    TECHNICAL GUIDE SPLIT -SYSTEM HEA T PUMPS 13 SEER – R-410A MODELS: THGD18 THRU 60 (1.5 THRU 5 NOMINAL TONS, 1 PHASE) Due to continuous produc t impr ovement, specifications are subject to change without notice. V isit us on th e web at www .york.com A dditional rating informa tion can be fo und at w ww .ahridirectory . org LISTED ISO 9001 Certifi ...

  • York THGD18 THRU 60 - page 2

    397763-YTG-B-0508 2 Johnson Controls Unitary Products All dimensions are in inches. They are subject to cha nge without notice. Ce rtif ied dimensio ns will be provide d upon request. Physical and Electrical Data MODEL THGD18 S41S1 THGD24 S41S1 THGD30 S41S1 THGD36 S41S1 THGD42 S41S1 THGD48 S41S1 THGD60 S41S1 Unit Supply V oltage 208-230V , 1 φ, 60 ...

  • York THGD18 THRU 60 - page 3

    397763-YTG-B-0508 Johnson Controls Unitary Produ cts 3 PROCEDURES: 1. Unit factory charge listed on the unit nameplate includes re frigerant for the condenser, the smallest evaporator and 15 feet of interconnect- ing line tubing. 2. V erify the TXV or orifice and additional charge required for s pecific evaporator coil in t he system using the abov ...

  • York THGD18 THRU 60 - page 4

    397763-YTG-B-0508 4 Johnson Controls Unitary Products COOLING CAP ACITY - With Air Handler Coils UNIT MODEL AIR HANDLER COIL MODEL 1 COOLING MODEL W RA TED CFM NET MBH SEER EER TOT AL SENS. 13 SEER HP WITH MA THGD18S41S1 MA08B 17 FC/MC/PC18B 600 17.0 12 .6 13.00 1 1.00 MA08B 17 FC/MC/PC24B 600 17.0 12.9 13.50 1 1.00 THGD24S41S1 MA08B 17 FC/MC/PC24B ...

  • York THGD18 THRU 60 - page 5

    397763-YTG-B-0508 Johnson Controls Unitary Produ cts 5 — = Not applicable. 13 SEER HP WITH A V / SV / F*FV - V ARIABLE SPEED THGD18S41S1 A V24 17 – 550 17.0 13.0 14.00 12.00 THGD24S41S1 A V24 17 – 750 23.0 17.2 14.00 12.00 A V36 21 – 750 23.0 18.0 14.00 12.00 THGD30S41S1 A V36 21 – 1000 29 .0 24.4 14.00 12.00 THGD36S41S1 A V36 21 – 1250 ...

  • York THGD18 THRU 60 - page 6

    397763-YTG-B-0508 6 Johnson Controls Unitary Products COOLING CAP ACITY - Up flow , Downflow & Horizont al Furnaces and Coils UNIT MODEL FURNACE** COIL MODEL COOLING CFM RANGE (Min.-max.) W RA TED CFM NET MBH SEER 1 EER TOT AL SENS. THGD18S41S1 450 - 750 14,17 FC/MC/PC18 600 17.0 12.6 13.00 1 1.00 450 - 750 14,17 FC/MC/PC24 600 17.0 12.9 13.50 ...

  • York THGD18 THRU 60 - page 7

    397763-YTG-B-0508 Johnson Controls Unitary Produ cts 7 COOLING CAP ACITY - W ith V ariable Spe ed Furnaces UNIT MODEL V ARIABLE SPEED FURNACE MODEL COIL MODEL 1 W COOLING RA TED CFM Net MBH SEER EER TOT AL SENS. 13 SEER HP WITH V ARIABLE SPEED FURNACES 2 THGD18S41S1 PV8*A12 F C/MC/PC18A 14 600 17.0 12.9 14 .00 12.00 PV9*A12 F C/MC/PC18A 14 600 17.0 ...

