Carrier 13 50XP - page 1
PERFORMANCE™ 13 50XP SINGLE-PACKAGED ELECTRIC COOLING UNITS WITH PURON® (R-410A) REFRIGERANT 2 to 5 Nominal Tons Product Data UNIT 50XP Single-Packaged Products with Energy-Sa ving Features and Puron® refrigerant. • Low Sound Le vels • 13 SEER • V ariable Speed Blo wer-Standard • Factory Installed TXV Features/Bene fi ts One-piece cool ...
-
Carrier 13 50XP - page 2
2 50XP cooling unit that is pre-wired, pre- piped, and pre-charged for minimum installation expense. 50XP units are av ailable in a variety of standard cooling sizes with voltage options to meet residential and light commercial requirements. Units are light weight, and install easily on a rooftop or at ground-le vel. The hightech, composite base pa ...
-
Carrier 13 50XP - page 3
3 50XP Model number nomenc lature ARI* capacities COOLING CAPACITIES AND EFFICIENCIES 50XP 024 3 UNIT 50XP NOMINAL T ONS ST ANDARD CFM NET COOLING CAP ACITIES (Btuh) EER@A** SEER† SOUND RA TINGS‡ (dB) 024 2 800 24,000 11.0 13.0 72 030 2-1/2 1000 28,800 11.0 13.0 72 036 3 1100 36,000 11.0 13.0 72 042 3-1/2 1400 41,000 11.0 13.0 72 048 4 1450 45, ...
-
Carrier 13 50XP - page 4
4 50XP OUTDOOR SOUND: OCT A VE B AND D A T A—DECIBELS (Lw(A)) Ph ysical data * Required fi lter siz es shown are based on the larger of the ARI (Air Conditioning & Refrigeration Institute) rated cooling air fl ow or the heating air fl ow v elocity of 300 ft/min f or throwa way type or 450 ft/min f or high-capacity type. Air fi lter pressu ...
-
Carrier 13 50XP - page 5
5 50XP F actory-installed options Coil options include T in-Plated* indoor hairpins, copper/ copper and vinyl-coated construction for refrigerant coils. Units are shipped standard with copper tube/aluminum fi n construction. See model number nomenclature for coil options. *T in-Plated indoor coils are built with special hairpins that are designed ...
-
Carrier 13 50XP - page 6
6 50XP ECONOMIZER FIL TER RACK MANUAL OUTSIDE AIR DAMPER DAMPER BLADE MANUAL OUTSIDE AIR HOOD REPLACEMENT P ANEL 7 50XP ...
-
Carrier 13 50XP - page 7
7 50XP Base unit dimensions—50XP024-036 UNIT ELECTRICAL CHARA CTERISTICS UNIT WEIGHT UNIT HEIGHT in. [mm] “A” CENTER OF GRA VITY in. [mm] lb kg X Y Z 50XP024 208/230-1-60 343 156 39.02 [991.1] 20 [508] 19.3 [489] 17.6 [447] 50XP030 208/230-1-60 343 156 39.02 [991.1] 20 [508] 19.3 [489] 17.6 [447] 50XP036 208/230-1-60, 208/230-3-60 366 166 41. ...
-
Carrier 13 50XP - page 8
8 50XP Base unit dimensions—50XP042-060 UNIT ELECTRICAL CHARA CTERISTICS UNIT WEIGHT UNIT HEIGHT in. [mm] “A” CENTER OF GRA VITY in. [mm] lb kg X Y Z 50XP042 208/230-1-60, 208/230-3-60 433 197 42.98 [1091.7] 21 [533.4] 20.5 [520.2] 16.6 [421.6] 50XP048 208/230-1-60, 208/230-3-60 456 207 44.98 [1142.5] 19.5 [495.3] 17.6 [447.6] 18.0 [457.2] 50 ...
