    SER VICE MANUAL CONTENTS 1. TECHNICAL CHANGES ··································· 3 2. P ART NAMES AND FUNCTIONS ····················· 3 3. SPECIFICA TION ················································ 4 4. OUTLINES AND DIMENSIONS ······? ...

  • Mitsubishi MUZ-FD09NA - page 2

    2 Revision A: • 3. SPECIFICA TION has been corrected. ...

  • Mitsubishi MUZ-FD09NA - page 3

    3 3 1 TECHNICAL CHANGES MUZ-FD09NA MUZ-FD09NA - U1 MUZ-FD12NA MUZ-FD12NA - U1 1. New model P ART NAMES AND FUNCTIONS 2 MUZ-FD09NA MUZ-FD12NA Air outlet Drain outlet Piping Drain hose Air inlet ...

  • Mitsubishi MUZ-FD09NA - page 4

    4 4 3 SPECIFICA TION Outdoor unit model MUZ-FD09NA MUZ-FD12NA Capacity Rated (Minimum~Maximum) Cooling 1 Btu/h 9,000 (2,800~9,000) 12,000 (2,800~12,000) Heating 47 1 Btu/h 10,900 (3,000~18,000) 13,600 (3,000~21,000) Capacity Rated Heating 17 2 Btu/h 12,500 13,600 Power consumption Rated (Minimum~Maximum) Cooling 1 W 650 (160~650) 960 (160~960) Heat ...

  • Mitsubishi MUZ-FD09NA - page 5

    5 5 T est condition ARI Mode T est Indoor air condition Outdoor air condition Dry bulb (°F) Wet bulb (°F) Dry bulb (°F) Wet bulb (°F) SEER (Cooling) "A" Cooling Steady State at rated compressor Speed 80 67 95 (75) "B-2" Cooling Steady State at rated compressor Speed 80 67 82 (65) "B-1" Cooling Steady State at minim ...

  • Mitsubishi MUZ-FD09NA - page 6

    6 6 OUTLINES AND DIMENSIONS 4 Unit: inch MUZ-FD09NA MUZ-FD12NA Liquid pipe :1/4 (flared) Gas pipe :3/8 (flared) 6-23/32 2 5-7/8 2-23/32 1-3/4 15-3/4 12 ~ 12-3/4 13-9/16 11 / 1 6 1-9/16 7/8 21-5/8 1 1-1/32 13/32 31-1/2 19-1 1/16 5-15/16 1 1-29/32 17/32 29/32 1 1-1/4 Air in handle Air in Air out 2- 3/8 13/16 Oval hole Drain hole 1-5/8 REQUIRED SP ACE ...

  • Mitsubishi MUZ-FD09NA - page 7

    7 7 5 WIRING DIAGRAM MUZ-FD09NA MUZ-FD12NA ...

  • Mitsubishi MUZ-FD09NA - page 8

    8 6 REFRIGERANT SYSTEM DIAGRAM Unit:inch MUZ-FD09NA MUZ-FD12NA Outdoor heat exchanger Flared connection Defrost thermistor RT6 1 Discharge temperature thermistor RT6 2 Service port Service port Flared connection Stop valve (with strainer) Stop valve (with service port) Refrigerant flow in cooling Compressor 4-way valve Refrigerant flow in heating R ...

  • Mitsubishi MUZ-FD09NA - page 9

    9 D ATA 7 MUZ-FD09NA MUZ-FD12NA 7-1. PERFORMANCE DA T A 1) COOLING CAP ACITY Model Indoor air Outdoor intake air DB temperature ( ˚ F) IWB 75 85 95 105 1 15 ( ˚ F) TC SHC TPC TC SHC TPC TC SHC TPC TC SHC TPC TC SHC TPC MUZ-FD09NA 71 1 1.0 6.9 0.58 10.3 6.5 0.63 9.7 6.1 0.68 9.0 5.6 0.72 8.3 5.2 0.75 67 10.4 7.9 0.55 9.7 7.4 0.60 9.0 6.8 0.65 8.4 ...