  • York THGD18 THRU 60 - page 8

    397763-YTG-B-0508 8 Johnson Controls Unitary Products THGD30S41S1 PV8*C16 HC42C 21 1000 29.0 24.0 14 .00 12.00 PV8*C20 HC42C 21 1 100 29.0 25.6 14.00 12.00 P(C,V)9*C16 HC42C 21 1000 29.0 23.8 14.00 12.00 P(C,V)9*C20 HC42C 21 1050 29.0 23.8 14.00 12.00 PV8*C16 HD48C 21 1000 29.0 24 .0 14.00 12.00 PV8*C20 HD48C 21 1 100 29.0 25.4 14.00 12.00 P(C,V)9* ...

  • York THGD18 THRU 60 - page 9

    397763-YTG-B-0508 Johnson Controls Unitary Produ cts 9 THGD48S41S1 PV8*C16 FC/MC /PC48C 21 1500 46.5 34.2 13.00 1 1.00 PV8*C20 FC/MC /PC48C 21 1600 47.0 35.4 13.00 1 1.50 P(C,V)9*C16 FC/MC/PC48C 21 1600 47.0 35.2 13.00 1 1.00 P(C,V)9*C20 FC/MC/PC48C 21 1600 47.0 35.4 14.00 1 1.50 P(C,V)9*D20 FC/MC/PC48D 24 1550 47.0 35.6 14.00 1 1.50 PV8*C16 FC/MC ...

  • York THGD18 THRU 60 - page 10

    397763-YTG-B-0508 10 Johnson Controls Unitary Products HEA TING PERFORMANCE - With Air Handler UNIT MODEL* AIR HANDLER COIL 1 MODEL ARI HEA TING 2 47 ° F1 7 ° FH S P F MBH COP KW MBH COP KW STD 13 SEER HP WITH MA THGD18S41S1 MA08B FC/MC18B 17.0 3.32 1.50 12.7 3. 00 1.24 7.70 MA08B FC/MC24B 17.0 3.44 1.45 10.4 2.60 1.17 7 .70 THGD24S41S1 MA08B FC/ ...

  • York THGD18 THRU 60 - page 11

    397763-YTG-B-0508 Johnson Controls Unitary Produ cts 11 CP equals MBH output divided by (t otal KW input x 3.412). HSPF (Heating Seasonal Performance Factor) is the total heating ou tput during a normal annual usage period for heating divided by the total electric power input during the same period. — = Not Applicable. 13 SEER HP WITH A V / SV / ...

  • York THGD18 THRU 60 - page 12

    397763-YTG-B-0508 12 Johnson Controls Unitary Products CP equals MBH output divided by (total KW input x 3.412). HSPF (Heating Seasonal Performance Factor) is the total heat ing output during a normal annual usage period for heating divided by the total electric power input during the same period. — = Not Applicable. HEA TING PERFORMANCE - Up flo ...

  • York THGD18 THRU 60 - page 13

    397763-YTG-B-0508 Johnson Controls Unitary Produ cts 13 HEA TING CAP ACITY - With V ariable Spe ed Furnaces UNIT MODEL V ARIABLE SPEED FURNACE COIL 1 MODEL ARI HEA TING 2 47 ° F1 7 ° FH S P F MBH COP KW MBH COP KW STD 13 SEER HP WITH V ARIABLE SPEED FURNACES 3 THGD18S41S1 PV8*A12 FC/MC/PC18A 16.7 3.5 6 1.37 1 1.5 3.12 1 .08 8.00 PV9*A12 FC/MC/PC1 ...

  • York THGD18 THRU 60 - page 14

    397763-YTG-B-0508 14 Johnson Controls Unitary Products THGD30S41S1 PV8*C20 HC42C 28.0 3.68 2.23 16.2 2. 50 1.90 8.00 P(C,V)9*C16 HC42C 27.8 3.58 2.28 16 .2 2.46 1.93 8.00 P(C,V)9*C20 HC42C 27.8 3.58 2.28 16 .2 2.46 1.93 8.00 PV8*C16 HD48C 28.0 3.68 2.23 16.2 4. 76 1.00 8.00 PV8*C20 HD48C 28.0 3.68 2.23 16.2 3. 80 1.25 8.00 P(C,V)9*C16 HD48C 28.0 3. ...

