    347337-UIM-A-0408 R-22 OUTDOOR SPLIT -SYSTEM AIR CONDITIONING MODELS: 13 SEER A Y018-030 SERIES 1.5 TO 2.5 T ONS INSTALLATION MANUAL LISTED ISO 9001 Certified Quality Management System SECTION I: GENERAL The outdoor units are designed to be connected to a matching indoor coil with sweat connect lines. Sweat connect units are factory charged with re ...

  • Johnson Controls 13 SEER - page 2

    347337-UIM-A-0408 2 Johnson Controls Unitary Products SECTION III: UNIT INST ALLA TION LOC A T IO N Before starting the installation, select and check the suitability of the location for both the indoor and outdoor unit. Observe all limitations and clearance requirements. The outdoor unit must have sufficient clearance for air entrance to the conde ...

  • Johnson Controls 13 SEER - page 3

    347337-UIM-A-0408 Johnson Controls Unitary Produ cts 3 PIPING CONNECTIONS The outdoor condensing unit must be connected to the indoor evapora - tor coil using field supplied r efrigerant grade (ACR) co pper tubing that is internally clean and dry . Units shoul d be installed only with the tubing sizes for approved system combinations as specified i ...

  • Johnson Controls 13 SEER - page 4

    347337-UIM-A-0408 4 Johnson Controls Unitary Products Connect the refrigerant lines u sing the following proced ure: 1. Remove the cap and Schrader core from both the liquid and vapor service valve service ports at the outdoor unit. Connect low pres- sure nitrogen to the liquid line service port. 2. Braze the liquid line to the liqui d valve at the ...

  • Johnson Controls 13 SEER - page 5

    347337-UIM-A-0408 Johnson Controls Unitary Produ cts 5 SECTION V : INST ALLA TIONS REQUIRING AN ADD-ON TXV KIT For installations requiring a TXV kit, refer to the Installation Instruct ions accompanying the TXV kit. SECTION VI: EV ACU A TI ON It will be necessary to evacuate the system to 500 microns or less. If a leak is suspected, leak test with ...

  • Johnson Controls 13 SEER - page 6

    347337-UIM-A-0408 6 Johnson Controls Unitary Products SECTION VIII: ELECTRICAL CONNECTIONS GENERAL INFORMA TION & GROUNDING Check the electrical supply to be sure that it meets the values specified on the unit nameplate and wiring label. Power wiring, control (low voltage) wiring, disconnect switch es and over current protection must be supplie ...

  • Johnson Controls 13 SEER - page 7

    347337-UIM-A-0408 Johnson Controls Unitary Produ cts 7 For additional connection diagrams for a ll UP G equipment refer to “Low V oltage System Wiring” document available online at www . upgnet.com in the Product Catalog Section. FIGURE 9: Thermostat Chart - Single S tage AC with PSC Air Handler AC 1A Single Stage Air Conditioner – PSC Air Ha ...

  • Johnson Controls 13 SEER - page 8

    347337-UIM-A-0408 8 Johnson Controls Unitary Products FIGURE 10: Thermostat Chart - Single S tage AC with PSC Air Handler AC 1B Single Stage Air Conditioner – PSC Air Handler C 24 – Volt Comm on Y Compressor Contactor SINGLE STAGE AIR CONDIT IONER MA SHP AHP ID MODELS SINGLE STAGE AIR CONDIT I O N ER Other Part Nu mbers: SAP = Legacy 265902 = 0 ...

  • Johnson Controls 13 SEER - page 9

    347337-UIM-A-0408 Johnson Controls Unitary Produ cts 9 FIGURE 1 1: Thermostat Chart - Single St age AC with PSC Fur nace AC 5D Single Stage Air Conditioner – Single Stage PSC Furnace HM1 Humidistat Y Full Stage Compressor G Fan *PP11C70224 THERMOSTAT RH 24 – Volt Hot (Heat XFMR) RC 24 – Volt Hot (Cool XFMR) W Full Stage Heat Clipping Jump er ...

  • Johnson Controls 13 SEER - page 10

    347337-UIM-A-0408 10 Johnson Controls Unitary Products FIGURE 12: Thermostat Chart - Single S tage AC with PSC Furnace AC 5E Single Stage Air Conditioner – Single Stage PSC Furnace C 24 – Volt Comm on Y Compressor Contactor SINGLE STAGE AIR CONDIT IONER SINGLE STAGE AIR CONDIT I O N ER Y Full Stage Compressor G Fan *BP11C50124 *BN11C01124 *DP11 ...

