    INST ALLA TION, OPERA TION & MAINTENANCE MANUAL SINGLE PACKAGED ROOF TOP AIR CONDITIONERS 'PT' SERIES MODELS: PT036 - PT360 Part Number: 800-213-03 ...

  • Cooline PT036 - page 2

    Contents Page General Model decoding ................................................................................................................. ..................................... 2 General statement .............................................................................................................. .............................. ...

  • Cooline PT036 - page 3

    C : 1.5 HP ODP D : 2 HP ODP D : 2 HP ODP E : 3 HP ODP F : 3 HP TEFC G : 5 HP ODP H : 5 HP TEFC J : 7.5 HP ODP K : 7.5 HP TEFC J : 7.5 HP ODP K : 7.5 HP TEFC L : 10 HP ODP M : 10 HP TEFC L : 10 HP ODP M : 10 HP TEFC N : 15 HP ODP P : 15 HP TEFC MODELS: PT075 - PT360 (BEL T DRIVEN MOTOR) 1& 2 BASIC 3, 4 & 5 NOMINAL COOLING CAP ACITY (MBH) 8 B ...

  • Cooline PT036 - page 4

    GENERAL GENERAL ST A TEMENT This unit is from the PT series that was designed & built for the optimum performance. However, it is required that you become well acquainted with good practices for the proper installation/operation/and maintenance procedures in order to ensure a safe trouble free operation, year after year. Please read through the ...

  • Cooline PT036 - page 5

    GENERAL These units are shipped completely assembled, charged, and wired. They do not require any field installation of refrigerant tubing. Units require external power, thermostat wiring, condensate drain piping and ducting as applicable. Size of unit for an installation should be based on a heat gain calculation made according to applicable stand ...

  • Cooline PT036 - page 6

    B C A E D B C D A A TTENTION TO RIGGERS • Insert 2" nominal pipe through holes in the base rail as shown in the figure below for slings. • Holes in base rail are centered around the unit center of gravity. • Use wooden pallet or spreader bar when rigging, to prevent the slings from damaging the unit. • Rollers may be used to move the u ...

  • Cooline PT036 - page 7

    CONDENSA TE DRAIN CONNECTION • Use standard PVC pipe with NPT connection for the condensate drain. Provide a 'P' trap immediately at the condensate drain connection. • Piping has to be sloped away from the unit. • Remember to remove the drain hole plug before operating the unit. Avoid bends & elbows. DUCT CONNECTION The units ca ...

  • Cooline PT036 - page 8

    UNIT DIMENSIONS PT036 - PT075 ABCD E F G H J K L M PT036 - PT060 1460(57.48) 1025(40.35) 1430(56.3) 700(27.56) 163(6.42) 373(14.68) 250(9.84) 500(19.69) 57(2.24) 304(11.96) 343(13.49) 340(13.39) PT075 1775(69.88) 1150(45.28) 1745(68.7) 800(31.5) 175(6.89) 480(18.9) 325(12.8) 672(26.46) 80(3.15) 280(11.02) 275(10.83) 600(23.62) MODEL DIMENSIONS NOTE ...

  • Cooline PT036 - page 9

    UNIT DIMENSIONS PT090 - PT120 NOTE: 1. All dimensions are in mm (dimensions in brackets are in inches). 2. Service clearance should be 1200mm (4 feet) on all sides. 8 SIDE VIEW SIDE VI E W FRONT VIEW TOP VIEW ...

  • Cooline PT036 - page 10

    UNIT DIMENSIONS PT180 NOTE: 1. All dimensions are in mm (dimensions in brackets are in inches). 2. Service clearance should be 1200mm (4 feet) on all sides. 9 SIDE VIEW SIDE VIEW FR ONT VIEW TOP VIEW ...

  • Cooline PT036 - page 11

    UNIT DIMENSIONS PT215 - PT240 NOTE: 1. All dimensions are in mm (dimensions in brackets are in inches). 2. Service clearance should be 1200mm (4 feet) on all sides. 10 SIDE VIEW SIDE VIEW FRONT VIEW TOP VIEW ...

  • Cooline PT036 - page 12

    UNIT DIMENSIONS PT300 - PT360 NOTE: 1. All dimensions are in mm (dimensions in brackets are in inches). 2. Service clearance should be 1200mm (4 feet) on all sides. 11 SIDE V IEW SIDE VIEW FRONT VI EW TOP VIEW ...

