    INST ALLA TION AND OPERA TING INSTRUCTIONS RayT emp™ Hot W ater Energy Management Contr ol Catalog No: 5000.61B Effective: 04-15-05 Replaces: 09-01-02 P/N 241098 ...

  • Raypak RayTemp Hot Water Energy Management Control - page 2

    2 Section 1. GETTING ST ARTED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 THE BIG PICTURE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 WHA T COMES WITH THE CONTROLL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4 Section 2. IN ...

  • Raypak RayTemp Hot Water Energy Management Control - page 3

    3 THE BIG PICTURE This RayT emp control is designed to make recirculating domestic hot water heating systems ener gy efficient. In a r ecirculating sys- tem, hot water is continuously pumped throughout the building. This lar ge loop has many branch- es which extend to fixtures in the rooms. It is essentially a giant radiator which has tremendous he ...

  • Raypak RayTemp Hot Water Energy Management Control - page 4

    4 WHA T COMES WITH THE CONTROL Before arriving at the job site to begin the installation, it’ s important to first inspect the system and determine what materials you will need. Some parts are included with the control while the oth- ers you will need to provide. Check the following list to verify that you received the following parts. 1 Control ...

  • Raypak RayTemp Hot Water Energy Management Control - page 5

    5 On the sensor end, roll the shielding and tape so it will not contact a conductor . On the control end, the shield should be grounded. Do not ground both ends of the shielding. A void routing wiring on or near other electrical wires, conduit, motors, spark igniters or other sources of high, intermittent voltage or current. EMI (spikes) can disrup ...

  • Raypak RayTemp Hot Water Energy Management Control - page 6

    6 Fig # 8285.2 INST ALLA TION LA YOUT ...

  • Raypak RayTemp Hot Water Energy Management Control - page 7

    7 ”DIP” SWITCH SETTINGS ON CIRCUIT BOARD CAUTION: Incorrect DIP switch settings may damage the RayT emp!!! Make all adjustments with ALL power off. The four relay outputs are factory set for normally closed dry contacts. These DIP switches ar e located behind the terminal block, on the right side. The black dots in the diagram indicate where to ...

  • Raypak RayTemp Hot Water Energy Management Control - page 8

    CONNECTING THE OPTIONAL “ELSA” BRAND MODEM Raypak recommends the ELSA Microlink 56k modem for data communication. This modem will work with RayT emp and technical support will be provided if this modem is installed with the cor- rect cables. Raypak will not be able to provide support if you use other modem brands or build your own cables. In ei ...

  • Raypak RayTemp Hot Water Energy Management Control - page 9

    9 USING THE FRONT P ANEL TO CHECK SENSORS AND RELA YS The RayT emp front panel features an alphanumeric LCD display of four r ows by 20 lines. Six keys are provided to select scr eens, fields, and make pr ogram changes. The up-arrow and down-arr ow "WINDOW" keys are used to step thru each of the screens. The down-arr ow screen selects the ...

  • Raypak RayTemp Hot Water Energy Management Control - page 10

    10 Section 3. CONNECTING A COMPUTER This section explains how to connect your personal computer to the RayT emp. Once connected, you can view all of the front panel screens cover ed in the previous section. Y ou can also retrieve the recorded data and view color graphs of temperatur e and demand profiles. "PTT" is the option- al software ...

  • Raypak RayTemp Hot Water Energy Management Control - page 11

    11 INST ALLING PTT SOFTW ARE ON YOUR PC This section provides instructions for installing PTT communication software. First insert the PTT CD into your CD drive. Double click on the folder Ptt258 then double click on Install. The PTT communication software will then be installed on your C:GBX subdirectory . T o run PTT , type PTT (then press enter ...

  • Raypak RayTemp Hot Water Energy Management Control - page 12

    12 READING LOGGED DA T A Under the "History Report" menu item, logged data can be retrieved from a RayT emp control, saved to a disk file, viewed graphically on screen, or output to a printer . T o retrieve history , con- nect the RayT emp serial cable between the RayT emp and your laptop PC. Then select "Retrieve". The RayT emp ...