  • Johnson Controls 13 SEER - page 11

    347337-UIM-A-0408 Johnson Controls Unitary Produ cts 11 INDICA TIONS OF PROPER OPERA TION Cooling 1. The outdoor fan should be running, with warm air being dis- charged from the top of the unit. 2. The indoor blower (furnace or air handler) will be operating, dis- charging cool air from the ducts. Co ils or other parts in the air cir- cuit should b ...

  • Johnson Controls 13 SEER - page 12

    Subject to change without notice. Printed in U.S.A. 347337-UIM-A-0408 Copyright © 2008 by Johnson Controls, Inc. All rights reserved. Supersedes: 259715-UIM-A-0606 Johnson Contro ls Unitary Produc t s 5005 Y ork Driv e Norman, OK 7306 NOTES ...

Produzent Johnson Controls Kategorie Air Conditioner

Dokumente, die wir vom Produzenten des Geräts Johnson Controls 13 SEER erhalten, können wir in mehrere Gruppen teilen. Unteranderem in:
- technische Zeichnungen Johnson Controls
- Bedienungsanleitungen 13 SEER
- Produktkarten Johnson Controls
- Informationsbroschüren
- oder Energieetiketten Johnson Controls 13 SEER
Jede von ihnen ist wichtig, jedoch finden wir die wichtigsten Informationen für den Nutzer des Geräts in der Bedienungsanleitung Johnson Controls 13 SEER.

Die Dokumentengruppe, die als Bedienungsanleitungen bezeichnet wird, wird ebenfalls in detaillierte Arten geteilt, solche wie: Montageanleitungen Johnson Controls 13 SEER, Wartungsanleitungen, Kurzanleitungen oder Benutzeranleitungen Johnson Controls 13 SEER. Abhängig vom Bedarf, sollten Sie das Dokument finden, das Sie brauchen. In unserem Service können Sie sich die populärste Bedienungsanleitung des Produkts Johnson Controls 13 SEER ansehen.

Die komplette Bedienungsanleitung des Geräts Johnson Controls 13 SEER, wie sollte sie aussehen?
Die Bedienungsanleitung, auch bezeichnet als Benutzerhandbuch, oder einfach nur „Anleitung”, ist ein technisches Dokument, das dem Benutzer bei der Nutzung von Johnson Controls 13 SEER hilfreich sein soll. Die Bedienungsanleitungen werden in der Regel von technischen Schriftstellern geschrieben, aber in einer Sprache, die für alle Nutzer von Johnson Controls 13 SEER verständlich ist.

Eine gänzliche Bedienungsanleitung von Johnson Controls sollte einige Grundelemente enthalten. Ein Teil von ihnen ist nicht so wichtig, wie z.B.: die Titelseite oder Autorenseiten. Die restlichen von ihnen jedoch, sollten Informationen liefern, die für den Nutzer von enormer Wichtigkeit sind.

1. Einführung und Hinweise, wie man sich in einer Bedienungsanleitung von Johnson Controls 13 SEER bewegt - Am Anfang jeder Bedienungsanleitung sollten wir Hinweise bezüglich der Nutzungsart eines bestimmten Ratgebers finden. In ihr sollten sich Informationen über die Lokalisierung des Inhaltsverzeichnisses von Johnson Controls 13 SEER befinden, FAQ oder über oft auftretende Probleme – also Stellen, die von den Benutzern in jeder Bedienungsanleitung am meisten gesucht werden
2. Inhaltsverzeichnis - Index aller Ratschläge bezüglich Johnson Controls 13 SEER, die wir im aktuellen Dokument finden
3. Ratschläge zur Nutzung der Grundfunktionen des Geräts Johnson Controls 13 SEER - die uns die ersten Schritte während der Nutzung von Johnson Controls 13 SEER erleichtern sollten
4. Troubleshooting - geordneter Tätigkeitslauf, der uns bei der Diagnose und als nächstes bei der Lösung wichtiger Probleme mit Johnson Controls 13 SEER hilft
5. FAQ - häufig gestellte Fragen
6. Kontaktdaten Informationen darüber, wo man Kontakt zum Produzenten / Service von Johnson Controls 13 SEER im bestimmten Land suchen kann, wenn es nicht gelingt, das Problem selbst zu lösen.

Haben Sie eine Frage bezüglich Johnson Controls 13 SEER?

Nutzen Sie das untere Formular

Wenn Sie mit Hilfe der gefundenen Bedienungsanleitung Ihr Problem mit Johnson Controls 13 SEER nicht gelöst haben, stellen Sie eine Frage, indem Sie das untere Formular nutzen. Wenn einer der Nutzer ein ähnliches Problem mit Johnson Controls 13 SEER hatte, ist es möglich, dass er mit Ihnen die Lösung teilen möchte.

Text vom Bild übertragen

Kommentare (0)