  • Mitsubishi MUZ-FD09NA - page 10

    10 10 7-2. PERFORMANCE CURVE 65 70 75 75 70 65 12 10 6 8 Indoor intake air DB tem perat ure (°F) = 381 CFM Airflow 15 25 35 45 55 Outdoor intake air WB temperature (°F) 0.4 0.6 0.8 Indoor intak e air DB temperat ure (°F ) T otal power consumption (kW) T otal capacity (1 0 3 Btu/h) 65 70 75 75 70 65 20 18 16 14 8 6 12 10 1.1 0.6 Indoor intake air ...

  • Mitsubishi MUZ-FD09NA - page 11

    11 11 7-3. CONDENSING PRESSURE Cooling Data is based on the condition of indoor humidity 50 %. Air flow should be set to High speed. MUZ-FD12NA (PSIG) Condensing pressure 86 80 75 70 68 70 75 80 85 90 95 100 105(°F) 120 125 130 135 140 145 150 155 160 165 170 175 180 Suction pressure Outdoor ambient temperature Indoor DB temperature (°F) (PSIG) 8 ...

  • Mitsubishi MUZ-FD09NA - page 12

    75 70 65 (PSIG) (PSIG) Condensing pressure Outdoor ambient temperature 14 20 25 30 35 40 45 50 55 60 65 70 (°F) 220 200 180 160 140 240 260 280 320 300 340 360 380 400 Ind oor DB tem perat ure( °F) 75 70 65 Suction pressure Outdoor ambient temperature 14 20 25 30 35 40 45 50 55 58Hz 58Hz 60 65 70(°F) 80 70 60 90 100 11 0 120 130 140 150 160 170 ...

  • Mitsubishi MUZ-FD09NA - page 13

    13 13 7-4. ST ANDARD OPERA TION DA T A Model MSZ-FD09NA MSZ-FD12NA Item Unit Cooling Heating Cooling Heating T otal Capacity Btu/h 9,000 10,900 12,000 13,600 SHF — 0.76 — 0.73 — Input kW 0.650 0.750 0.960 0.980 Rated frequency Hz 35 43 51 54 Electrical circuit Indoor unit MSZ-FD09NA MSZ-FD12NA Power supply V, phase, Hz 208/230 , 1 , 60 Input ...

  • Mitsubishi MUZ-FD09NA - page 14

    14 7-5. CAP ACITY AND INPUT CORRECTION BY INVERTER OUTPUT FREQUENCY Capacity correction factors Input correction factors Input correction factors Capacity correction factors Correction of Cooling capacity The operational frequency of compressor Correction of Cooling total input The operational frequency of compressor Correction of Heating total inp ...

  • Mitsubishi MUZ-FD09NA - page 15

    15 15 8 ACTUA TOR CONTROL MUZ-FD09NA MUZ-FD12NA 8-2. R.V . COIL CONTROL Heating . . . . . . . . . . . . . . . . . ON Cooling . . . . . . . . . . . . . . . . . OFF Dry . . . . . . . . . . . . . . . . . . . . OFF NOTE : The 4-way valve reverses for 5 seconds right before start-up of the compressor . ON OFF ON OFF Outdoor fan motor Compressor 5 second ...

  • Mitsubishi MUZ-FD09NA - page 16

    16 SER VICE FUNCTIONS 9 9-1. CHANGE IN DEFROST SETTING Changing defrost finish temperature <JS> T o change the defrost finish temperature, cut/solder the JS wire of the outdoor inverter P .C. board. (Refer to 10-6-1.) Jumper Defrost fi nish temperature JS Soldered (Initial setting) 41°F (5°C) None (Cut) 50°F (10°C) MUZ-FD09V A MUZ-FD12V ...

  • Mitsubishi MUZ-FD09NA - page 17

    17 Outline of the function This air conditioner can memorize the abnormal condition which has occurred once. Even though LED indication listed on the troubleshooting check table (10-3.) disappears, the memorized failure details can be recalled. This mode is very useful when the unit needs to be repaired for the abnormality which doesn't recur ...

