    C US ® Cop yright ©2009-2010 Goodman Manufacturing Co mpany, L.P. RT6612021 Rev. 3 August 2010 This manual is to be used by qualified, professionally trained HV AC technicians only . Goodman does not assume any responsibility for property damage or personal injury due to improper service procedures performed by an unqualified person. ACVC9/AMVC95 ...

  • Goodman Mfg ACVC9/AMVC95 - page 2

    PRODUCT IDENTIFICA TION 2 The model and manufacturing number are used for positive identification of component parts used in manufacturing. Please use these numbers when requesting service or parts information. WARNING WARNING HIGH VOLTAGE! Disconnect ALL power before servicing or installing this unit. Multiple power sources may be present. Failure ...

  • Goodman Mfg ACVC9/AMVC95 - page 3

    3 PRODUCT IDENTIFICA TION The model and manufacturing number are used for positive identification of component parts used in manufacturing. Please use these numbers when requesting service or parts information. AMVC950453BXAA AMVC950704CXAA AMVC950905CXAA AMVC950905DXAA AMVC951155DXAA ACVC90704CXAA ACVC90905DXAA AMVC950453BXAB AMVC950704CXAB AMVC95 ...

  • Goodman Mfg ACVC9/AMVC95 - page 4

    4 PRODUCT DESIGN installation (1 or 2 pipes). The optional Combustion Air Pipe is dependent on installation/code requirements and must be 2” or 3” diameter PVC. 2. Line voltage wiring can enter through the right or left side of the furnace. Low voltage wiring can enter through the right or left side of furnace. 3. Conversion kits for propane ga ...

  • Goodman Mfg ACVC9/AMVC95 - page 5

    5 PRODUCT DESIGN quired due to the natural reduction in the density of both the gas fuel and combustion air as altitude increases. The kit will provide the proper design certified input rate within the specified altitude range. High altitude kits are purchased according to the installa- tion altitude and usage of either natural or propane gas. Refe ...

  • Goodman Mfg ACVC9/AMVC95 - page 6

    COMPONENT IDENTIFICA TION 6 Counterflow /Horizontal Upflow/Horizontal 1 Two-Stage Gas Valve 2 Gas Line Entrance (Alternate) 3 Pressure Switch(es) 4 Gas Manifold 5 Combustion Air Intake Connection 6 Hot Surface Igniter 7 Rollout Limit 8 Burners 9 Flame Sensor 1 0 Flue Pipe Connection 1 1 Flue Pipe 1 2 Primary Limit 1 3 Gas Line Entrance 1 4 Flue Pip ...

  • Goodman Mfg ACVC9/AMVC95 - page 7

    7 PRODUCT DIMENSIONS GMVC95/AMVC95___X* NOTE: Airflow area will be reduced by approximately 18% if duct flanges are not unfolded. This could cause performance issues and noise issues. AIR DIS CHARG E A IR DISC HARGE LOW VOL TAGE EL EC TR IC AL HOL E HIGH VOL T AGE ELECT RICAL HOLE SIDE CUT-OUT LE FT S I D E VIE W SID E CUT -OUT HI GH VO L T AGE ELE ...

  • Goodman Mfg ACVC9/AMVC95 - page 8

    PRODUCT DIMENSIONS 8 GCVC9/ACVC9_____X* NOTE: Airflow area will be reduced by approximately 18% if duct flanges are not unfolded. This could cause performance issues and noise issues. LOW VOLT AGE ELECTR ICAL H OLE AIR I NT A KE PIPE 2" PVC LEFT SIDE DR AI N L I N E HOL ES DR AI N TRA P 28 5/1 6 11 1 / 2 9 1 3/ 16 15 1/ 2 UNF OLDE D FL ANG ES ...

  • Goodman Mfg ACVC9/AMVC95 - page 9

    9 PRODUCT DESIGN LOW F IR E HIGH FI R E LOW F IR E HI G H FIR E LOW FIRE HIGH FI R E LOW FIRE HI G H FIRE G MV C 95 0453 BX* G MV C 95 0704 CX* A M VC 9504 53BX * A M VC 9507 04CX * -0 . 45 - 0 . 9 0 -0 . 5 0 -0 .9 5 -0 . 25 - 0 . 2 5 -0. 25 -0 . 2 5 G MV C 95 0905 CX* A M VC 9509 05CX * - 0. 75 -1 .85 - . 060 - 1. 7 0 - 0. 10 -0 .10 - 0 .10 - 0. 1 ...