  • Cooline PT036 - page 13

    POWER SUPPL Y 380/415-3-50 (4 wire) OPERA TION INSTRUCTIONS ST ART -UP INSPECTION & CHECK LIST After the installation is completed in all respect, the following points should be covered before the system is switched on for operation. 1. Check unit location as per installation instructions. 2. Make sure all electrical fasteners/connections are t ...

  • Cooline PT036 - page 14

    MIN. MAX. FLA RLA LRA HP FLA kW FLA – – 15.2 20 5/6 7.6/9.1 16.4/18.3 20/20 380/415-3-50 342 457 2.3 5.9 42 0.75 5.5 7.5/10* 11.4/15.2 21.1/25.9 25/30 12* 18.2 29.6 30 – – 20.8 30 5/6 7.6/9.1 20.8/20.8 30/30 380/415-3-50 342 457 2.3 10.4 55 0.75 5.5 7.5/10* 11.4/15.2 21.1/25.9 35/30 12* 18.2 29.6 30 – – 22.1 30 5/6 7.6/9.1 22.1/22.1 30/ ...

  • Cooline PT036 - page 15

    ELECTRICAL DA T A 342 457 1.9 – – 51 60 7.5/10 11.4/15.2 51/51 60/60 10 * /12 * 15.2/18.2 51/51 60/60 15 * /20 * 22.8/30.4 51/51 60/60 25 * /30 * 38/45.6 59/68.5 60/70 – – 54.8 70 7.5/10 11.4/15.2 54.8/54.8 70/70 10 * /12 * 15.2/18.2 54.8/54.8 70/70 15 * /20 * 22.8/30.4 54.8/54.8 70/70 25 * /30 * 38/45.6 63.8/73.3 70/80 MOCP MCA ELECTRIC HE ...

  • Cooline PT036 - page 16

    Performex-1 TM CONTROLLER : OPERA TION & FUNCTIONS The COOLINE Packaged units are provided with technologically advanced new Performex TM Controller Microprocessor Based Electronic Control Board, incorporating the following benefits and features: - COMPLETE UNIT CONTROL: Provides complete unit control for heating and cooling application whether ...

  • Cooline PT036 - page 17

    7. LEAD/LAG OPERA TION: Whenever a compressor needs to be on, the controller will turn on the compressor with the shorter accumulated run time provided its 3 minutes minimum off time has lapsed. Otherwise the other compressor will on first. Similarly, the compressor with the longer accumulated run time will be the first one to be cut off. This is t ...

  • Cooline PT036 - page 18

    MAINTENANCE INSTRUCTIONS AIRFLOW ADJUSTMENT (Applicable for PT075 - PT360 only) The airflow could be adjusted by adjusting pulleys of blower motor or belt tension with proper mounting and alignment of the pulleys: • Refer to fan performance tables in the catalog for selecting applicable airflow, RPM and brake horse power at specified static press ...

  • Cooline PT036 - page 19

    FORCE SCALE SPAN SCALE RING "0" LARGE "0" RING SMALL BELT SP A N DEFLE CT ION = 64 BELT SP AN B G - GR OUND FIELD WIRI NG N - NEUT RAL TERMIN AL BLOCK L3 - LIN E3 L2 - LIN E2 LI - LIN E 1 LEGE ND CONTROL WI RES-INTERC ONNECTING A B +5V A +5V GND FUSED DIS CONNECT SW ITCH OR CIRCUIT BREAKER L1 G L3 N L2 PACKAGED UNIT CONTROL P AN ...

  • Cooline PT036 - page 20

    PREVENTIVE MAINTENANCE SCHEDULE 12 X X X X X X X X X X X X X FREQUENCY OF MAINTENANCE, MONTHS (FIRST 4 YEARS) I T E M CAUTION: Disconnect power supply and allow all rotating parts to stop before servicing the unit. 6 X X Clean air filter (Aluminum)* Pressure wash condenser & cooling coil as required Check blower belt, tension, wear tear/replace ...

  • Cooline PT036 - page 21

    1. Check the power. Switch ON the circuit breaker. Replace fuse if it blown. 2. Check wiring against diagram. 3. Check and correct it. 4. Replace it. 1. Replace battery 1. Correct belt. Check tension and alignment. 2. Check wiring against diagram. 3. Check and correct it. 4. Replace if. 5. Replace it. 1. Check the rotation of blower, interchange ph ...