-
Carrier 13 50XP - page 9
9 50XP Accessory dimensions UNIT SIZE ODS CA T ALOG NUMBER A in. [mm] B in. [mm] C in. [mm] D in. [mm] 50XP024-036 CPRFCURB006A00 8 [203] 11 [279] 16-1/2 [419] 28-3/4 [730] CPRFCURB007A00 14 [356] 11 [279] 16-1/2 [419] 28-3/4 [730] 50XP042-060 CPRFCURB008A00 8 [203] 16-3/16 [411] 17-3/8 [441] 40-1/4 [1022] CPRFCURB009A00 14 [356] 16-3/16 [411] 17-3 ...
-
Carrier 13 50XP - page 10
10 50XP I Determine cooling and heating requirements at design conditions: Given: Required Cooling Capacity (TC) . . . . . . . . . . 34,500 Btuh Sensible Heat Capacity (SHC) . . . . . . . . . . . . 26,000 Btuh Required Heating Capacity . . . . . . . . . . . . . . 15,000 Btuh Condenser Entering Air Temperature . . . . . . . . . . . . 95°F Indoor-Ai ...
-
Carrier 13 50XP - page 11
11 50XP P erf ormance data- Standard ECM Indoor Motor COOLING CAP A CITIES See Legend and Notes on page 13. 50XP024 COOLING PERFORMANCE TABLE Temp (F) Outdoor Air Entering Condenser Evaporator Air—CFM/BF 800/0.026 900/0.032 1000/0.04 Evaporator Air — Ewb (F) 62 63* 67 72 62 63* 67 72 62 63* 67 72 75 TC SHC kW 24.0 24.5 26.5 29.1 24.6 25.1 27.1 ...
-
Carrier 13 50XP - page 12
12 50XP P erf ormance data (cont)- Standar d ECM Indoor Motor COOLING CAP A CITIES See Legend and Notes on page 13. 50XP036 COOLING PERFORMANCE TABLE Temp (F) Outdoor Air Entering Condenser Evaporator Air—CFM/BF 1100/0.06 1225/0.07 1400/0.08 Evaporator Air — Ewb (F) 62 63* 67 72 62 63* 67 72 62 63* 67 72 75 TC 36.2 36.8 39.7 43.8 36.9 37.4 40.3 ...
-
Carrier 13 50XP - page 13
13 50XP P erf ormance data (cont)- Standar d ECM Indoor Motor COOLING CAP A CITIES 50XP048 COOLING PERFORMANCE TABLE Temp (F) Outdoor Air Entering Condenser Evaporator Air—CFM/BF 1260/0.06 1400/0.06 1600/0.08 Evaporator Air — Ewb (F) 62 63* 67 72 62 63* 67 72 62 63* 67 72 75 TC 45.0 45.8 49.6 54.7 46.7 47.3 51.2 56.3 48.1 48.7 52.5 57.8 SHC 39. ...
-
Carrier 13 50XP - page 14
14 50XP P erf ormance data (cont) ECONOMIZER 1-in. FIL TER PRESSURE DR OP (in. wg) MUL TIPLICA TION F A CTORS Example: 15.0 kW (at 240v) heater on 208 v = 15.0 (.75 mult f actor) = 11.25 capacity at 208 v UNIT50XP PRESSURE DROP 024-036 0.20 042-060 0.25 HEA TER kW RA TING VO LT AG E DISTRIBUTION MUL TIPLICA TION F ACT OR 240 200 208 230 240 .69 .75 ...
-
Carrier 13 50XP - page 15
15 50XP 50XP ECM DR Y COIL AIRFLO W–SMALL CABINET 50XP ECM DR Y COIL AIRFLO W–LARGE CABINET 50XP ECM WET COIL PRESSURE DROP UNIT SIZE CFM ADJUST PIN SELECT LO PIN NOM PIN HI PIN EXTERNAL STATIC PRESSURE RANGE 0.0–0.39 0.4–0.69 0.7–1.0 0.0–0.39 0.4–0.69 0.7–1.0 0.0–0.39 0.4–0.69 0.7–1.0 024 COOLING 800 725 — 885 805 730 990 9 ...