  • Raypak RayTemp Hot Water Energy Management Control - page 13

    13 T o end the modem session, select the following screen in the LapT op window . This screen is used to terminate the call. The RayT emp will actually terminate the phone connection and prevent the modem from answering the phone for about five minutes. The message "CARRIER LOST" will appear in the LapT op window . Another call may then b ...

  • Raypak RayTemp Hot Water Energy Management Control - page 14

    14 Section 4. PROGRAMMING QUICK REFERENCE This section describes all the programmable features of the contr ol. Y ou make program changes from the front panel or by using a laptop. For information on connection with a LapT op using PTT software, refer to the pr evious section. The following keys provide access to all RayT emp display and programmin ...

  • Raypak RayTemp Hot Water Energy Management Control - page 15

    15 Screen code and description, in sequence of appearance See page FM PRODUCT IDENTIFICA TION - Model, type, and version 17 SE SENSORS - Displays temperature of each standard sensor 17 OS OPTIONAL SENSORS - Displays other sensors 17 RT RELA Y TEST - On/Off relay status and manual override 17 ST SENSOR TEST - Simulates sensor temperatures 23 RM RUN ...

  • Raypak RayTemp Hot Water Energy Management Control - page 16

    16 Screen Code and Description - continued See page HL SELECT - Supply High Limit 20 LL SELECT - Supply Low Limit 20 DW SELECT - Demand window in minutes 20 DM SELECT - Demand % for maximum temperature 20 DA SELECT - Demand % for ASL strategy 20 R0 SELECT - # of Room Sensors Installed 21 R1 SELECT - Desired Daytime Room T emperatur e 21 R2 SELECT - ...

  • Raypak RayTemp Hot Water Energy Management Control - page 17

    17 FIRST SCREEN A T POWER-UP FM PRODUCT IDENTIFICA TION. This screen displays the model number , type of control, copyright notice, and software version number . Press F2 to select the next screen in or der , or press two keys for direct access to any one of the following screens. MANUAL OVERRIDE MO SELECT (MODE) - Operating Mode selects one of thr ...

  • Raypak RayTemp Hot Water Energy Management Control - page 18

    18 ERASE MEMORY / RESET PROGRAM ER ERASE/RESET - Press F4 or F5 to select which item will be r eset or cleared, then press CTRL+E to confirm each action. Set BAUD Rate will reconfigure the serial port accor ding to the BA screen. If the speed is differ- ent, then reset the BAUD rate on your LapT op (garbage characters will appear). Zero Run Meters ...

  • Raypak RayTemp Hot Water Energy Management Control - page 19

    19 TIME SCHEDULE TS TIME SCHEDULE This is a seven-day time clock. Each line is a program for starting a new period (such as Night) on a day (such as M-F) and at a time (such as 6:00 am). Up to 20 lines can be displayed or programmed using the SP ACE, F4 and F5 keys. Periods end automatically when a new one starts. The day codes are M-F (Monday thru ...

  • Raypak RayTemp Hot Water Energy Management Control - page 20

    20 C6 SELECT - Maximum Extra T emperature C6 and C7 are an extra set of temperatures which can be scheduled for any purpose. They will become the maximum and minimum supply temperature if the Extra schedule is activated by the time clock. Default T emp 140°F . C7 SELECT - Minimum Extra T emperature See C6 above. Default T emp 130°F . HL SELECT - ...

  • Raypak RayTemp Hot Water Energy Management Control - page 21

    21 RETURN TEMPERA TURE The return sensor is used to compensate for seasonal changes in loop heat loss. The strategy may raise the supply/branch temperature in cold weather to ensure that the last r ooms on the loop have hot enough water even during low demand periods. R0 SELECT - Return Sensor Installed Select YES if this sensor is connected, other ...

