Casablanca Fan Company HM 101 - page 1
66401100 e xcellence in hot water Installation, Operating and Servicing Instructions HeatMaster HM 71 HM 101 ...
-
Casablanca Fan Company HM 101 - page 2
1 INTENDED USERS OF THESE INSTR UCTIONS These instructions are intended for - specifying engineers - installing engineers - end-users - servicing engineers SYMBOLS The follo wing symbols are used in these instructions: Essential instruction for operating the system correctly . Essential instruction for personal saf ety or en vironmental protection. ...
-
Casablanca Fan Company HM 101 - page 3
OPERA TING PRINCIPLE The HeatMaster is a high performance, direct fired hot water stor age heater , which has indirect heat transfer due to its T ank-in-T ank construction. At the hear t of the HeatMaster is a stainless steel cylinder through which the flue tubes pass. This is surrounded by a mild steel shell containing the primar y water (neutral ...
-
Casablanca Fan Company HM 101 - page 4
3 DESCRIPTION Flue reduction collar T op cover A utomatic air v ent Central heating flow pipe Flue pipes and turbulators Insulation Burner Detector NTC3 Heating return Combustion chamber Burner chamber plate Primar y circuit Primar y safety v alve Low water pressure s witch Detector NTC1 and NTC2 Casing front panel Primar y expansion v essel Domest ...
-
Casablanca Fan Company HM 101 - page 5
4 DIMENSIONS The units are delivered fully assemb led, tested and packed on a timber base with shoc kproof edges and protected by heat-shrunk plastic film. On delivery and after unpacking, check the equipment f or damage. F or transpor t pur poses, refer to the weights and dimensions giv en below . TECHNICAL SPECIFICA TION D G F E J H B A K C C/2 H ...
-
Casablanca Fan Company HM 101 - page 6
5 HEA TMASTER CONTROL SETTINGS Description The 71/101 series is fitted with an electronic controller (MCBA) which controls burner operation (ignition, safety and modulation), and provides f acilities to adapt the controller to the desired application. The MCBA has three lev els of settings : manuf acturer, installer and user . There are three tempe ...
-
Casablanca Fan Company HM 101 - page 7
6 BOILER ROOM Important •K eep vents free at all times . • Do not store inflammable products in the boiler room. • Do not store corrosive products near the boiler , such as paints, solvents , chlor ine, salt, soap and other cleaning products. • If you smell gas, do not s witch on the light or light a flame. T ur n off the mains gas tap at t ...
-
Casablanca Fan Company HM 101 - page 8
7 INST ALLA TION Balanced flue boiler connection type: C • C13: concentric hor izontal connection • C33: concentric vetical connection • C53: parallel chimney connection • C63: concentr ic vertical connection without ter minal (only in Germany and Luxembourg). C53 C13 C33 2 m min. 150 min. 120 Maximum length concentric : 6 metres Maximum le ...
-
Casablanca Fan Company HM 101 - page 9
8 INST ALLA TION HO T W A TER CONNECTIONS Pressure reducing valve If the mains water pressure is greater than 6 bar , a pressure reducing v alve must be fitted. Expansion relief valve The tank expansion relief v alve must be A CV approved and calibrated to a maximum of 7 bar . The valv e discharge must be connected to the drain. Hot water expansion ...
-
Casablanca Fan Company HM 101 - page 10
HEA TING CONNECTION The HeatMaster has two connections at the rear that can be used to connect a central heating circuit. Connecting a heating system may reduce the domestic hot water perf or mance. W ARNING The maximum pump motor load f or the MCBA is 250 W att. If a larger pump is required, install a relay between the pump and the MCBA. Expansion ...
-
Casablanca Fan Company HM 101 - page 11
10 ELECTRICAL CONNECTION Po wer supply The boiler operates with a 230 V - 50 Hz single phase supply . A double pole isolator with a 6 amp fuse or a 6 amp MCB must be fitted outside the boiler to allow pow er to be shut off during servicing and before an y repairs are carried out on the boiler. Conformity Boiler installation must comply with the pre ...
-
Casablanca Fan Company HM 101 - page 12
7 8 9 10 11 12 L1 N T1 T2 S3 B4 L1 N T1 T2 S3 B4 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 1 2 3 4 5 6 1 2 3 4 5 6 7 8 9 10 11 12 1 2 3 4 5 1 2 3 L1 N T1 T2 S3 B4 B5 T6 T7 T8 3 4 230V ~ 50 Hz 56 MM FF X1 X2 X3 X4 F M BG 2000-M/101 1 2 3 4 5 C 1 B5 T6 T7 T8 L1 N T1 T2 S3 B4 L1 N V1 V2 V1 V2 2 1 13 14 15 17 16 BG 2000-M 71/101 HEA TMASTER 71 ...