-
Carrier 13 50XP - page 16
16 50XP INDOOR THERMOST A T DISCONNECT PER NEC* FROM POWER SOURCE RETURN AIR T OP CO VER *NEC - NA TIONAL ELECTRICAL CODE Typical piping and wiring ROOF RETURN-AIR FLEXIBLE DUCT CEILING CONCENTRIC DIFFUSER BO X (FIELD-SUPPLIED) SUPPL Y -AIR FLEXIBLE DUCT ROOF-MOUNTING CURB C00023 C00063 50XP ...
-
Carrier 13 50XP - page 17
17 50XP Condensate trap — A 2-in. condensate trap must be fi eld supplied. Ductwork — Secure do wn fl ow dischar ge ductwork to roof curb . For horizontal dischar ge applications, attach ductwork to unit with fl anges. T o con vert a unit to down fl o w discharge — Units are equipped with factory-installed inserts in the do wn fl ow open ...
-
Carrier 13 50XP - page 18
18 50XP Electrical data UNIT SIZE 50XP V -PH-Hz V O LTAG E RANGE COMPRESSOR OUTDOOR F AN MOT OR INDOOR F AN MOT OR ELECTRIC HEA T PO WER SUPPL Y Min Max RLA LRA FLA FLA Nominal kW* FLA UNIT MCA MAX FUSE or CKT . BKR. MOCP 024 208/230-1-60 187 253 13.5 61.0 0.8 4.3 —/— 3.8/5 5.4/7.2 7.5/10 —/— 18.1/20.8 26/30 36.1/41.7 22.0/22.0 27.9/31.4 37 ...
-
Carrier 13 50XP - page 19
19 50XP 4 5 2=5v 4 5 7=7v 4 5 5=2v LEGEND FLA — Full Load Amps LRA — Lock ed Rotor Amps MCA — Minimum Circuit Amps MOCP — Maximum Ov ercurrent Protection RLA — Rated Load Amps NO TES: 1. In compliance with NEC (National Electr ical Code) requirements for multimotor and combination load equipment (refer to NEC Ar ticles 430 and 440), the o ...
-
Carrier 13 50XP - page 20
20 50XP T ypical wiring schematic— 208/230-1-60 C01037 ...
-
Carrier 13 50XP - page 21
21 50XP T ypical wiring schematic— 208/230-3-60 C03026 ...
-
Carrier 13 50XP - page 22
22 50XP Operating sequence Cooling — When the system thermostat calls for cooling, 24 V is supplied to the “Y” and “G” terminals of the thermostat. This completes the circuit to the contactor coil (C) and indoor (e vaporator) fan time delay relay (TDR). The normally open contacts of C close and complete the circuit to compressor motor (CO ...
-
Carrier 13 50XP - page 23
23 50XP Packaged Electric Cooling Units Constant Volume Application HVAC Guide Specifications Size Range: 2 to 5 Tons, Nominal Cooling Carrier Model Number: 50XP Part 1—General SYSTEM DESCRIPTION Outdoor rooftop or ground mounted, electric cooling unit utilizing a hermetic compressor for cooling duty and optional electric heating. Unit shall disc ...
-
Carrier 13 50XP - page 24
Copyright 2005 Carrier Corp. • 7310 W. Morris St. • Indianapolis, IN 46231 Printed in U.S.A. edition date: 10/05 Manufacturer reserves the right to change, at any time, specifications or designs without notice and obligations Catalog No: 50XP-4PD Replaces: 50XP-3PD L. Grille 1. Louvered Grille: Louvered grille shall be standard on all units. M. ...
Haben Sie eine Frage bezüglich Carrier 13 50XP?
Nutzen Sie das untere Formular
Wenn Sie mit Hilfe der gefundenen Bedienungsanleitung Ihr Problem mit Carrier 13 50XP nicht gelöst haben, stellen Sie eine Frage, indem Sie das untere Formular nutzen. Wenn einer der Nutzer ein ähnliches Problem mit Carrier 13 50XP hatte, ist es möglich, dass er mit Ihnen die Lösung teilen möchte.