2 Johnson Controls T echnical Guide: YK145.00-EG4 (309) W ater Source Heat Pumps Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Product Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ...
-
York YK145.00-EG4 - page 3
Johnson Controls 3 W ater Source Heat Pumps T echnical Guide: YK145.00-EG4 (309) INTR ODUCTION Performance and dependability in a no-nonsense heat pump. The R-Series units by YORK are completely self-contained heat pumps. This equipment employs a water-to- refrigerant heat exchanger to extract (heating cycle) or reject (cooling cycle) heat from/to ...
-
York YK145.00-EG4 - page 4
4 Johnson Controls T echnical Guide: YK145.00-EG4 (309) W ater Source Heat Pumps SPECIFICA TIONS GENERAL All R-series models ½ - 6 ton ship as factory-charged packages, complete with R-410A refrigerant. Horizontal (RSH) units are designed for suspended ceiling mount- ing. RSH models are shipped with ‘straight-through’ evaporator fan discharge ...
-
York YK145.00-EG4 - page 5
Johnson Controls 5 W ater Source Heat Pumps T echnical Guide: YK145.00-EG4 (309) NOMENCLA TURE WA TER SOUR CE HEA T PUMP Product Category RS = Water-Cooled HP R-410A Product Indentifier V = Vertical Arrangement (Upflow) H = Horizontal Arrangment Miscellaneous Options A = None D = Condensate Overflow Switch Heating Options 0 = None Design Series t n ...
-
York YK145.00-EG4 - page 6
6 Johnson Controls T echnical Guide: YK145.00-EG4 (309) W ater Source Heat Pumps PHY SICAL D A T A Model Series 007 009 012 018 024 030 036 042 048 060 070 Nominal Cooling (T on) 1 0.5 0.75 1.0 1.5 2.0 2.5 3 3.5 4 5 6 Compressor-T ype Rotary Reciprocating Scroll Air Coil-T ype Enhanced Copper tubes, Enhanced Aluminum Fins Face Area(sq ft) 1.17 1.17 ...
-
York YK145.00-EG4 - page 7
Johnson Controls 7 W ater Source Heat Pumps T echnical Guide: YK145.00-EG4 (309) ARI/ISO PERFORMANCE D A T A PERFORMANCE D A T A - ARI/ISO 13256-1 WA TER LOOP CONDITIONS* Unit Model Flow Rate (USGPM) Air Flow (SCFM) Cooling Capacity (Btuh) EER Heating Capacity (Btuh) COP 007 1.8 260 6,800 12.5 8,700 4.5 009 2.4 320 8,900 12.4 1 1,600 4.4 012 3.0 40 ...
-
York YK145.00-EG4 - page 8
8 Johnson Controls T echnical Guide: YK145.00-EG4 (309) W ater Source Heat Pumps PERFORMANCE D A T A RS*007 — 320 CFM EWT (F) GPM WPD COOLING HEA TING PSI FT TC SC kW HR EER HTG kW HE LA T (F) COP 20 1.8 4.8 1 1.0 4.1 0.44 2.6 80 2.7 30 1.0 2.1 4.9 8.5 6.0 0.30 9.5 28.0 5.0 0.45 3.5 82 3.3 1.4 2.8 6.4 8.7 6.1 0.28 9.7 30.8 5.3 0.47 3.7 83 3.3 1.8 ...
-
York YK145.00-EG4 - page 9
Johnson Controls 9 W ater Source Heat Pumps T echnical Guide: YK145.00-EG4 (309) PERFORMANCE D A T A RS*009 — 320 CFM EWT (F) GPM WPD COOLING HEA TING PSI FT TC SC kW HR EER HTG kW HE LA T (F) COP 20 2.4 7.0 16.1 5.6 0.57 3.7 84 2.9 30 1.2 2.6 6.0 12.8 9.0 0.47 14.4 27.4 6.1 0.74 3.6 86 2.4 1.8 4.1 9.6 13.1 9.1 0.43 14.6 30.6 6.6 0.72 4.2 87 2.7 ...
-
York YK145.00-EG4 - page 10
10 Johnson Controls T echnical Guide: YK145.00-EG4 (309) W ater Source Heat Pumps PERFORMANCE D A T A RS*012 — 400 CFM EWT (F) GPM WPD COOLING HEA TING PSI FT TC SC kW HR EER HTG kW HE LA T (F) COP 20 3.0 3.9 9.0 8.2 0.86 5.3 87 2.8 30 1.5 2.0 4.5 16.9 1 1.8 0.53 18.7 32.0 9.0 0.91 5.9 89 2.9 2.3 2.6 6.1 17.1 1 1.9 0.49 18.8 34.7 9.5 0.93 6.3 90 ...