  • York THGD18 THRU 60 - page 15

    397763-YTG-B-0508 Johnson Controls Unitary Produ cts 15 CP equals MBH output divided by (total KW input x 3.412). HSPF (Heating Seasonal Performance Factor) is the total heating ou tput during a normal annual usage period for heating divided by the total electric power input during the same period. — = Not Applicable. THGD48S41S1 PV8*C16 FC/MC/PC ...

  • York THGD18 THRU 60 - page 16

    397763-YTG-B-0508 16 Johnson Controls Unitary Products ACCESSORIES Refer to Price Manual for specific model numbers. St art Assist Kit (2SA067*) - May be required on 42, 48, 60 models. Models 18, 24 , 30, 36 ha ve been factory installed. Blower Time Delay - A vailable to increase efficiency whe n installed. Installs on indoor section and maintains ...

  • York THGD18 THRU 60 - page 17

    397763-YTG-B-0508 Johnson Controls Unitary Produ cts 17 Multipliers for determining the performance with other indoor sections . NOTE: For dry bulb temperatures dif ferent than t hose liste d (between 73-87 F), sensible cap acity incr eases by 1060 BTUH per 1000 CFM per degr ee above the listed temperature and decreases by 1060 BTUH per 1 000 CFM p ...

  • York THGD18 THRU 60 - page 18

    397763-YTG-B-0508 18 Johnson Controls Unitary Products Multipliers for determining the perfo rman ce with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those liste d (bet ween 73-87 F), sensible capacit y incr eases by 1060 BTUH per 1000 CFM per deg ree abo ve the listed temperatu re and decre ases by 1060 BTUH per 1000 CFM ...

  • York THGD18 THRU 60 - page 19

    397763-YTG-B-0508 Johnson Controls Unitary Produ cts 19 Multipliers for determining the performance with other indoor sections . NOTE: For dry bulb temperatures dif ferent than t hose liste d (between 73-87 F), sensible cap acity incr eases by 1060 BTUH per 1000 CFM per degr ee above the listed temperature and decreases by 1060 BTUH per 1 000 CFM p ...

  • York THGD18 THRU 60 - page 20

    397763-YTG-B-0508 20 Johnson Controls Unitary Products Multipliers for determining the perfo rman ce with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those liste d (bet ween 73-87 F), sensible capacit y incr eases by 1060 BTUH per 1000 CFM per deg ree abo ve the listed temperatu re and decre ases by 1060 BTUH per 1000 CFM ...

  • York THGD18 THRU 60 - page 21

    397763-YTG-B-0508 Johnson Controls Unitary Produ cts 21 Multipliers for determining the performance with other indoor sections . NOTE: For dry bulb temperatures dif ferent than t hose liste d (between 73-87 F), sensible cap acity incr eases by 1060 BTUH per 1000 CFM per degr ee above the listed temperature and decreases by 1060 BTUH per 1 000 CFM p ...

  • York THGD18 THRU 60 - page 22

    397763-YTG-B-0508 22 Johnson Controls Unitary Products Multipliers for determining the perfo rman ce with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those liste d (bet ween 73-87 F), sensible capacit y incr eases by 1060 BTUH per 1000 CFM per deg ree abo ve the listed temperatu re and decre ases by 1060 BTUH per 1000 CFM ...

  • York THGD18 THRU 60 - page 23

    397763-YTG-B-0508 Johnson Controls Unitary Produ cts 23 Multipliers for determining the performance with other indoor sections . NOTE: For dry bulb temperatures dif ferent than t hose liste d (between 73-87 F), sensible cap acity incr eases by 1060 BTUH per 1000 CFM per degr ee above the listed temperature and decreases by 1060 BTUH per 1 000 CFM p ...