  • Raypak RayTemp Hot Water Energy Management Control - page 22

    22 BRANCH TEMPERA TURE - NOT USED B0 SELECT - # of Branch Sensors Installed Not used. RELA Y SEQUENCING HS SELECT - # of Heaters Enter 1 thru 4 for the number of heaters connected to relay out- puts 1 thru 4. This allows the RayT emp to correctly sequence heaters and recor d demand. SP - SELECT - Stages Per Heater Enter the number of stages in each ...

  • Raypak RayTemp Hot Water Energy Management Control - page 23

    23 DD SELECT - Differential Increasing DD lengthens the heater burn cycle; decr easing DD improves temperature stability . For instance: desired=140, deadband=1, heater turns off at 141 and on at 139. This deadband applies equally to all stages. D1 SELECT - T emperature Delay Between Stages (In addition to dif ferential setting) This value causes s ...

  • Raypak RayTemp Hot Water Energy Management Control - page 24

    24 SA VINGS TEST SETUP S1 SELECT - Day of Month for Savings T est Selecting a value other than 0 (default) acti- vates the flip-flop savings test. This test will cause a simulation of conditions before the RayT emp was installed - for 24 hours on the day specified every month. The test will run only on the day of month selected AND on multiples of ...

  • Raypak RayTemp Hot Water Energy Management Control - page 25

    25 T otal days in service displays the total operating days in modes RUN, BYP ASS, and OFF . When 24 V AC power is absent this value will not increase however the clock will still operate. Number of power interruptions value is incremented each time 24 V AC power is removed or inter- rupted. ASL strategy temp reduced a value other than zero indicat ...

  • Raypak RayTemp Hot Water Energy Management Control - page 26

    26 LOCA TION TEXT DN TEXT - Company Name Accepts entry of company name into RayT emp memory . This information will appear in installation reports. Edit with SP ACE, BACKSP , F4, and F5. PN TEXT - Property Name Accepts entry of site name into RayT emp memory . This informa- tion will appear in installation reports. Edit with SP ACE, BACKSP , F4, an ...

  • Raypak RayTemp Hot Water Energy Management Control - page 27

    27 F AX MODEM SETUP AND TEST FD TEXT - Fax Dial-Out Use this screen to enter the phone number of the fax machine which is to receive fax alarm messages, installation reports, and/or graphics. Example "A TDT5551212". Edit text with SP ACE, BACKSP , F4, and F5. XX V ALUE - Fax Graph Max T emp This value sets the highest value of the Y -axis ...

  • Raypak RayTemp Hot Water Energy Management Control - page 28

    28 XH V ALUE - Fax on Hour of Day This option sets the time of day to transmit fax reports. It works in conjunction with XW and XM, above. The RayT emp will attempt to fax the specified data on the specified day (above) and at this specified time. Military time is used with values of 0 to 23, 12 is noon. If the first attempt is not successful then ...

  • Raypak RayTemp Hot Water Energy Management Control - page 29

    29 W ARRANTY The Raypak RayT emp Control is warranted to be free from defects in material and workmanship for a peri- od of one year from the date of installation or fourteen months from date of shipment, whichever occurs first. THE FORGOING W ARRANTY IS IN LIEU OF AND EXCLUDES ALL OTHER W ARRANTIES NOT EXPRESS- L Y SET FORTH HEREIN, WHETHER EXPRES ...

  • Raypak RayTemp Hot Water Energy Management Control - page 30

    Raypak Inc., 2151 Eastman A venue, Oxnard, CA 93030 • (805) 278-5300 • (800) 872-9725 www .raypak.com ...

Produzent Raypak Kategorie Water Heater

Dokumente, die wir vom Produzenten des Geräts Raypak RayTemp Hot Water Energy Management Control erhalten, können wir in mehrere Gruppen teilen. Unteranderem in:
- technische Zeichnungen Raypak
- Bedienungsanleitungen RayTemp Hot Water Energy Management Control
- Produktkarten Raypak
- Informationsbroschüren
- oder Energieetiketten Raypak RayTemp Hot Water Energy Management Control
Jede von ihnen ist wichtig, jedoch finden wir die wichtigsten Informationen für den Nutzer des Geräts in der Bedienungsanleitung Raypak RayTemp Hot Water Energy Management Control.

