Summary
  • EMI T2HB - page 1

    EMI AMErIcA SErIES Mul tI-ZonE HEA t PuMP condEnSIng unItS P/N# 240006458 Rev . B [10/08] Enviromaster International LLC 5780 Success Dr . Rome, NY 13440 www .enviromaster .com InSt AllA tIon, oPErA tIon And MAIntEnAncE MAnuAl An ISO 9001-2000 Certied Company S2HB Multi-Zone S2HB, T2HB, T3HB, and T4HB Hea T PumPS Nominal Circuit Capacities: 9,00 ...

  • EMI T2HB - page 2

    www .enviromaster .com 2 multi-zone Heat Pump Condensing units inST alla Tion, oPera Tion and mainTenanCe manual EMI AMErIcA SErIES Mul tI-zonE HEA t PuMP condEnSIng unItS Shipping Damage MUST be Reported to the Carrier IMMEDIA TEL Y!!! Exa mine the cart on fo r si gns of da mage if any i s ev iden t ope n pa ckag ing a nd check the unit for shippi ...

  • EMI T2HB - page 3

    www .enviromaster .com 3 multi-zone Heat Pump Condensing units EMI AMErIcA SErIES Mul tI-zonE HEA t PuMP condEnSIng unItS • Co mp re ss or a nd F a n Mo to r Co nt ac to r • Capacitor • Low V oltage Connections • Large Capacity Suction Accumulator (9, 12, & 18 Only) • High Pressure Control (18 & 24 Only) • Solid Core Filter Drie ...

  • EMI T2HB - page 4

    www .enviromaster .com 4 multi-zone Heat Pump Condensing units S2HB InSt AllA tIon InStructIonS SEctIon 1. Loosen the screws on left and right sides of the front panel. (Do not remove these screws.) 2. Remove the screws on the front of the panel. 3. T o remove front panel: 4. S lide front panel forward to clear side screws and remove. Side discharg ...

  • EMI T2HB - page 5

    www .enviromaster .com 5 multi-zone Heat Pump Condensing units S2HB ElEctrIcAl WIrIng InSt AllA tIon SEctIon 3. Use only HACR type breakers or time delay fuses. Select the wi re size accord - ing to the ampacity rating. 4. T o access electrical connections and wiring diagram: a) Remove the screws on the side panel adjacent to the back panel. b) The ...

  • EMI T2HB - page 6

    www .enviromaster .com 6 multi-zone Heat Pump Condensing units 8. Check wiring diagram for the re - quired number of low voltage wires to be run between indoor and out- door sections. 9. Connect the 24 V olt wiring matching color to color . Refer to the wiring diagram on the inside panel of the condenser , and also refer to the wiring diagram on th ...

  • EMI T2HB - page 7

    www .enviromaster .com 7 multi-zone Heat Pump Condensing units t2HB, t3HB , And t4HB InSt AllA tIon InStructIonS SEctIon noTe: For S2HB installation refer to the S2HB Installation Instruction in this manual. 1. Remove the screw on the back panel. 2. R emove pa ne l t o e xp os e el e tr ic al wiring. 3. L ocation of electrical and tubing connec - t ...

  • EMI T2HB - page 8

    www .enviromaster .com 8 multi-zone Heat Pump Condensing units 5. with a screw - d r i v e r p u n c h out and remo ve the knock-outs in the low & high V olt elec - trical connec - tion box. Note: Power should be run to a weather proof disconnect box usually within 3 feet of the unit. eleCTriCal Wiring 6. From the disconnect box feed the high V ...

  • EMI T2HB - page 9

    www .enviromaster .com 9 multi-zone Heat Pump Condensing units The system will support refrigerant runs to the inside unit of up to 100' equivalent feet with a 35' rise included. The uni ts are furnished with sweat connections and are equipped with refrigerant valves and Mul tI-zonE HEA t PuMP rEfrIgErAnt PIPIng InSt AllA tIon Schrad er ? ...

