 Fig.1. Block diagram Efficiency Optimizer function The Efficiency Optimizer fun ction is a new feature for the UP S adding cost effectiveness, minimizing power loss and reducing power consumption. Alternating between bypass and on-line modes is achieved automatically and in accordance with the condi tions of the utility power. On-line mode may be ...
-
EMC 4K VA 20K VA UPS - page 5
4 3. Safety information Information presented here is v ital to all personnel and please also read the UPS safety manual. Storage and Transportation Please handle with extreme caution since a hi gh amount of energy is contained with the batteries. Always keep the unit in position as marked on th e packaging and never drop the unit. Installation If ...
-
EMC 4K VA 20K VA UPS - page 6
6 5.2 Rear panel views 4K/5KV A (120VDC) Rear panel 7 6KV A Rear panel (Without ISO) ...
-
EMC 4K VA 20K VA UPS - page 7
8 6KV A Rear panel (With ISO) 9 8K~10KV A Rear panel (Without ISO) ...
-
EMC 4K VA 20K VA UPS - page 8
10 8K~10 KV A Rear panel (With ISO) 11 12KV A Rear panel (ISO and With ISO) ...
-
EMC 4K VA 20K VA UPS - page 9
12 15/20 KV A Rear panel (ISO and With ISO) 13 5.3 Connection to mains and loads (4000 - 20000 VA) Only qualified specialists or technicians who conform to applic able safety standards may carry out the installat ion of this equipment. The installation m ust further comply with all local legislation and regulations . Follow all installation and saf ...
-
EMC 4K VA 20K VA UPS - page 10
14 figures 2 and 3 for proper installation. Refer to local wiring rules. z Should computer or alarm connect ions be used, use connections according to chapter 6 of the manual provided with th at option. The connections can be referred to on the rear p anel. z The installati on is now complete. b*) removable jumper w hen dual in put use d 15 Fig. 2 ...
-
EMC 4K VA 20K VA UPS - page 11
16 5.4 Default settings at the factory On the LCD display you will find severa l of the UPS parameters to sele ct. Default settings are as follows: Settings Selection Factory default Output Voltage Setting 208/220/230/ 240 Vac 230V (FOR HV series) Input/Bypass Voltage ±10% +10/-15% +15/-20% +10/-15% Input/Frequency ±2% ±5% ±7% ±5% HE Mode Sett ...
-
EMC 4K VA 20K VA UPS - page 12
18 USB port (option) Connecting the UPS to your computer is a ccomplished through the USB port on the back of your computer. USB compliant hardware and operating system will be ne cessary including installation of a UPS driver. The se rial port cannot be used when using the USB port. The USB cable is standard and can be bought separately. 6.1 EPO p ...
-
EMC 4K VA 20K VA UPS - page 13
20 7.3 Control panel functions Operation of the UPS is indicated on the mon itor panel with five LED indic ators and an LCD screen. This displa y is also capable of alerti ng the user with audible alarms. ON : This green LED is lit when UP S has been turned on. ON-LINE : When the UPS is in normal or static byp ass modes, there is voltage at the ...
-
EMC 4K VA 20K VA UPS - page 14
22 UPS configurations 1. Various settings that have been chosen are shown in the UPS setti ng display. 2. To enter configuration mode, press the “FUNC” button for one second. The first configuration parameter will be shown on the LCD display. 3. Press the “FUNC” button to scroll through the parameters . 4. Press the “ENTER” button to se ...
-
EMC 4K VA 20K VA UPS - page 15
24 **) Note: In order for the UPS and power m a nagement software to operate normally, Manual Bypass should always be set to OFF as the load will not be protected by the unit when Manual Bypass is ON. This is aimed for operating an ex ternal maintenance bypass switch. ***) Note: You should turn UPS off and keep the AC power before you use “Genera ...