  • Goodman Mfg ACVC9/AMVC95 - page 10

    10 PRODUCT DESIGN LO W FIRE HI G H FIRE LO W FIR E HIG H FI RE LO W FIRE HIGH F IRE LO W FIR E HIGH F I RE G M VC 9504 53B X * G M VC 9507 04C X * AMV C95 0453 BX* AMV C95 0704 CX* - 0.10 - 0.1 0 20 1973 08 - 0 .30 - 0.75 111 7711 3 - 0.1 0 - 0. 10 - 0 .22 - 0 .55 HA PS 2 8 1117 711 5 G M VC 9509 05C X * AMV C95 0905 CX* - 0.10 - 0.1 0 0 130 F 0007 ...

  • Goodman Mfg ACVC9/AMVC95 - page 11

    11 PRODUCT DESIGN Pa rt N u m b e r 20 16 290 3 201 62 904 2 01 629 05 20 16 290 7 201 62 908 0 130 F 001 05 Open Setting (° F) 16 0 1 50 14 5 15 5 1 7 0 130 G MV C950 453B X* A MV C 95 0 4 53 B X* -- - - - - 1 - -- - - - - - - G MV C950 704C X* A MV C 95 0 7 04 C X* - -- --- --- 1 --- --- G MV C950 905C X* A MV C 95 0 9 05 C X* - -- --- --- -- - ...

  • Goodman Mfg ACVC9/AMVC95 - page 12

    12 PRODUCT DESIGN P art N um b e r 10 1235 34 101 2 3535 10 1235 37 1 012 3536 101 235 33 0130 F 000 38 Ope n Se t ting ( ° F) 220 1 50 190 18 0 200 12 0 G MV C95 045 3BX * AMV C 950 453 B X* - -- 2 --- -- - --- - -- G MV C95 070 4CX * AMV C 950 704 C X* - - -- - - 2 - - -- - -- - - G MV C95 090 5CX * AMV C 950 905 C X* - -- -- - --- -- - --- 2 G ...

  • Goodman Mfg ACVC9/AMVC95 - page 13

    13 PRODUCT DESIGN Coil Matches: A large array of Amana® brand coils are available for use with the GCVC9 and ACVC9 furnaces, in either counterflow or horizontal applications & with GMVC95 and AMVC95 furnaces, in either upflow or horizontal applications. These coils are available in both cased and uncased models (with the option of a field inst ...

  • Goodman Mfg ACVC9/AMVC95 - page 14

    14 PRODUCT DESIGN Thermost at s: ComfortNet™ CTK01A* Thermostat Kit Filters: Filters are required with this furnace and must be provided by the installer. The filters used must comply with UL900 or CAN/ULCS111 standards. Installing this furnace without filters will void the unit warranty Upflow Filters Return air filters may be installated at the ...

  • Goodman Mfg ACVC9/AMVC95 - page 15

    15 PRODUCT DESIGN Counterflow Filters "A" Min Return Air Optional Ac ce ss Door Return air filters may be installated at the at the counterflow top return. A field supplied center filter support must be provided by the installer in order to use the top return. The furnace will accommodate the following counterflow top return filter size s ...

  • Goodman Mfg ACVC9/AMVC95 - page 16

    FURNACE SPECIFICA TIONS 1. These furnaces are manufactured for natural gas operation. Optional Kits are available for conversion to propane gas operation. 2. For elevations above 2000 ft. the rating should be reduced by 4% for each 1000 ft. above sea level. The furnace must not be derated, orifice changes should only be made if necessary for altitu ...

  • Goodman Mfg ACVC9/AMVC95 - page 17

    FURNACE SPECIFICA TIONS 17 1. These furnaces are manufactured for natural gas operation. Optional Kits are available for conversion to propane gas operation. 2. For elevations above 2000 ft. the rating should be reduced by 4% for each 1000 ft. above sea level. The furnace must not be derated, orifice changes should only be made if necessary for alt ...

  • Goodman Mfg ACVC9/AMVC95 - page 18

    FURNACE SPECIFICA TIONS 1. These furnaces are manufactured for natural gas operation. Optional Kits are available for conversion to propane gas operation. 2. For elevations above 2000 ft. the rating should be reduced by 4% for each 1000 ft. above sea level. The furnace must not be derated, orifice changes should only be made if necessary for altitu ...