  • EMI T2HB - page 10

    www .enviromaster .com 10 multi-zone Heat Pump Condensing units • A P-trap is recommended when the suc- tion riser is equal to or greater than 20 feet in height. • When the condenser is installed above the evaporator , the P-trap will help the return of oil back to the compressor . • The placement of the P-trap should be at the halfway mark o ...

  • EMI T2HB - page 11

    www .enviromaster .com 11 multi-zone Heat Pump Condensing units 8. Evacuate line to 500 microns or less to ensure all moisture has been removed and there are no leaks. It is ill eg al to disc ha rge ref rig era nt into th e at mo sp her e. Us e pr op er re cl ai min g methods & equipment when installing or servicing this unit. WArnIng ! ! 2. Pr ...

  • EMI T2HB - page 12

    www .enviromaster .com 12 multi-zone Heat Pump Condensing units 9. Once ce rt ai n of a go od e va c ua ti on an d l ea k fr e e j oi nt s, b ac k- se at th e v al ve s ( co un te r- cl oc kw is e ) to op en an d al l ow factory charge to ll lines and indoor unit. 1 1. Refer to Field Charging Charts to “ne tune” the refrigerant charge to ...

  • EMI T2HB - page 13

    www .enviromaster .com 13 multi-zone Heat Pump Condensing units The use of the superheat method is highly recommended for eld charging or checking th e exi st in g re fr ig era nt cha rge in a sys tem . Because each installation is different in terms of ind oo r ai r flo w , ref ri ger an t lin e le ng th, etc .. , the factory charge may not be ...

  • EMI T2HB - page 14

    www .enviromaster .com 14 multi-zone Heat Pump Condensing units Mul tI-zonE HEA t PuMP fIEld cHArgIng ...

  • EMI T2HB - page 15

    www .enviromaster .com 15 multi-zone Heat Pump Condensing units Mul tI-zonE HEA t PuMP fIEld cHArgIng ...

  • EMI T2HB - page 16

    www .enviromaster .com 16 multi-zone Heat Pump Condensing units Mul tI-zonE HEA t PuMP fIEld cHArgIng ...

  • EMI T2HB - page 17

    www .enviromaster .com 17 multi-zone Heat Pump Condensing units Mul tI-zonE HEA t PuMP fIEld cHArgIng ...

  • EMI T2HB - page 18

    www .enviromaster .com 18 multi-zone Heat Pump Condensing units ST arTing THe uniT • Before starting the unit in cool weather , power the system 24 hours before at - tempting to start. • Do a nal system check using the super- heat/subcooling method. Record results on T est Unit Performance Data sheet (next page). - Cooling mode superheat is ...

  • EMI T2HB - page 19

    www .enviromaster .com 19 multi-zone Heat Pump Condensing units St Art -uP And trouBlESHoo tIng tESt ProcEdurE The T est Unit Performance Data sheet below is provided for use by a qualied service professional. In order for our T echni - cal Service Departme nt to better serve you, please complete and have this information ready when calling. Mak ...

  • EMI T2HB - page 20

    www .enviromaster .com 20 multi-zone Heat Pump Condensing units Mul tI-zonE condEnSEr SEquEncE of oPErA tIon EM I Amer ica Series m ulti- zone he at pum p conden sers are desi gned to oper ate with EMI America Series indoor air han - dlers. Both the condenser (outdoor unit) and evaporator (indoor unit) have a hi gh V olt service connection. Each is ...

  • EMI T2HB - page 21

    www .enviromaster .com 21 multi-zone Heat Pump Condensing units DFT TST R and DF2 deFroST ConTrol TeSTing deFroST oPera Tion uSing TeST PinS Single-Zone and dual-Zone SequenCe oF oPera Tion W arning! B ef or e re mo vi ng th e ac ce ss p an el s to the unit make sure that all power is dis - c on ne ct ed fr om t he un it . F a il ur e t o d o so co ...

  • EMI T2HB - page 22

    www .enviromaster .com 22 multi-zone Heat Pump Condensing units Mul tI-zonE condEnSEr SEquEncE of oPErA tIon Refer to the indoor unit for the proper low V olt interconnect wiring. LOw VOL T INTERCONNECT DIAgRAMS oPera Tion and mainTenanCe The EMI America Series outdoor section is th e com pr es so r be ar in g uni t of the sy ste m. It operates at ...

