Bedienungsanleitung Simplicity LINC GATEWAY 514067-UAD-A-0509

18 Seiten 0.81 mb
Download

Zur Seite of 18

Summary
  • Simplicity LINC GATEWAY 514067-UAD-A-0509 - page 1

    514067-UAD-A- 0509 APPLICATION GUIDE OVERVIEW The Simplicity ® LINC Gateway operates as a Modbus® Client providing an interface between a BACnet® MS/TP control system and devices that communicate using the Modbus RTU protocol. The Simplicity ® LINC allows monitoring and cont rol by a third-party BACnet Building Automation System (BAS). The Simp ...

  • Simplicity LINC GATEWAY 514067-UAD-A-0509 - page 2

    514067-UAD -A-0509 2 Johnson Controls Unitary Products CONNECTION The Simplicity ® LINC has 2 ports, one fo r connection to the BAS network (BACnet) and one to the Simplicity ® board (Modbus). BACNET NETWORK The only connection required in the field is to the BACnet (BAS) network. NOTE: Proper termination and groun ding of the shields must be obs ...

  • Simplicity LINC GATEWAY 514067-UAD-A-0509 - page 3

    514067-UAD-A-0509 Johnson Controls Unitary Products 3 FLASH MEMORY MANAGEMENT The Flash Memory chip used in the Simp licity ® controllers has a 1,000,000 write cycle rating. To prevent premature failure of the flash memory, it should not be written to more often than once every 10 minutes, on average. ADDITIONAL CAPABILITY MODBUS COMMUNICATION ALA ...

  • Simplicity LINC GATEWAY 514067-UAD-A-0509 - page 4

    514067-UAD -A-0509 4 Johnson Controls Unitary Products TABLE 2: POINTS LIST IN DESCRIPTION ORDER Read/ Write BACnet Object T ype BACnet Object Inst Descriptor Default Min Max Point Description R (2) A V 14 ACC_OVER_TME – – – Accumulated Unoccupied Override T ime (in hours) R (2) A V 15 ACTIVE_ALARM – – – Active Alarm R (5) BV 16 AIR_PRO ...

  • Simplicity LINC GATEWAY 514067-UAD-A-0509 - page 5

    514067-UAD-A-0509 Johnson Controls Unitary Products 5 TABLE 2: POINTS LIST IN DESCRIPTION ORDER (CONTINUED) Read/ Write BACnet Object T ype BACnet Object Inst Descriptor Default Min Max Point Description R/W (2) A V 20 ECO_1ST_STPT 55 40 65 Economizer First Stage Setpoint R (5) BV 7 ECONO_INST – – – Economizer Installed R (5) BV 36 ECO_L_TO_S ...

  • Simplicity LINC GATEWAY 514067-UAD-A-0509 - page 6

    514067-UAD -A-0509 6 Johnson Controls Unitary Products TABLE 2: POINTS LIST IN DESCRIPTION ORDER (CONTINUED) Read/ Write BACnet Object T ype BACnet Object Inst Descriptor Default Min Max Point Description R (5) BV 44 E_HPS1 – – – Elite High Pressure Switch for Compressor #1 Input Status (1=closed, 0=open/fault) R (5) BV 48 E_HPS2 – – – ...

  • Simplicity LINC GATEWAY 514067-UAD-A-0509 - page 7

    514067-UAD-A-0509 Johnson Controls Unitary Products 7 TABLE 2: POINTS LIST IN DESCRIPTION ORDER (CONTINUED) Read/ Write BACnet Object T ype BACnet Object Inst Descriptor Default Min Max Point Description R (5) BV 66 E_FREEZE_ST – – – Hot H2O Freeze Thermostat Switch #1 Input Status (1=closed, 0=open/fault) R (2) A V 55 HW_VL V_OUT – – – ...

  • Simplicity LINC GATEWAY 514067-UAD-A-0509 - page 8

    514067-UAD -A-0509 8 Johnson Controls Unitary Products TABLE 2: POINTS LIST IN DESCRIPTION ORDER (CONTINUED) Read/ Write BACnet Object T ype BACnet Object Inst Descriptor Default Min Max Point Description R (5) BV 14 LOW_SUP_VOL T – – – Low Supply V oltage (0=comps not overrid- den by LSV , 1=comps overridden) R/W (5) BV 96 MANUAL_WRITE – ? ...

  • Simplicity LINC GATEWAY 514067-UAD-A-0509 - page 9

    514067-UAD-A-0509 Johnson Controls Unitary Products 9 TABLE 2: POINTS LIST IN DESCRIPTION ORDER (CONTINUED) Read/ Write BACnet Object T ype BACnet Object Inst Descriptor Default Min Max Point Description R/W (2) A V 71 SPCE_ALM_TMP 0 0 25 Space Sensor Alarm T emperature (degrees F , 0 = disabled) R/W (2) A V 72 SPCE_ALM_TIM 0 0 120 Space Sensor Ala ...