  • Mitsubishi MUZ-FD09NA - page 18

    18 Does POWER lamp on the indoor unit blink at the interval of 0.5 seconds? Blinks: The outdoor unit is abnormal. Beep is emitted at the same timing as the blinking of POWER lamp. 2 Ye s (Blinks ) No (OFF) The outdoor unit might be abnormal. Con fi rm if outdoor unit is abnormal according to the following procedures. Operational procedure Con fi ...

  • Mitsubishi MUZ-FD09NA - page 19

    19 3. Outdoor unit failure mode table POWER lamp (Indoor unit) Abnormal point (Failure mode / protection) LED indication (Outdoor P .C. board) Condition Correspondence Indoor/ outdoor unit failure mode recall function Outdoor unit failure mode recall function OFF None (Normal) —— — — — 2-time fl ash 2.5 seconds OFF Outdoor power system ? ...

  • Mitsubishi MUZ-FD09NA - page 20

    20 10-3. TROUBLESHOOTING CHECK T ABLE No. Symptom LED indication Abnormal point/ Condition Condition Correspondence 1 Outdoor unit does not oper- ate. 1-time fl ash every 2.5 seconds Outdoor power sys- tem Overcurrent protection stop is continuously performed 3 times within 1 minute after the compressor gets started, or failure of restart of compr ...

  • Mitsubishi MUZ-FD09NA - page 21

    21 No. Symptom LED indication Abnormal point/ Condition Condition Correspondence 18 Outdoor unit operates. 7-time fl ash 2.5 seconds OFF Low discharge tem- perature protection T emperature of discharge temperature thermistor has been 122°F (50°C) or less for 20 minutes. Refer to 10-5. "Check of LEV". Check refrigerant circuit and refri ...

  • Mitsubishi MUZ-FD09NA - page 22

    22 10-4. TROUBLE CRITERION OF MAIN P ARTS MUZ-FD09NA MUZ-FD12NA Part name Check method and criterion Figure Defrost thermistor (RT61) Ambient temperature thermistor (RT65) Outdoor heat ex- changer temperature thermistor (RT68) Measure the resistance with a tester . Refer to 10-6. “T est point diagram and voltage”, 1. “Inverter P .C. board”, ...

  • Mitsubishi MUZ-FD09NA - page 23

    23 10-5. TROUBLESHOOTING FLOW Are the voltages balanced? Disconnect the connector (CN61) between compressor and the intelligent power module (IPM). Replace the inverter P .C. board. Check the voltage between terminals. Check the compressor . See 10-5. “Check of compressor”. No Ye s See 10-5. “Check of open phase”. ● With the connector bet ...

  • Mitsubishi MUZ-FD09NA - page 24

    24 F Check of compressor start failure D Check of compressor winding E Check of compressor operation time ● Disconnect the connector (CN61) between the compressor and intelligent power module, and measure the resistance between the compressor terminals. <<Measurement point>> at 3 points BLK-WHT BLK-RED WHT -RED <<Judgement>&g ...

  • Mitsubishi MUZ-FD09NA - page 25

    25 Is the thermistor normal? (Refer to 10-6.1.) Reconnect the connector of thermistor . T urn ON the power supply and press EMERGENCY OPERA TION switch. No Replace the thermistor except RT64. When R T64 is abnormal, replace the inverter P .C. board. Does the unit operate for 10 minutes or more without showing thermistor abnormality? OK. (Cause is p ...

  • Mitsubishi MUZ-FD09NA - page 26

    26 I Check of outdoor fan motor J Check of power supply Is the outdoor fan motor normal? (Refer to 10-4.) Replace the outdoor fan motor . Disconnect CN932 from the inverter P .C. board, and measure the resistance of the outdoor fan motor . Replace the inverter P .C. board. No Ye s Is there voltage 208/230 V AC between the indoor terminal block S1 a ...

  • Mitsubishi MUZ-FD09NA - page 27

    27 Press OPERA TE/ST OP (ON/OFF) button of the remote controller (the set temperature is displayed) with the remote controller headed towards the indoor unit. 1 Expansion valve operates in full-opening direction. OK. NOTE : After check of LEV , do the undermentioned operations. 1. T urn OFF the power supply and turn ON it again. 2. Press RESET butt ...

