H EA T P UM P INSTALLATION INSTRUCTION S HEAT PUMP SAFETY INSTALLATION RE QUIREMENTS These inst ructions are intend ed as a general guide only for use by qualified persons and do not su persede any na tional or local codes in any way . The i nstallation mu st comply wit h all st ate and local codes as well as the National Elect rical Code ■ The h ...
-
Whirlpool W4GH6 - page 2
2 To o l s a n d P a r t s Gat her the r equ ir ed to ols and pa rts bef or e star tin g instal lati on. Read and fol low the instruction s provided with an y tools listed here. T ools Needed Parts Needed Check local cod es and HV AC supplier . Check exist ing electrical supply , and read “Electrica l Requirements, ” “Location Requirements,? ...
-
Whirlpool W4GH6 - page 3
3 Minimum Clearances Line Set Isolation The follow ing illustrati ons demonstrate procedures which ensure proper refrigerant line set i solation. Installing Horizontal Runs This sh ows how to instal l line se ts on horizon tal runs . NOTE : T o hang line set from joist or raft er , use either metal strappin g material or anchored heavy nylo n wire ...
-
Whirlpool W4GH6 - page 4
4 Ele ct rica l R equir em ents NOTE : All outdoor wiri ng must be suitable for outdoor u se. Use copper conductors only . ■ All field w iring must be don e in accordance with National Electrical Code requirements, ap plicable requirements of UL, or local codes, where applicable. ■ Electrical wiring, disconnect means and over -current pr otec t ...
-
Whirlpool W4GH6 - page 5
5 1. Discon nect powe r . 2. Remove the refriger ant from the existing system per the manufacturer’ s in structions provided with the recovery system bei ng used. Connect t he R-22 gauge set is connecte d to both side s of the refrigerant sys tem (as shown), and verify that the enti r e syste m is void of refrigerant in accordance with the manu f ...
-
Whirlpool W4GH6 - page 6
6 17. Inst all the val ve cores. 18. Install the R-410A thermal exp ansion valv e specified for t his system in the indoor coil. NOTE : R-410A s ystems use only thermal ex pansion valv es. 19. Pressurize the line s and indoor coil with a pressure not to exceed 20 ps ig. 20. Leak test the li nes with a pr essure no t to exceed 20 psig. 21. Ope n the ...
-
Whirlpool W4GH6 - page 7
7 6. Tighten to 20 to 3 0 ft lbs. Use backup wrench on all wr ench flats. NOTE : Overti ghtening may c rush the T eflon ® seal and c ause a leak. 7. Connect the ext ernal equal izer line to the equa lizer port on the suct ion line. 8. Tighten to 8 ft lbs. 9. Attach the superhe at sensing b ulb to the s uction hea der with the strap pr ovided with ...
-
Whirlpool W4GH6 - page 8
8 Normal Op erating Pressures NOTE : V alues p r ovided in ch art are typical pressures. Indoor un it matchup, ind oor air quality and indoor load will cause pressures to vary . T emperature o f the Ai r Entering the Outd oor Coil Model -24 -3 6 -48 -6 0 Liquid Suct ion Liquid Sucti on Liquid S uction Liquid S uction Cool ing—1 st Sta ge (L ow Ca ...
-
Whirlpool W4GH6 - page 9
9 Suction Line Sizes Installa tions exceed ing 100 ft are not recommended. Liquid Line Si zes Installa tions exceed ing 100 ft are not recommended . Make Elect rica l Connectio ns IMPORTANT: ■ Electrical wiring, disconnect means and over -current pr otec tio n ar e to be su ppli ed by the i nst aller . Ref er to the rating plate for the maxi mum ...
-
Whirlpool W4GH6 - page 10
10 4. Connect grou nd wire to groun d lug. 5. Connect lo w voltage circuit. T yp ical Wiring Connection (low voltag e circuit) 6. Replace control box c over . 7. Reconnect pow er . A. Ground lug B. Field supply ground w ire C. 208/230 volt field supply wires T1 T2 L1 L2 L1 L2 C A B A. Do not connect C (common) connection between indoor unit and the ...
-
Whirlpool W4GH6 - page 11
11 Outdoor Unit T ypical Wiring Diagram Complete Installat ion 1. Operate the heat pu mp for a period of at leas t 15 minutes to allow for pressures and te mperatures to stabil ize. 2. If heat pump doe s not appear to be fu nctioning correctly , have heat pu mp checked by a person cert ified by the EP A to handle refrig erant. FC H R S C H C F C Eq ...
-
Whirlpool W4GH6 - page 12
12 SEQUENCE OF OPERATION Cooling C ycle Upon cooling demand, the the rmostat closes circuit R to O an d Y . Closing R to O and Y ener gizes the reversing valve for cooling operation and closes the heat pump cont actor , starting the compressor and outdoor fan. The th ermostat automaticall y closes R to G circuit, w hich also brings on the indoor fa ...
-
Whirlpool W4GH6 - page 13
13 Time Delay The time d elay is 5 minut es long. The delay helps to p rote ct the compressor from short cycling in case the power to t he heat pump is int errupted or a pressure switch opens. The d elay is bypassed by placing the t imer select jumper across th e TEST pins f or 0.5 se conds. Pre s su re S wi tc h C irc u it The def ros t con tr ol ...
-
Whirlpool W4GH6 - page 14
14 2. Remove the heat er compartment acc ess panel. 3. Adjust the time period between defrost cycle s by placing t he defrost time plu g in t he proper positio n. See “ Defrost Control Board.” ■ For 30-minute intervals betw een defrost cycles, connect the Defrost Time Settin g Plug to the pins corr esponding to 30. ■ For 60-minute intervals ...
-
Whirlpool W4GH6 - page 15
15 TROUBLESHOOTING Heat Pump Fails to Operate Properly Review “Sequ ence of Operatio n” and visuall y inspect th e heat pump befor e troubleshooting: System Diagnostic Module W4GH6 heat pumps c ontain a diagno stic module for troubleshootin g heat pump system fail ures. By monitoring and analyzi ng data from the compressor and thermostat deman ...
-
Whirlpool W4GH6 - page 16
16 24 V AC Power Wiring The di agnost ic module r equires a const ant nomin al 24 V AC power supply . The wiring to the module’ s R and C terminals must be directly from the indoor unit or thermost at. The module cannot be pow er ed by R an d C te rminals o n the defr ost b oar d wi thout experienci ng nuisance ale rts. Thermostat Demand Wiring T ...
-
Whirlpool W4GH6 - page 17
17 Incorrectly Wired Module Codes Depending on the s ystem configuration, some Alert flash codes may not be act ive. The presence of safet y switches affects how the syst em alerts are display ed by the module. Incorrectly wiri ng the diagnostic modu le will cause false LED codes. The Incorr ectly W ired Module T roubleshooting cha rt describ es L ...
-
Whirlpool W4GH6 - page 18
18 ...
-
Whirlpool W4GH6 - page 19
19 Keep this book an d your sales s lip together for futur e ref erence. Y ou must pr ovide pro of of pur chase o r installation date for in-warranty service. Wr ite d own the f ollow ing in format ion ab out y our Spl it Syst em Heat Pump—Outd oor Section to better help you obtain assistanc e or service if you ever nee d it. Dealer nam e _______ ...
-
Whirlpool W4GH6 - page 20
48488 A006 © 200 6. All rights reserved. ® Registe red Tradem ark/TM T rademark of W hirlpool, U .S.A., Manufactur ed under license by Tradewin ds Distributi ng Compan y, LLC., Coco nut Grove, Florida 6/06 Printed in U.S.A. ...