-
EMC 4K VA 20K VA UPS - page 16
26 7.5 Trouble shooting Displayed on LCD Audible Alarm Alar m Description What Y ou Should Do Output Overload Two Beeps per second The UPS is overloaded (in Line Mode). Your equipment needs more power than the UPS can provide. The UPS operates in bypass. Shut off the least important equipment connected to the UPS. If this solves the overload proble ...
-
EMC 4K VA 20K VA UPS - page 17
28 9. Technical Specifications For model with 3 Phase in 1 Phase out Tower model (with LCD display) 8K31 10K31 12K31 15K31 20K31 Capacity (VA) 8000VA 10000VA 12000VA 15000V A 20000VA Capacity Capacity (W) 5600W 7000W 8400W 10500W 14000W 208/360V, 220/380V, 230/400V, 240/415V(3 Ф 5W) Load Capacity Voltage/Range Load Capacity 208~241V 0~25% 242~276V ...
-
EMC 4K VA 20K VA UPS - page 18
30 Net Weight kg (lb) W/O ISOT R 5 0 ( 1 1 0 ) 86.0 (189.2) 80(176) Shipping W eight kg (lb) W /O ISOTR 5 3 ( 1 1 6 . 7 ) 106.0 (233.2) 101.5(223.3) Dimensions W x D x H mm (inch) W/ ISOTR 257 x 590 x 700 (10.1"x23.2"x27.6") 342 x 690 x 715 (13.4" x 2 7.2" x 28.1") Net Weight kg (lb) W/ ISOT R 123.0 (270.6) 130 (286.0 ...
-
EMC 4K VA 20K VA UPS - page 19
32 Communication RS-232 Serial Port and USB Type Sealed, mainten ance-free lead acid batteries DC Voltage (V) Battery (Tower ) TBD TBD 240V / 12V7.2AH x 20 240V / 12V9AH x 20 Typical Recharge Time to 90% Full 4 hours Management Self-test, adjusta ble battery transfer points an d alarm settings Battery Protection Cut off without draini ng any curren ...
-
EMC 4K VA 20K VA UPS - page 20
34 10. VGD RM 6KVA(3U+3U) Mechanical A. VGD 6K RACK-MOUNT(3U+3U) DESIGN : (1) BASIC COMPONENT : INCLUDING 3U-UPS & 3U-BA TT . CABINET FRONT VIEW R E A R V I E W 35 (2) UPS REAR P ANEL COMPONENTS: H. TERMINAL BLOCK I. BREAKER J. EXTERNAL BA TTER Y CONNECTOR K. BYP ASS SWITCH L. SNMP SLOT M. RS232 + EPO N. TVSS O. USB P. REMOTE CONTROL POR T (3) ...
-
EMC 4K VA 20K VA UPS - page 21
36 (4) FEA TURE of REMOTE CONTROL FUNCTION: a. Remove the original right si de panel and take apart th e control panel unit. Then assemble the blank right side panel. b. Connect the C ontrol panel unit and Remote control port from rear side. 37 c. Running the remote-c ontr ol function. ...
-
EMC 4K VA 20K VA UPS - page 22
38 B. 5 in 1 FUNCTION BRACKETS on RACK-MOUNT 3U DESIGN: (1) 19” Rack installation: Mount the 3U rack-mount in a 19-inch EIA 310 C standard rack. 19” rack width 39 (2) 23” Rack installation: Change the position of the two mounting br ack ets to mount the 3U rack-mount in a 23-inch EIA 310 C standard rack. (3) T ower installation: a. Move the m ...
-
EMC 4K VA 20K VA UPS - page 23
40 (4) W all installation: Move the mounting brackets from the front to the side and attach the brackets by screws. Then mount the UPS to the wall as the below pictures shown. (5) Installation with rear B racket: W e can use bracket to support the rear side of UPS or battery cabinet. ...
Do you have a question concerning EMC 4K VA 20K VA UPS?
Use the form below
If you did not solve your problem by using a manual EMC 4K VA 20K VA UPS, ask a question using the form below. If a user had a similar problem with EMC 4K VA 20K VA UPS it is likely that he will want to share the way to solve it.