  • Mitsubishi MUZ-FD09NA - page 28

    28 Check the outdoor fan motor . (Refer to10-5. .) Is the fuse (F901) blown on the in- verter P .C. board? Check the connection of the connectors (CN932) of the outdoor fan motor . If the connection is poor , make it correct. Operate the outdoor unit by starting EMERGENCY OPERA TION. Check the LED indication on the in- verter P .C. board. Does the ...

  • Mitsubishi MUZ-FD09NA - page 29

    29 M How to check miswiring and serial signal error T urn OFF the power supply . Is there rated voltage in the power supply? Ye s No T urn ON the power supply . Check the power supply . Is there rated voltage between outdoor terminal block S1 and S2? No Check the wiring. Press EMERGENCY OPERA TION switch once. Does AREA-L lamp light up? <Con fi ...

  • Mitsubishi MUZ-FD09NA - page 30

    30 N Electromagnetic noise enters into TV sets or radios Ye s Is the unit grounded? No Ground the unit. Ye s Is the distance between the antennas and the indoor unit within 9.91 ft., or is the distance between the antennas and the outdoor unit within 9.91 ft.? No Extend the distance between the antennas and the indoor unit, and/or the antennas and ...

  • Mitsubishi MUZ-FD09NA - page 31

    31 10-6. TEST POINT DIAGRAM AND VOL T AGE -4 14 32 50 68 86 104 0 10 20 30 40 50 60 70 80 90 100 T emperature(°F) Defrost thermistor(RT61) Ambient temperature thermistor(RT65) Outdoor heat exchanger temperature thermistor(RT68) T emperature(°F) Discharge temperature thermistor(RT62) 32 50 68 86 104 122 140 158 176 194 212 230 248 0 100 200 300 40 ...

  • Mitsubishi MUZ-FD09NA - page 32

    32 1 1-1. MUZ-FD09NA MUZ-FD12NA NOTE : T urn OFF power supply before disassembling. OPERA TING PROCEDURE PHOTOS 1. Removing the cabinet (1) Remove the screw fixing the service panel. (See Photo 1.) (2) Pull down the service panel and remove it. (See Photo 1.) (3) Remove the screws fixing the conduit cover . (See Photo 2.) (4) Remove the conduit cov ...

  • Mitsubishi MUZ-FD09NA - page 33

    33 OPERA TING PROCEDURE PHOT OS 2. Removing the inverter assembly , inverter P .C. board (1) Remove the cabinet and panels. (Refer to 1.) (2) Disconnect the lead wire to the reactor and the following connectors; <Inverter P .C. board> CN721 (R.V .coil) CN932 (Fan motor) CN641 (Defrost thermistor and discharge temperature ther- mistor) CN643 ( ...

  • Mitsubishi MUZ-FD09NA - page 34

    34 OPERA TING PROCEDURE PHOT OS 5. Removing outdoor fan motor (1) Remove the cabinet and panels. (Refer to 1.) (2) Disconnect the connectors for outdoor fan motor . (3) Remove the propeller nut. (See Photo 7.) (4) Remove the propeller . (See Photo 7.) (5) Remove the screws fixing the fan motor . (See Photo 7.) (6) Remove the fan motor . 6. Removing ...

  • Mitsubishi MUZ-FD09NA - page 35

    35 ...

  • Mitsubishi MUZ-FD09NA - page 36

    HEAD OFFICE: TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAP AN Copyright 2008 MITSUBISHI ELECTRIC ENGINEERING CO.,L TD Distributed in Mar . 2008. No. OBH498 REVISED EDITION-A 7 Distributed in Jan. 2008. No. OBH498 7 Made in Japan New publication, effective Mar . 2008 Specifications subject to change without notice. TM ...