-
York YK145.00-EG4 - page 11
Johnson Controls 11 W ater Source Heat Pumps T echnical Guide: YK145.00-EG4 (309) PERFORMANCE D A T A RS*018 — 640 CFM EWT (F) GPM WPD COOLING HEA TING PSI FT TC SC kW HR EER HTG kW HE LA T (F) COP 20 4.8 8.4 19.4 10.4 1.09 6.7 83 2.8 30 2.4 3.1 7.1 26.6 18.6 0.96 29.9 27.7 12.0 1.17 8.0 85 3.0 3.6 4.9 1 1.3 27.3 19.1 0.90 30.4 30.2 12.4 1.21 8.3 ...
-
York YK145.00-EG4 - page 12
12 Johnson Controls T echnical Guide: YK145.00-EG4 (309) W ater Source Heat Pumps PERFORMANCE D A T A RS*024 — 800 CFM EWT (F) GPM WPD COOLING HEA TING PSI FT TC SC kW HR EER HTG kW HE LA T (F) COP 20 6.0 9.7 22.4 13.3 1.50 8.2 83 2.6 30 3.0 3.4 7.9 35.1 24.6 1.07 38.8 32.7 15.9 1.50 10.8 86 3.1 4.5 5.2 12.0 35.9 25.0 1.01 39.4 35.4 16.4 1.50 1 1 ...
-
York YK145.00-EG4 - page 13
Johnson Controls 13 W ater Source Heat Pumps T echnical Guide: YK145.00-EG4 (309) PERFORMANCE D A T A RS*030 — 1000 CFM EWT (F) GPM WPD COOLING HEA TING PSI FT TC SC kW HR EER HTG kW HE LA T (F) COP 20 7.8 7.8 18.0 17.5 1.97 10.8 84 2.6 30 3.9 4.2 9.8 38.6 27.0 1.43 43.5 26.9 19.2 1.88 12.8 86 3.0 5.8 5.4 12.4 39.5 27.5 1.41 44.3 28.0 20.3 1.92 1 ...
-
York YK145.00-EG4 - page 14
14 Johnson Controls T echnical Guide: YK145.00-EG4 (309) W ater Source Heat Pumps PERFORMANCE D A T A RS*036 — 1200 CFM EWT (F) GPM WPD COOLING HEA TING PSI FT TC SC kW HR EER HTG kW HE LA T (F) COP 20 9.0 10.1 23.3 19.9 1.94 2.0 83 3.0 30 4.5 3.4 7.9 45.6 31.9 1.27 49.9 35.9 23.2 2.06 16.2 86 3.3 6.8 6.3 14.6 47.5 33.1 1.26 51.8 37.8 24.0 2.13 1 ...
-
York YK145.00-EG4 - page 15
Johnson Controls 15 W ater Source Heat Pumps T echnical Guide: YK145.00-EG4 (309) PERFORMANCE D A T A RS*042 — 1400 CFM EWT (F) GPM WPD COOLING HEA TING PSI FT TC SC kW HR EER HTG kW HE LA T (F) COP 20 10.4 12.3 28.4 26.7 3.32 15.4 86 2.5 30 5.2 4.1 9.4 48.6 34.0 1.97 55.3 24.7 31.2 3.30 19.9 89 2.8 7.8 6.7 15.4 49.1 34.2 1.86 55.4 26.4 31.9 3.31 ...
-
York YK145.00-EG4 - page 16
16 Johnson Controls T echnical Guide: YK145.00-EG4 (309) W ater Source Heat Pumps PERFORMANCE D A T A RS*048 — 1600 CFM EWT (F) GPM WPD COOLING HEA TING PSI FT TC SC kW HR EER HTG kW HE LA T (F) COP 20 12.0 15.1 34.9 30.5 3.32 19.1 86 2.8 30 6.0 4.4 10.1 61.3 42.9 2.33 69.3 26.3 33.4 3.30 3.3 88 3.0 9.0 8.5 19.5 62.2 43.4 2.29 70.0 27.2 35.6 3.32 ...
-
York YK145.00-EG4 - page 17
Johnson Controls 17 W ater Source Heat Pumps T echnical Guide: YK145.00-EG4 (309) PERFORMANCE D A T A RS*060 — 2000 CFM EWT (F) GPM WPD COOLING HEA TING PSI FT TC SC kW HR EER HTG kW HE LA T (F) COP 20 15.0 17.8 41.1 38.2 3.32 26.8 86 2.9 30 7.5 5.9 13.5 72.6 50.8 2.77 82.1 26.2 43.2 3.90 29.9 88 3.2 1 1.2 7.5 17.3 73.8 51.4 2.60 82.7 28.4 45.2 3 ...
-
York YK145.00-EG4 - page 18
18 Johnson Controls T echnical Guide: YK145.00-EG4 (309) W ater Source Heat Pumps PERFORMANCE D A T A RS*070 — 2200 CFM EWT (F) GPM WPD COOLING HEA TING PSI FT TC SC kW HR EER HTG kW HE LA T (F) COP 20 17.5 20.8 48.0 42.1 3.32 30.7 86 2.6 30 8.8 8.3 19.1 82.7 57.9 3.22 93.7 25.7 47.9 4.86 31.3 88 2.9 13.1 12.5 28.9 83.4 58.1 3.14 94.1 26.6 49.4 4 ...