  • Goodman Mfg ACVC9/AMVC95 - page 19

    FURNACE SPECIFICA TIONS 19 1. These furnaces are manufactured for natural gas operation. Optional Kits are available for conversion to propane gas operation. 2. For elevations above 2000 ft. the rating should be reduced by 4% for each 1000 ft. above sea level. The furnace must not be derated, orifice changes should only be made if necessary for alt ...

  • Goodman Mfg ACVC9/AMVC95 - page 20

    FURNACE SPECIFICA TIONS 1. These furnaces are manufactured for natural gas operation. Optional Kits are available for conversion to propane gas operation. 2. For elevations above 2000 ft. the rating should be reduced by 4% for each 1000 ft. above sea level. The furnace must not be derated, orifice changes should only be made if necessary for altitu ...

  • Goodman Mfg ACVC9/AMVC95 - page 21

    FURNACE SPECIFICA TIONS 21 1. These furnaces are manufactured for natural gas operation. Optional Kits are available for conversion to propane gas operation. 2. For elevations above 2000 ft. the rating should be reduced by 4% for each 1000 ft. above sea level. The furnace must not be derated, orifice changes should only be made if necessary for alt ...

  • Goodman Mfg ACVC9/AMVC95 - page 22

    BLOWER PERFORMANCE SPECIFICA TIONS 22 1. Units are shipped without filter(s). CFM in chart is without filter(s). 2. All furnaces shipped with heating speed set at "B" and cooling speed set at "D". Installer should adjust blower speed as needed. The first task is to determine the proper aiflow for the cooling system. 3. For most ...

  • Goodman Mfg ACVC9/AMVC95 - page 23

    BLOWER PERFORMANCE SPECIFICA TIONS 23 1. Units are shipped without filter(s). CFM in chart is without filter(s). 2. All furnaces shipped with heating speed set at "B" and cooling speed set at "D". Installer should adjust blower speed as needed. The first task is to determine the proper aiflow for the cooling system. 3. For most ...

  • Goodman Mfg ACVC9/AMVC95 - page 24

    BLOWER PERFORMANCE SPECIFICA TIONS 24 1. Units are shipped without filter(s). CFM in chart is without filter(s). 2. All furnaces shipped with heating speed set at "B" and cooling speed set at "D". Installer should adjust blower speed as needed. The first task is to determine the proper aiflow for the cooling system. 3. For most ...

  • Goodman Mfg ACVC9/AMVC95 - page 25

    BLOWER PERFORMANCE SPECIFICA TIONS 25 1. Units are shipped without filter(s). CFM in chart is without filter(s). 2. All furnaces shipped with heating speed set at "B" and cooling speed set at "D". Installer should adjust blower speed as needed. The first task is to determine the proper aiflow for the cooling system. 3. For most ...

  • Goodman Mfg ACVC9/AMVC95 - page 26

    BLOWER PERFORMANCE SPECIFICA TIONS 26 1. Units are shipped without filter(s). CFM in chart is without filter(s). 2. All furnaces shipped with heating speed set at "B" and cooling speed set at "D". Installer should adjust blower speed as needed. The first task is to determine the proper aiflow for the cooling system. 3. For most ...

  • Goodman Mfg ACVC9/AMVC95 - page 27

    BLOWER PERFORMANCE SPECIFICA TIONS 27 1. Units are shipped without filter(s). CFM in chart is without filter(s). 2. All furnaces shipped with heating speed set at "B" and cooling speed set at "D". Installer should adjust blower speed as needed. The first task is to determine the proper aiflow for the cooling system. 3. For most ...

  • Goodman Mfg ACVC9/AMVC95 - page 28

    BLOWER PERFORMANCE SPECIFICA TIONS 28 1. Units are shipped without filter(s). CFM in chart is without filter(s). 2. All furnaces shipped with heating speed set at "B" and cooling speed set at "D". Installer should adjust blower speed as needed. The first task is to determine the proper aiflow for the cooling system. 3. For most ...

  • Goodman Mfg ACVC9/AMVC95 - page 29

    BLOWER PERFORMANCE SPECIFICA TIONS 29 1. Units are shipped without filter(s). CFM in chart is without filter(s). 2. All furnaces shipped with heating speed set at "B" and cooling speed set at "D". Installer should adjust blower speed as needed. The first task is to determine the proper aiflow for the cooling system. 3. For most ...