Produzent Mitsubishi Kategorie Air Conditioner

Dokumente, die wir vom Produzenten des Geräts Mitsubishi MUZ-FD09NA erhalten, können wir in mehrere Gruppen teilen. Unteranderem in:
- technische Zeichnungen Mitsubishi
- Bedienungsanleitungen MUZ-FD09NA
- Produktkarten Mitsubishi
- Informationsbroschüren
- oder Energieetiketten Mitsubishi MUZ-FD09NA
Jede von ihnen ist wichtig, jedoch finden wir die wichtigsten Informationen für den Nutzer des Geräts in der Bedienungsanleitung Mitsubishi MUZ-FD09NA.

Die Dokumentengruppe, die als Bedienungsanleitungen bezeichnet wird, wird ebenfalls in detaillierte Arten geteilt, solche wie: Montageanleitungen Mitsubishi MUZ-FD09NA, Wartungsanleitungen, Kurzanleitungen oder Benutzeranleitungen Mitsubishi MUZ-FD09NA. Abhängig vom Bedarf, sollten Sie das Dokument finden, das Sie brauchen. In unserem Service können Sie sich die populärste Bedienungsanleitung des Produkts Mitsubishi MUZ-FD09NA ansehen.

Ähnliche Bedienungsanleitungen

Die komplette Bedienungsanleitung des Geräts Mitsubishi MUZ-FD09NA, wie sollte sie aussehen?
Die Bedienungsanleitung, auch bezeichnet als Benutzerhandbuch, oder einfach nur „Anleitung”, ist ein technisches Dokument, das dem Benutzer bei der Nutzung von Mitsubishi MUZ-FD09NA hilfreich sein soll. Die Bedienungsanleitungen werden in der Regel von technischen Schriftstellern geschrieben, aber in einer Sprache, die für alle Nutzer von Mitsubishi MUZ-FD09NA verständlich ist.

Eine gänzliche Bedienungsanleitung von Mitsubishi sollte einige Grundelemente enthalten. Ein Teil von ihnen ist nicht so wichtig, wie z.B.: die Titelseite oder Autorenseiten. Die restlichen von ihnen jedoch, sollten Informationen liefern, die für den Nutzer von enormer Wichtigkeit sind.

1. Einführung und Hinweise, wie man sich in einer Bedienungsanleitung von Mitsubishi MUZ-FD09NA bewegt - Am Anfang jeder Bedienungsanleitung sollten wir Hinweise bezüglich der Nutzungsart eines bestimmten Ratgebers finden. In ihr sollten sich Informationen über die Lokalisierung des Inhaltsverzeichnisses von Mitsubishi MUZ-FD09NA befinden, FAQ oder über oft auftretende Probleme – also Stellen, die von den Benutzern in jeder Bedienungsanleitung am meisten gesucht werden
2. Inhaltsverzeichnis - Index aller Ratschläge bezüglich Mitsubishi MUZ-FD09NA, die wir im aktuellen Dokument finden
3. Ratschläge zur Nutzung der Grundfunktionen des Geräts Mitsubishi MUZ-FD09NA - die uns die ersten Schritte während der Nutzung von Mitsubishi MUZ-FD09NA erleichtern sollten
4. Troubleshooting - geordneter Tätigkeitslauf, der uns bei der Diagnose und als nächstes bei der Lösung wichtiger Probleme mit Mitsubishi MUZ-FD09NA hilft
5. FAQ - häufig gestellte Fragen
6. Kontaktdaten Informationen darüber, wo man Kontakt zum Produzenten / Service von Mitsubishi MUZ-FD09NA im bestimmten Land suchen kann, wenn es nicht gelingt, das Problem selbst zu lösen.

Haben Sie eine Frage bezüglich Mitsubishi MUZ-FD09NA?

Nutzen Sie das untere Formular

Wenn Sie mit Hilfe der gefundenen Bedienungsanleitung Ihr Problem mit Mitsubishi MUZ-FD09NA nicht gelöst haben, stellen Sie eine Frage, indem Sie das untere Formular nutzen. Wenn einer der Nutzer ein ähnliches Problem mit Mitsubishi MUZ-FD09NA hatte, ist es möglich, dass er mit Ihnen die Lösung teilen möchte.

Text vom Bild übertragen

Kommentare (0)