  • Cooline PT036 - page 22

    TROUBLE SHOOTING CHART SYMPTOM CAUSES CHECK & CORRECTIVE MEASURE 1. Low suction pressure 2. High discharge pressure 3. Less air quantity 4. Cooling coil ices up 5. Second stage (If exists) not working 6. Serving large area 1. Low ambient condition 2. Safety low pressure switch open due to low suction pressure 3. Fan cycling (whenever applicable ...

  • Cooline PT036 - page 23

    JUMPE R SETTIN G ON ECB DIP SWITCH SETTI NGS HEAT ER DAT A T ABLE (SEE HEATER DAT A TABLE) HEATER CONNECTION DETAILS TYPICAL SCHEMA TIC WIRING DIAGRAM MODELS : PT036 - PT075 (Single compressor units) NOTE: 1. Refer to next page for legend, notes & wiring diagram for optional items. 2. Refer to unit control box (inside panel) for exact wiring di ...

  • Cooline PT036 - page 24

    2. SMOKE DETECTOR OPTION CRANKCASE HE ATER CONNECTION 4. HP S CONNECTION OPTION STANDARD OPTIO NS 1. UVM OPTION 3. VOLT FREE CONTAC T OPTIO NS A. UNIT O N & OFF INDICATI ON OPTION C. BM ON ,OFF & TRIP IND ICATIO N OPTIO N PRESSURE SWITCH S ETTINGS TO HV TB TO NTB * TO HV TB * TO NT B FACTORY INSTALLED B.M SPEED * * * TYPICAL SCHEMA TIC WIRI ...

  • Cooline PT036 - page 25

    TYPICAL SCHEMA TIC WIRING DIAGRAM NOTE: 1. Refer to next page for legend, notes & wiring diagram for optional items. 2. Refer to unit control box (inside panel) for exact wiring diagram. MODELS : PT090 - PT120 (Dual compressor units) 24 ...

  • Cooline PT036 - page 26

    HPS OPTION FAN MOTO R CONTRO L CONNECTION (APPLIC ABLE FOR FM W ITH T.O.P) N TO NTB L2 TO HVTB BM WITH EXTERN AL OLR CONNECTION APPLI CA BLE FOR 1PH F M ONLY CRANKCASE HE ATER CONNE CTION A. UNIT ON & OFF INDICATION OPTI ON 3. VOLT FREE CON TACT OPTIONS 1. U VM OP TIO N 2. SMOKE DETECTO R OPTION STANDARD OPT IONS C. BM ON,OFF & TRIP INDICAT ...

  • Cooline PT036 - page 27

    HEATER DATA T AB LE CONNECTION FOR MANU EROP COM P. WITH SSPS CONNECTIO N FOR COMPRESSOR WITH MOTOR O VERLOAD 230V (SEE HEATER DATA TABLE) HEATER CONNECTION DETAILS CONNECTION FOR SCROLL COMP. W ITH SSPS TO HVT B TYPICAL SCHEMA TIC WIRING DIAGRAM NOTE: 1. Refer to next page for legend, notes & wiring diagram for optional items. 2. Refer to unit ...

  • Cooline PT036 - page 28

    TYPICAL SCHEMA TIC WIRING DIAGRAM MODELS : PT180 - PT240 (Dual compressor units) LEGEND AR AUXILIARY RELAY AFS AIRFLOW SWITCH AT B AUXILIARY TERMINAL BLOCK BM BLOWER MOTOR BMC BLOWER MOTOR CONTACTOR CC COMPRESSOR CONTACTOR CCA AUXILIARY CONTACT CB CIRCUIT BREAKER C. HTR CRANKCASE HEATER COMP COMPRESSOR ECB ELECTRONIC CONTROL BOARD FCS FAN CYCLING S ...

  • Cooline PT036 - page 29

    TYPICAL SCHEMA TIC WIRING DIAGRAM MODELS : PT300 - PT360 (Dual compressor units) NOTE: 1. Refer to next page for legend, notes & wiring diagram for optional items. 2. Refer to unit control box (inside panel) for exact wiring diagram. 28 ...

  • Cooline PT036 - page 30

    TYPICAL SCHEMA TIC WIRING DIAGRAM MODELS : PT300 - PT360 (Dual compressor units) LEGEND AR AUXILIARY RELAY AFS AIRFLOW SWITCH AT B AUXILIARY TERMINAL BLOCK BM BLOWER MOTOR BMC BLOWER MOTOR CONTACTOR CC COMPRESSOR CONTACTOR CCA AUXILIARY CONTACT CB CIRCUIT BREAKER C. HTR CRANKCASE HEATER COMP COMPRESSOR ECB ELECTRONIC CONTROL BOARD FCS FAN CYCLING S ...