  • Goodman Mfg ACVC9/AMVC95 - page 30

    BLOWER PERFORMANCE SPECIFICA TIONS 30 1. Units are shipped without filter(s). CFM in chart is without filter(s). 2. All furnaces shipped with heating speed set at "B" and cooling speed set at "D". Installer should adjust blower speed as needed. The first task is to determine the proper aiflow for the cooling system. 3. For most ...

  • Goodman Mfg ACVC9/AMVC95 - page 31

    BLOWER PERFORMANCE SPECIFICA TIONS 31 1. Units are shipped without filter(s). CFM in chart is without filter(s). 2. All furnaces shipped with heating speed set at "B" and cooling speed set at "D". Installer should adjust blower speed as needed. The first task is to determine the proper aiflow for the cooling system. 3. For most ...

  • Goodman Mfg ACVC9/AMVC95 - page 32

    BLOWER PERFORMANCE SPECIFICA TIONS 32 1. Units are shipped without filter(s). CFM in chart is without filter(s). 2. All furnaces shipped with heating speed set at "B" and cooling speed set at "D". Installer should adjust blower speed as needed. The first task is to determine the proper aiflow for the cooling system. 3. For most ...

  • Goodman Mfg ACVC9/AMVC95 - page 33

    PERFORMANCE 33 30 40 50 60 70 80 90 1 1 0 12 0 100 13 0 14 0 150 100 90 80 70 60 50 40 30 20 10 OU TPUT B TU/ HR x 1 000 BTU OUTPUT vs T EM PERA TURE RISE CHAR T TE M PE R AT U R E R ISE 600 CFM 700 900 100 0 1 100 1200 1400 1600 180 0 2000 2200 2400 CFM FORM ULA S BTU OUTPUT = C FM x 1.08 x R ISE RISE = BTU OUTP UT 1.08 ÷ CFM 800 ...

  • Goodman Mfg ACVC9/AMVC95 - page 34

    HIGH VOL T A GE! DISCONNECT ALL POWER BEFORE SERVICI NG OR INST A LLING THIS UNIT . MUL TIPL E POW ER SOURCES M A Y BE P RESENT . F AI LURE TO DO SO MA Y CAUS E PROPERTY DAM AGE, PERSONAL INJURY OR DEA TH. 34 WIRING DIAGRAMS Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring. N O 2 F U S E 3 A ...

  • Goodman Mfg ACVC9/AMVC95 - page 35

    HI GH VO L T AGE! DISC ONNECT ALL POWE R BEFORE SERVICI NG OR INS T A LLING THIS UNIT . MUL TIPL E POW ER SOURCES MA Y BE P RESENT . F AI LURE TO DO SO MA Y CAUSE PROP ERTY DAMAG E, PERSONAL I NJURY OR DEA TH . 35 Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring. WIRING DIAGRAMS TO +VDC TO M ...

  • Goodman Mfg ACVC9/AMVC95 - page 36

    HIGH VOL T A GE! DISCONNECT ALL POWER BEFORE SERVICI NG OR INST A LLING THIS UNIT . MUL TIPL E POW ER SOURCES M A Y BE P RESENT . F AI LURE TO DO SO MA Y CAUS E PROPERTY DAM AGE, PERSONAL INJURY OR DEA TH. 36 SCHEMA TICS BLOWER ASSEMBLY SCHEMATIC ACVC9/AMVC95/GCVC9/GMVC95_____X* MODEL FURNACES This schematic is for reference only. Not all wiring is ...

  • Goodman Mfg ACVC9/AMVC95 - page 37

    HIGH VOL T A GE! DISCONNECT ALL POWER BEFORE SERVICI NG OR INST A LLING THIS UNIT . MUL TIPL E POW ER SOURCES M A Y BE P RESENT . F AI LURE TO DO SO MA Y CAUS E PROPERTY DAM AGE, PERSONAL INJURY OR DEA TH. 37 SCHEMA TICS TYPICAL SCHEMATIC ACVC9/AMV95/GCVC9/GMVC95_____X* MODEL FURNACES WR 50C51-289 INTEGRATED IGNITION CONTROL This schematic is for r ...