  • York THGD18 THRU 60 - page 24

    397763-YTG-B-0508 24 Johnson Controls Unitary Products Multipliers for determining the perfo rman ce with other indoor sections. HEA TING PERFORMANCE DA T A CONDENSING UNIT MODEL NO THGD1 8S41S1 EV APORA TOR COIL MODEL NO AHP18 AIR TEMP . ENTERING OUTDOOR UNIT AIR TEMP . ENTERING INDOOR COIL ID CFM 450 600 750 MBTUH KW C.O.P . MBTUH KW C.O.P . MBTU ...

  • York THGD18 THRU 60 - page 25

    397763-YTG-B-0508 Johnson Controls Unitary Produ cts 25 Multipliers for determining the performance with other indoor sections . HEA TING PERFORMANCE DA T A CONDENSING UNIT MODEL NO THGD2 4S41S1 EV APORA TOR COIL MODEL NO AHP24 AIR TEMP . ENTERING OUTDOOR UNIT AIR TEMP . ENTERING INDOOR COIL ID CFM 600 800 1000 MBTUH KW C.O.P . MBTUH KW C.O.P . MBT ...

  • York THGD18 THRU 60 - page 26

    397763-YTG-B-0508 26 Johnson Controls Unitary Products Multipliers for determining the perfo rman ce with other indoor sections. HEA TING PERFORMANCE DA T A CONDENSING UNIT MODEL NO THGD3 0S41S1 EV APORA TOR COIL MODEL NO AHP36 AIR TEMP . ENTERING OUTDOOR UNIT AIR TEMP . ENTERING INDOOR COIL ID CFM 800 1000 1200 MBTUH KW C.O.P . MBTUH KW C.O.P . MB ...

  • York THGD18 THRU 60 - page 27

    397763-YTG-B-0508 Johnson Controls Unitary Produ cts 27 Multipliers for determining the performance with other indoor sections . HEA TING PERFORMANCE DA T A CONDENSING UNIT MODEL NO THGD3 6S41S1 EV APORA TOR COIL MODEL NO AHP36 AIR TEMP . ENTERING OUTDOOR UNIT AIR TEMP . ENTERING INDOOR COIL ID CFM 1000 1200 1400 MBTUH KW C.O.P . MBTUH KW C.O.P . M ...

  • York THGD18 THRU 60 - page 28

    397763-YTG-B-0508 28 Johnson Controls Unitary Products Multipliers for determining the perfo rman ce with other indoor sections. HEA TING PERFORMANCE DA T A CONDENSING UNIT MODEL NO THGD4 2S41S1 EV APORA TOR COIL MODEL NO FC/MC/PC/UC48 AIR TEMP . ENTERING OUTDOOR UNIT AIR TEMP . ENTERING INDOOR COIL ID CFM 1200 1400 1600 MBTUH KW C.O.P . MBTUH KW C ...

  • York THGD18 THRU 60 - page 29

    397763-YTG-B-0508 Johnson Controls Unitary Produ cts 29 Multipliers for determining the performance with other indoor sections . HEA TING PERFORMANCE DA T A CONDENSING UNIT MODEL NO THGD4 8S41S1 EV APORA TOR COIL MODEL NO AHP/SHP48 AIR TEMP . ENTERING OUTDOOR UNIT AIR TEMP . ENTERING INDOOR COIL ID CFM 1400 1600 1800 MBTUH KW C.O.P . MBTUH KW C.O.P ...

  • York THGD18 THRU 60 - page 30

    Subject to change without notice. Printe d in U.S.A. 397763-YTG-B-0508 Copyright © 2008 by Johnson Controls, Inc. All ri ghts reserved. Supersedes: 397763-YTG-A-0408 Johnson Controls Unitary Product s 5005 Y ork Drive Norman, OK 73069 Multipliers for determining the perfo rman ce with other indoor sections. HEA TING PERFORMANCE DA T A CONDENSING U ...