  • Simplicity LINC GATEWAY 514067-UAD-A-0509 - page 10

    514067-UAD -A-0509 10 Johnson Controls Unitary Products TABLE 3: POINTS LIST IN OBJECT ORDER Read/ Write BACnet Object T ype BACnet Object Inst Descriptor Default Min Max Point Description R/W (2) A V 1 OCC_COOL_SP 72 45 99 Occupied Cooling Setpoint R/W (2) A V 2 UNOC_COOL_SP 85 45 99 Un-Occupied Cooling Setpoint R/W (2) A V 3 SA T_COOL_SP 50 40 65 ...

  • Simplicity LINC GATEWAY 514067-UAD-A-0509 - page 11

    514067-UAD-A-0509 Johnson Controls Unitary Products 11 TABLE 3: POINTS LIST IN OBJECT ORDER (CONTINUED) Read/ Write BACnet Object T ype BACnet Object Inst Descriptor Default Min Max Point Description R (2) A V 38 ALARM_3 – – – System Alarm #3 R (2) A V 39 ALARM_4 – – – System Alarm #4 R (2) A V 40 ALARM_5 – – – System Alarm #5 R ( ...

  • Simplicity LINC GATEWAY 514067-UAD-A-0509 - page 12

    514067-UAD -A-0509 12 Johnson Controls Unitary Products TABLE 3: POINTS LIST IN OBJECT ORDER (CONTINUED) Read/ Write BACnet Object T ype BACnet Object Inst Descriptor Default Min Max Point Description R/W (2) A V 69 OP_STPT_DIF 1 1 5 Operating Setpoint Differential R/W (2) A V 70 SA T_ALM_COOL 0 0 80 Supply Air T emperature Alarm Setpoint for Cooli ...

  • Simplicity LINC GATEWAY 514067-UAD-A-0509 - page 13

    514067-UAD-A-0509 Johnson Controls Unitary Products 13 TABLE 3: POINTS LIST IN OBJECT ORDER (CONTINUED) Read/ Write BACnet Object T ype BACnet Object Inst Descriptor Default Min Max Point Description R (5) BV 19 LOW_AMB_OVRD – – – Low Ambient T emperature (0=comps not overridden by LA T , 1=comps overridden) R (5) BV 20 POP_ENABLED – – ? ...

  • Simplicity LINC GATEWAY 514067-UAD-A-0509 - page 14

    514067-UAD -A-0509 14 Johnson Controls Unitary Products TABLE 3: POINTS LIST IN OBJECT ORDER (CONTINUED) Read/ Write BACnet Object T ype BACnet Object Inst Descriptor Default Min Max Point Description R (5) BV 47 E_LPS2 – – – Elite Low Pressure Switch for Compressor #2 Input Status (1=closed, 0=open/fault) R (5) BV 48 E_HPS2 – – – Elite ...

  • Simplicity LINC GATEWAY 514067-UAD-A-0509 - page 15

    514067-UAD-A-0509 Johnson Controls Unitary Products 15 TABLE 3: POINTS LIST IN OBJECT ORDER (CONTINUED) Read/ Write BACnet Object T ype BACnet Object Inst Descriptor Default Min Max Point Description R (5) BV 71 I_IF AN_ST A T – – – Intelli-Comfort Indoor Fan Output Status (0=output is OFF , 1=output is ON) R (5) BV 72 I_F AN_OVER – – – ...

  • Simplicity LINC GATEWAY 514067-UAD-A-0509 - page 16

    514067-UAD -A-0509 16 Johnson Controls Unitary Products TROUBLESHOOTING The Simplicity ® LINC Gateway consists of two printed circuit boards. TABLE 4: SIMPLICITY ® LINC GATEWAY RS485 BOARD (Bottom) BacNET Board (Top) Normal Board Op eration Normal Board Op eration The PWR LED should be on during operation. The RX and T X LEDs should flash when a ...

  • Simplicity LINC GATEWAY 514067-UAD-A-0509 - page 17

    514067-UAD-A-0509 Johnson Controls Unitary Products 17 FIGURE 3: SIMPLICITY ® LINC GATEWAY LED LOCATION PWR (RS485) PWR (BACnet) GP105 (BACnet) LB (BACnet) RX (RS485) TX (RS485) LA (BACnet) TX (BACnet) RX (BACnet) ...

  • Simplicity LINC GATEWAY 514067-UAD-A-0509 - page 18

    Subject to change without notice. Print ed in U.S.A. 514067-UAD-A-0509 Copyright © 2009 by Johnson Controls, Inc. Al l rights reserved. Supersedes: Nothing Johnson Contro ls Unitary Products 5005 York Drive Norman, OK 73069 ...