Produzent Goodman Mfg Kategorie Furnace

Dokumente, die wir vom Produzenten des Geräts Goodman Mfg ACVC9/AMVC95 erhalten, können wir in mehrere Gruppen teilen. Unteranderem in:
- technische Zeichnungen Goodman Mfg
- Bedienungsanleitungen ACVC9/AMVC95
- Produktkarten Goodman Mfg
- Informationsbroschüren
- oder Energieetiketten Goodman Mfg ACVC9/AMVC95
Jede von ihnen ist wichtig, jedoch finden wir die wichtigsten Informationen für den Nutzer des Geräts in der Bedienungsanleitung Goodman Mfg ACVC9/AMVC95.

Die Dokumentengruppe, die als Bedienungsanleitungen bezeichnet wird, wird ebenfalls in detaillierte Arten geteilt, solche wie: Montageanleitungen Goodman Mfg ACVC9/AMVC95, Wartungsanleitungen, Kurzanleitungen oder Benutzeranleitungen Goodman Mfg ACVC9/AMVC95. Abhängig vom Bedarf, sollten Sie das Dokument finden, das Sie brauchen. In unserem Service können Sie sich die populärste Bedienungsanleitung des Produkts Goodman Mfg ACVC9/AMVC95 ansehen.

Ähnliche Bedienungsanleitungen

Die komplette Bedienungsanleitung des Geräts Goodman Mfg ACVC9/AMVC95, wie sollte sie aussehen?
Die Bedienungsanleitung, auch bezeichnet als Benutzerhandbuch, oder einfach nur „Anleitung”, ist ein technisches Dokument, das dem Benutzer bei der Nutzung von Goodman Mfg ACVC9/AMVC95 hilfreich sein soll. Die Bedienungsanleitungen werden in der Regel von technischen Schriftstellern geschrieben, aber in einer Sprache, die für alle Nutzer von Goodman Mfg ACVC9/AMVC95 verständlich ist.

Eine gänzliche Bedienungsanleitung von Goodman Mfg sollte einige Grundelemente enthalten. Ein Teil von ihnen ist nicht so wichtig, wie z.B.: die Titelseite oder Autorenseiten. Die restlichen von ihnen jedoch, sollten Informationen liefern, die für den Nutzer von enormer Wichtigkeit sind.

1. Einführung und Hinweise, wie man sich in einer Bedienungsanleitung von Goodman Mfg ACVC9/AMVC95 bewegt - Am Anfang jeder Bedienungsanleitung sollten wir Hinweise bezüglich der Nutzungsart eines bestimmten Ratgebers finden. In ihr sollten sich Informationen über die Lokalisierung des Inhaltsverzeichnisses von Goodman Mfg ACVC9/AMVC95 befinden, FAQ oder über oft auftretende Probleme – also Stellen, die von den Benutzern in jeder Bedienungsanleitung am meisten gesucht werden
2. Inhaltsverzeichnis - Index aller Ratschläge bezüglich Goodman Mfg ACVC9/AMVC95, die wir im aktuellen Dokument finden
3. Ratschläge zur Nutzung der Grundfunktionen des Geräts Goodman Mfg ACVC9/AMVC95 - die uns die ersten Schritte während der Nutzung von Goodman Mfg ACVC9/AMVC95 erleichtern sollten
4. Troubleshooting - geordneter Tätigkeitslauf, der uns bei der Diagnose und als nächstes bei der Lösung wichtiger Probleme mit Goodman Mfg ACVC9/AMVC95 hilft
5. FAQ - häufig gestellte Fragen
6. Kontaktdaten Informationen darüber, wo man Kontakt zum Produzenten / Service von Goodman Mfg ACVC9/AMVC95 im bestimmten Land suchen kann, wenn es nicht gelingt, das Problem selbst zu lösen.

Haben Sie eine Frage bezüglich Goodman Mfg ACVC9/AMVC95?

Nutzen Sie das untere Formular

Wenn Sie mit Hilfe der gefundenen Bedienungsanleitung Ihr Problem mit Goodman Mfg ACVC9/AMVC95 nicht gelöst haben, stellen Sie eine Frage, indem Sie das untere Formular nutzen. Wenn einer der Nutzer ein ähnliches Problem mit Goodman Mfg ACVC9/AMVC95 hatte, ist es möglich, dass er mit Ihnen die Lösung teilen möchte.

Text vom Bild übertragen

Kommentare (0)