  • Cooline PT036 - page 31

    MODEL NUMBER PT036L PT048L PT060L PT075L PT090 PT100L PT120L PT180L PT215L COMPRESSOR 800-684-08 800-672-52 800-643-01 800-674-78 800-684-09 800-672-52 800-674-25 800-674-67/81 800-674-38 FAN MOTOR 800-555-26 800-555-26 800-555-26 800-555-26 800-545-68 800-545-68 800-545-68 800-545-68 800-545-68 FAN MOTOR CAPACITOR 800-353-15 800-353-15 800-353-15 ...

Produzent Cooline Kategorie Air Conditioner

Dokumente, die wir vom Produzenten des Geräts Cooline PT036 erhalten, können wir in mehrere Gruppen teilen. Unteranderem in:
- technische Zeichnungen Cooline
- Bedienungsanleitungen PT036
- Produktkarten Cooline
- Informationsbroschüren
- oder Energieetiketten Cooline PT036
Jede von ihnen ist wichtig, jedoch finden wir die wichtigsten Informationen für den Nutzer des Geräts in der Bedienungsanleitung Cooline PT036.

Die Dokumentengruppe, die als Bedienungsanleitungen bezeichnet wird, wird ebenfalls in detaillierte Arten geteilt, solche wie: Montageanleitungen Cooline PT036, Wartungsanleitungen, Kurzanleitungen oder Benutzeranleitungen Cooline PT036. Abhängig vom Bedarf, sollten Sie das Dokument finden, das Sie brauchen. In unserem Service können Sie sich die populärste Bedienungsanleitung des Produkts Cooline PT036 ansehen.

Ähnliche Bedienungsanleitungen

Die komplette Bedienungsanleitung des Geräts Cooline PT036, wie sollte sie aussehen?
Die Bedienungsanleitung, auch bezeichnet als Benutzerhandbuch, oder einfach nur „Anleitung”, ist ein technisches Dokument, das dem Benutzer bei der Nutzung von Cooline PT036 hilfreich sein soll. Die Bedienungsanleitungen werden in der Regel von technischen Schriftstellern geschrieben, aber in einer Sprache, die für alle Nutzer von Cooline PT036 verständlich ist.

Eine gänzliche Bedienungsanleitung von Cooline sollte einige Grundelemente enthalten. Ein Teil von ihnen ist nicht so wichtig, wie z.B.: die Titelseite oder Autorenseiten. Die restlichen von ihnen jedoch, sollten Informationen liefern, die für den Nutzer von enormer Wichtigkeit sind.

1. Einführung und Hinweise, wie man sich in einer Bedienungsanleitung von Cooline PT036 bewegt - Am Anfang jeder Bedienungsanleitung sollten wir Hinweise bezüglich der Nutzungsart eines bestimmten Ratgebers finden. In ihr sollten sich Informationen über die Lokalisierung des Inhaltsverzeichnisses von Cooline PT036 befinden, FAQ oder über oft auftretende Probleme – also Stellen, die von den Benutzern in jeder Bedienungsanleitung am meisten gesucht werden
2. Inhaltsverzeichnis - Index aller Ratschläge bezüglich Cooline PT036, die wir im aktuellen Dokument finden
3. Ratschläge zur Nutzung der Grundfunktionen des Geräts Cooline PT036 - die uns die ersten Schritte während der Nutzung von Cooline PT036 erleichtern sollten
4. Troubleshooting - geordneter Tätigkeitslauf, der uns bei der Diagnose und als nächstes bei der Lösung wichtiger Probleme mit Cooline PT036 hilft
5. FAQ - häufig gestellte Fragen
6. Kontaktdaten Informationen darüber, wo man Kontakt zum Produzenten / Service von Cooline PT036 im bestimmten Land suchen kann, wenn es nicht gelingt, das Problem selbst zu lösen.

Haben Sie eine Frage bezüglich Cooline PT036?

Nutzen Sie das untere Formular

Wenn Sie mit Hilfe der gefundenen Bedienungsanleitung Ihr Problem mit Cooline PT036 nicht gelöst haben, stellen Sie eine Frage, indem Sie das untere Formular nutzen. Wenn einer der Nutzer ein ähnliches Problem mit Cooline PT036 hatte, ist es möglich, dass er mit Ihnen die Lösung teilen möchte.

Text vom Bild übertragen

Kommentare (0)