-
York YK145.00-EG4 - page 19
Johnson Controls 19 W ater Source Heat Pumps T echnical Guide: YK145.00-EG4 (309) CORRECTION F ACT ORS ANTIFREEZE CORRECTION T ABLE Antifreeze Concentration 5% 10% 15% 20% 25% 30% 40% Ethylene Glycol Cooling 0.998 0.995 0.993 0.991 0.989 0.987 0.984 Heating 0.995 0.990 0.985 0.980 0.974 0.969 0.964 PD 1.040 1.055 1.080 1.105 1.135 1.165 1.210 Propy ...
-
York YK145.00-EG4 - page 20
20 Johnson Controls T echnical Guide: YK145.00-EG4 (309) W ater Source Heat Pumps BL O WER PERFORMANCE BLO WER PERFORMANCE Unit Size Rated CFM Min. CFM Max. CFM Motor Speed External Static Pressure (in w .g.) 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 007 260 182 299 High - - - - - - - - - Med - - 300 270 235 200 - - - Low 275 260 240 210 180 - - - - 009 32 ...
-
York YK145.00-EG4 - page 21
Johnson Controls 21 W ater Source Heat Pumps T echnical Guide: YK145.00-EG4 (309) ELECTRICAL D A T A RSH/RSV ELECTRICAL D A T A Unit Size SUPPL Y VOL T AGE COMPRESSOR BLOWER MIN. CCT . AMP ACITY MAX FUSE / CCT . BKR. AMP QTY RLA LRA HP FLA 007 208-230/1/60 1 @ 3.4 22.0 0.10 0.8 5.05 15 009 208-230/1/60 1 @ 4.6 28.0 0.10 0.8 6.55 15 012 208-230/1/60 ...
-
York YK145.00-EG4 - page 22
22 Johnson Controls T echnical Guide: YK145.00-EG4 (309) W ater Source Heat Pumps D A B E C G 1.50" J 2.00" K L 1.63" M 3/4 FPT DRAIN W A TER IN W A TER OUT SUPPL Y AIR AIR RETURN 0.75" TYP 0.75" Ø0.875" 1 2 3 3 - BLOWER SERVICE DOOR 2 - COMPRESSOR AND C ONDENSER 1 - ELECTRICAL BOX SERVICE DOOR SERVICE DOORS SERVICE D ...
-
York YK145.00-EG4 - page 23
Johnson Controls 23 W ater Source Heat Pumps T echnical Guide: YK145.00-EG4 (309) A C K L 2 1" G D G F E G D G F E SERVICE DOORS 1 - ELECTRICAL BOX SERVICE DOOR 2 - COMPRESSOR AND C ONDENSER SERVICE DOOR 3 - BL OWER SER VICE DOOR B 2" AIR SUPPL Y RETURN AIR 1 3 W A TER IN W A TER OUT DRAIN 3/4Ø POWER CONNECTION LOW VOL T AGE CONNECTION B ...
-
York YK145.00-EG4 - page 24
24 Johnson Controls T echnical Guide: YK145.00-EG4 (309) W ater Source Heat Pumps WIRING DIA GRAM SINGLE PHASE RS* UNITS: 208-230V/1Ph/60Hz 265V/1PH/60Hz ...
-
York YK145.00-EG4 - page 25
Johnson Controls 25 W ater Source Heat Pumps T echnical Guide: YK145.00-EG4 (309) WIRING DIA GRAM 3 PHASE RS* UNITS: 208-230V/3Ph/60Hz 460V/3Ph/60Hz 575V/3Ph/60Hz ...
-
York YK145.00-EG4 - page 26
26 Johnson Controls T echnical Guide: YK145.00-EG4 (309) W ater Source Heat Pumps NO TES ...
-
York YK145.00-EG4 - page 27
Johnson Controls 27 W ater Source Heat Pumps T echnical Guide: YK145.00-EG4 (309) NO TES ...
-
York YK145.00-EG4 - page 28
Printed on recycled paper T echnical Guide: YK145.00-EG4 (309) Supersedes: Nothing © 2008 Johnson Controls, Inc. P .O. Box 423, Milwaukee, WI 53201 Printed in USA www .johnsoncontrols.com ...
Haben Sie eine Frage bezüglich York YK145.00-EG4?
Nutzen Sie das untere Formular
Wenn Sie mit Hilfe der gefundenen Bedienungsanleitung Ihr Problem mit York YK145.00-EG4 nicht gelöst haben, stellen Sie eine Frage, indem Sie das untere Formular nutzen. Wenn einer der Nutzer ein ähnliches Problem mit York YK145.00-EG4 hatte, ist es möglich, dass er mit Ihnen die Lösung teilen möchte.