Produzent York Kategorie Air Conditioner

Dokumente, die wir vom Produzenten des Geräts York THGD18 THRU 60 erhalten, können wir in mehrere Gruppen teilen. Unteranderem in:
- technische Zeichnungen York
- Bedienungsanleitungen THGD18 THRU 60
- Produktkarten York
- Informationsbroschüren
- oder Energieetiketten York THGD18 THRU 60
Jede von ihnen ist wichtig, jedoch finden wir die wichtigsten Informationen für den Nutzer des Geräts in der Bedienungsanleitung York THGD18 THRU 60.

Die Dokumentengruppe, die als Bedienungsanleitungen bezeichnet wird, wird ebenfalls in detaillierte Arten geteilt, solche wie: Montageanleitungen York THGD18 THRU 60, Wartungsanleitungen, Kurzanleitungen oder Benutzeranleitungen York THGD18 THRU 60. Abhängig vom Bedarf, sollten Sie das Dokument finden, das Sie brauchen. In unserem Service können Sie sich die populärste Bedienungsanleitung des Produkts York THGD18 THRU 60 ansehen.

Ähnliche Bedienungsanleitungen

Die komplette Bedienungsanleitung des Geräts York THGD18 THRU 60, wie sollte sie aussehen?
Die Bedienungsanleitung, auch bezeichnet als Benutzerhandbuch, oder einfach nur „Anleitung”, ist ein technisches Dokument, das dem Benutzer bei der Nutzung von York THGD18 THRU 60 hilfreich sein soll. Die Bedienungsanleitungen werden in der Regel von technischen Schriftstellern geschrieben, aber in einer Sprache, die für alle Nutzer von York THGD18 THRU 60 verständlich ist.

Eine gänzliche Bedienungsanleitung von York sollte einige Grundelemente enthalten. Ein Teil von ihnen ist nicht so wichtig, wie z.B.: die Titelseite oder Autorenseiten. Die restlichen von ihnen jedoch, sollten Informationen liefern, die für den Nutzer von enormer Wichtigkeit sind.

1. Einführung und Hinweise, wie man sich in einer Bedienungsanleitung von York THGD18 THRU 60 bewegt - Am Anfang jeder Bedienungsanleitung sollten wir Hinweise bezüglich der Nutzungsart eines bestimmten Ratgebers finden. In ihr sollten sich Informationen über die Lokalisierung des Inhaltsverzeichnisses von York THGD18 THRU 60 befinden, FAQ oder über oft auftretende Probleme – also Stellen, die von den Benutzern in jeder Bedienungsanleitung am meisten gesucht werden
2. Inhaltsverzeichnis - Index aller Ratschläge bezüglich York THGD18 THRU 60, die wir im aktuellen Dokument finden
3. Ratschläge zur Nutzung der Grundfunktionen des Geräts York THGD18 THRU 60 - die uns die ersten Schritte während der Nutzung von York THGD18 THRU 60 erleichtern sollten
4. Troubleshooting - geordneter Tätigkeitslauf, der uns bei der Diagnose und als nächstes bei der Lösung wichtiger Probleme mit York THGD18 THRU 60 hilft
5. FAQ - häufig gestellte Fragen
6. Kontaktdaten Informationen darüber, wo man Kontakt zum Produzenten / Service von York THGD18 THRU 60 im bestimmten Land suchen kann, wenn es nicht gelingt, das Problem selbst zu lösen.

Haben Sie eine Frage bezüglich York THGD18 THRU 60?

Nutzen Sie das untere Formular

Wenn Sie mit Hilfe der gefundenen Bedienungsanleitung Ihr Problem mit York THGD18 THRU 60 nicht gelöst haben, stellen Sie eine Frage, indem Sie das untere Formular nutzen. Wenn einer der Nutzer ein ähnliches Problem mit York THGD18 THRU 60 hatte, ist es möglich, dass er mit Ihnen die Lösung teilen möchte.

Text vom Bild übertragen

Kommentare (0)