Die Dokumentengruppe, die als Bedienungsanleitungen bezeichnet wird, wird ebenfalls in detaillierte Arten geteilt, solche wie: Montageanleitungen Raypak RayTemp Hot Water Energy Management Control, Wartungsanleitungen, Kurzanleitungen oder Benutzeranleitungen Raypak RayTemp Hot Water Energy Management Control. Abhängig vom Bedarf, sollten Sie das Dokument finden, das Sie brauchen. In unserem Service können Sie sich die populärste Bedienungsanleitung des Produkts Raypak RayTemp Hot Water Energy Management Control ansehen.

Ähnliche Bedienungsanleitungen

Die komplette Bedienungsanleitung des Geräts Raypak RayTemp Hot Water Energy Management Control, wie sollte sie aussehen?
Die Bedienungsanleitung, auch bezeichnet als Benutzerhandbuch, oder einfach nur „Anleitung”, ist ein technisches Dokument, das dem Benutzer bei der Nutzung von Raypak RayTemp Hot Water Energy Management Control hilfreich sein soll. Die Bedienungsanleitungen werden in der Regel von technischen Schriftstellern geschrieben, aber in einer Sprache, die für alle Nutzer von Raypak RayTemp Hot Water Energy Management Control verständlich ist.

Eine gänzliche Bedienungsanleitung von Raypak sollte einige Grundelemente enthalten. Ein Teil von ihnen ist nicht so wichtig, wie z.B.: die Titelseite oder Autorenseiten. Die restlichen von ihnen jedoch, sollten Informationen liefern, die für den Nutzer von enormer Wichtigkeit sind.

1. Einführung und Hinweise, wie man sich in einer Bedienungsanleitung von Raypak RayTemp Hot Water Energy Management Control bewegt - Am Anfang jeder Bedienungsanleitung sollten wir Hinweise bezüglich der Nutzungsart eines bestimmten Ratgebers finden. In ihr sollten sich Informationen über die Lokalisierung des Inhaltsverzeichnisses von Raypak RayTemp Hot Water Energy Management Control befinden, FAQ oder über oft auftretende Probleme – also Stellen, die von den Benutzern in jeder Bedienungsanleitung am meisten gesucht werden
2. Inhaltsverzeichnis - Index aller Ratschläge bezüglich Raypak RayTemp Hot Water Energy Management Control, die wir im aktuellen Dokument finden
3. Ratschläge zur Nutzung der Grundfunktionen des Geräts Raypak RayTemp Hot Water Energy Management Control - die uns die ersten Schritte während der Nutzung von Raypak RayTemp Hot Water Energy Management Control erleichtern sollten
4. Troubleshooting - geordneter Tätigkeitslauf, der uns bei der Diagnose und als nächstes bei der Lösung wichtiger Probleme mit Raypak RayTemp Hot Water Energy Management Control hilft
5. FAQ - häufig gestellte Fragen
6. Kontaktdaten Informationen darüber, wo man Kontakt zum Produzenten / Service von Raypak RayTemp Hot Water Energy Management Control im bestimmten Land suchen kann, wenn es nicht gelingt, das Problem selbst zu lösen.

Haben Sie eine Frage bezüglich Raypak RayTemp Hot Water Energy Management Control?

Nutzen Sie das untere Formular

Wenn Sie mit Hilfe der gefundenen Bedienungsanleitung Ihr Problem mit Raypak RayTemp Hot Water Energy Management Control nicht gelöst haben, stellen Sie eine Frage, indem Sie das untere Formular nutzen. Wenn einer der Nutzer ein ähnliches Problem mit Raypak RayTemp Hot Water Energy Management Control hatte, ist es möglich, dass er mit Ihnen die Lösung teilen möchte.

Text vom Bild übertragen

Kommentare (0)