Produzent Simplicity Kategorie Network Router

Dokumente, die wir vom Produzenten des Geräts Simplicity LINC GATEWAY 514067-UAD-A-0509 erhalten, können wir in mehrere Gruppen teilen. Unteranderem in:
- technische Zeichnungen Simplicity
- Bedienungsanleitungen LINC GATEWAY 514067-UAD-A-0509
- Produktkarten Simplicity
- Informationsbroschüren
- oder Energieetiketten Simplicity LINC GATEWAY 514067-UAD-A-0509
Jede von ihnen ist wichtig, jedoch finden wir die wichtigsten Informationen für den Nutzer des Geräts in der Bedienungsanleitung Simplicity LINC GATEWAY 514067-UAD-A-0509.

Die Dokumentengruppe, die als Bedienungsanleitungen bezeichnet wird, wird ebenfalls in detaillierte Arten geteilt, solche wie: Montageanleitungen Simplicity LINC GATEWAY 514067-UAD-A-0509, Wartungsanleitungen, Kurzanleitungen oder Benutzeranleitungen Simplicity LINC GATEWAY 514067-UAD-A-0509. Abhängig vom Bedarf, sollten Sie das Dokument finden, das Sie brauchen. In unserem Service können Sie sich die populärste Bedienungsanleitung des Produkts Simplicity LINC GATEWAY 514067-UAD-A-0509 ansehen.

Ähnliche Bedienungsanleitungen

Die komplette Bedienungsanleitung des Geräts Simplicity LINC GATEWAY 514067-UAD-A-0509, wie sollte sie aussehen?
Die Bedienungsanleitung, auch bezeichnet als Benutzerhandbuch, oder einfach nur „Anleitung”, ist ein technisches Dokument, das dem Benutzer bei der Nutzung von Simplicity LINC GATEWAY 514067-UAD-A-0509 hilfreich sein soll. Die Bedienungsanleitungen werden in der Regel von technischen Schriftstellern geschrieben, aber in einer Sprache, die für alle Nutzer von Simplicity LINC GATEWAY 514067-UAD-A-0509 verständlich ist.

Eine gänzliche Bedienungsanleitung von Simplicity sollte einige Grundelemente enthalten. Ein Teil von ihnen ist nicht so wichtig, wie z.B.: die Titelseite oder Autorenseiten. Die restlichen von ihnen jedoch, sollten Informationen liefern, die für den Nutzer von enormer Wichtigkeit sind.

1. Einführung und Hinweise, wie man sich in einer Bedienungsanleitung von Simplicity LINC GATEWAY 514067-UAD-A-0509 bewegt - Am Anfang jeder Bedienungsanleitung sollten wir Hinweise bezüglich der Nutzungsart eines bestimmten Ratgebers finden. In ihr sollten sich Informationen über die Lokalisierung des Inhaltsverzeichnisses von Simplicity LINC GATEWAY 514067-UAD-A-0509 befinden, FAQ oder über oft auftretende Probleme – also Stellen, die von den Benutzern in jeder Bedienungsanleitung am meisten gesucht werden
2. Inhaltsverzeichnis - Index aller Ratschläge bezüglich Simplicity LINC GATEWAY 514067-UAD-A-0509, die wir im aktuellen Dokument finden
3. Ratschläge zur Nutzung der Grundfunktionen des Geräts Simplicity LINC GATEWAY 514067-UAD-A-0509 - die uns die ersten Schritte während der Nutzung von Simplicity LINC GATEWAY 514067-UAD-A-0509 erleichtern sollten
4. Troubleshooting - geordneter Tätigkeitslauf, der uns bei der Diagnose und als nächstes bei der Lösung wichtiger Probleme mit Simplicity LINC GATEWAY 514067-UAD-A-0509 hilft
5. FAQ - häufig gestellte Fragen
6. Kontaktdaten Informationen darüber, wo man Kontakt zum Produzenten / Service von Simplicity LINC GATEWAY 514067-UAD-A-0509 im bestimmten Land suchen kann, wenn es nicht gelingt, das Problem selbst zu lösen.

Haben Sie eine Frage bezüglich Simplicity LINC GATEWAY 514067-UAD-A-0509?

Nutzen Sie das untere Formular

Wenn Sie mit Hilfe der gefundenen Bedienungsanleitung Ihr Problem mit Simplicity LINC GATEWAY 514067-UAD-A-0509 nicht gelöst haben, stellen Sie eine Frage, indem Sie das untere Formular nutzen. Wenn einer der Nutzer ein ähnliches Problem mit Simplicity LINC GATEWAY 514067-UAD-A-0509 hatte, ist es möglich, dass er mit Ihnen die Lösung teilen möchte.

Text vom Bild übertragen

Kommentare (0)