-
Casablanca Fan Company HM 101 - page 13
12 COMMISSIONING FILLING THE HO T W A TER AND HEA TING CIRCUITS IMPORT ANT The hot water tank must be pressurised bef ore the heating circuit is filled. 1. Close the primar y circuit filling valves (11). 2. Open the stop valve (1) and the dr awoff tap (8). When water flows out of the tap , the hot water tank is full and the draw off tap (8) should ...
-
Casablanca Fan Company HM 101 - page 14
13 BURNER FEA TURES 71/101 Gas burner features (*) propane Gas category T ype HM 71 HM 101 Input Kw 22.0 - 69.9 25.0 - 107 / 22.0 - 110 (*) Output Kw 18.4 - 63.0 23.0 - 96.3 / 20.2 - 99.0 (*) Combustion efficiency - natural gas % 92.0 92.1 Natural gas CO 2 % 9.0 9.5 Gas G20 - 20 mbar - I 2E(S)B - I 2 Er - I 2H Flow m 3 /h 2.12 - 7.40 2.64 - 11.32 G ...
-
Casablanca Fan Company HM 101 - page 15
14 DRAINING THE BOILER Wa ter flowing out of the drain cock ma y be e xtremely hot and could cause severe scalding. K eep people awa y from discharges of hot water . Draining the heating circuit 1. T urn OFF the on/off switch on the boiler control panel, isolate e xter nal electrical supply , and tur n off the gas supply to the boiler. 2. Close the ...
-
Casablanca Fan Company HM 101 - page 16
15 USING THE BOILER Y our system should be serviced at least once a year by a qualified engineer. If the boiler is subject to heavy use, it may require servicing more than once a year - consult your service engineer for advice. Starting the burner: In normal operation, the burner starts automatically whenever the boiler temperature falls below the ...
-
Casablanca Fan Company HM 101 - page 17
Changing the MCBA settings: Parameter mode Proceed as follo ws: • Press the “MODE” button once; the display will sho w “P ARA”. Press the “STEP” button once; the first digit is “1” and the last two show the setting f or the first parameter . • T o change these last two , press “+” to increase and “-” to decrease. • Sav ...
-
Casablanca Fan Company HM 101 - page 18
17 USER GUIDE codes 00 02 03-07 11 12 13-17 18 19 25 28 31 32 33 36 37 38 44 Error description No flame detected No ignition after 5 attempts Internal error Eprom error Low water pressure or 24V fuse f ailure Internal error Primar y temperature 1 > 110 °C Primar y temperature 2 > 110 °C Primar y temperature 1 gradient too high No fan signal ...
-
Casablanca Fan Company HM 101 - page 19
18 SERVICE RECORD Date installed: % CO 2 (min. load) : % CO 2 (max. load) : Gas LPG Model : Serial number : Heating system pressure setting : ❏ ❏ Name and signature : Flue gas T° : Efficiency : Gas pressure : INST ALLA TION DET AILS Date serviced : % CO 2 (min. load) : % CO 2 (max. load) : Gas LPG Remarks : ❏ ❏ Name and signature : Flue ga ...
-
Casablanca Fan Company HM 101 - page 20
INTERNA TIONAL A CV international n.v KERKPLEIN, 39 B-1601 RUISBR OEK - BELGIUM TEL.: +32 2 334 82 20 F AX: +32 2 378 16 49 E-MAIL: international.info@acv-world.com BELGIUM A CV BELGIUM n v/sa KERKPLEIN, 39 B-1601 RUISBR OEK-BELGIUM TEL.: +32 2 334 82 40 F AX: +32 2 334 82 59 E-MAIL: belgium.info@acv-world.com CHILE ALBIN TROTTER Y ACV L TDA SAN P ...
Haben Sie eine Frage bezüglich Casablanca Fan Company HM 101?
Nutzen Sie das untere Formular
Wenn Sie mit Hilfe der gefundenen Bedienungsanleitung Ihr Problem mit Casablanca Fan Company HM 101 nicht gelöst haben, stellen Sie eine Frage, indem Sie das untere Formular nutzen. Wenn einer der Nutzer ein ähnliches Problem mit Casablanca Fan Company HM 101 hatte, ist es möglich, dass er mit Ihnen die Lösung teilen möchte.