  • EMI T2HB - page 23

    www .enviromaster .com 23 multi-zone Heat Pump Condensing units S2HB dIMEnSIonS And SPEcIfIcA tIonS noTe: All EMI products are subject to ongoing development programs so design and specications may change without notice. S2HB eleCTriCal SPeCiFiCa TionS model (1) Vol TS/HZ/PHaSe Fa n ComPreSSor 1 ComPreSSor 2 ToT al amPS min. Cir. amPS (2) HaCr B ...

  • EMI T2HB - page 24

    www .enviromaster .com 24 multi-zone Heat Pump Condensing units S2HB Sy StEM PErforMAncE S2HB / CaH SYSTem PerFormanCe model Cooling Hea Ting S2HB (Outdoor) indoor units Btuh Seer SHr eer Btuh HSPF C.o.P . 9900 CAH12 + CAH12 18,600 13.0 79 1 1.4 14,600 7.7 3.1 2200 CAH12 + CAH12 22,600 13.0 .75 1 1.3 18,400 7.7 3.2 9200 CAH12 + CAH12 20,600 13.0 .7 ...

  • EMI T2HB - page 25

    www .enviromaster .com 25 multi-zone Heat Pump Condensing units S2HB Sy StEM PErforMAncE S2HB / unH Side diSCHarge model Cooling Hea Ting S2HB (Outdoor) indoor units Btuh Seer SHr eer Btuh HSPF C.o.P . 9900 UNH09 + UNH09 18,600 13.0 .75 11.9 14,800 7.7 3.3 2200 UNH12 + UNH12 22,600 13.0 .73 11.7 18,400 7.7 3.3 9200 UNH09 + UNH12 20,600 13.0 .74 1 1 ...

  • EMI T2HB - page 26

    www .enviromaster .com 26 multi-zone Heat Pump Condensing units t2HB, t3HB , And t4HB dIMEnSIonS And SPEcIfIcA tIonS noTe: All EMI products are subject to ongoing development programs so design and specications may change without notice. lInE SEt , Sound & WEIgHt dA t A model line Set diameters Sound Weight liquid Suction dBa lbs. T2HB8800 3 ...

  • EMI T2HB - page 27

    www .enviromaster .com 27 multi-zone Heat Pump Condensing units t2HB, t3HB , And t4HB SPEcIfIcA tIonS noTe: All EMI products are subject to ongoing development programs so design and specications may change without notice. ELECTRICAL SPECIFICA TIONS • t2HB, t3HB , And t4HB - 208/230V - 60 HErtz 1 - PHASE CAP ACITY F AN MTR COMPRESSOR TOT AL AM ...

  • EMI T2HB - page 28

    www .enviromaster .com 28 multi-zone Heat Pump Condensing units WlH / t2HB, t3HB , or t4HB SyStEM PErforMAncE d A t A model Cooling Heating outdoor indoor air Handler Btuh Seer SHr eer Btuh HSPF CoP T2HB8800 (2) WLH24 36000 13 0.72 12.1 26800 7.7 3.3 T2HB8400 (2) WLH24 42000 13 0.68 1 1.9 32000 7.7 3.2 T2HB4400 (2) WLH24 48000 13 0.65 1 1.8 37400 7 ...

  • EMI T2HB - page 29

    www .enviromaster .com 29 multi-zone Heat Pump Condensing units CAH T2HB, T3HB, or T4HB T op Discharge t2HB, t3HB , And t4HB SPEcIfIcA tIonS cAH / t2HB, t3HB , or t4HB SyStEM PErforMAncE d A t A model Cooling Heating outdoor indoor air Handler Btuh Seer SHr eer Btuh HSPF CoP T2HB8800 (2) CAH24 36000 13 0.75 12.3 24400 7.7 3.1 T2HB8400 (2) CAH24 420 ...

  • EMI T2HB - page 30

    www .enviromaster .com 30 multi-zone Heat Pump Condensing units UNH T2HB, T3HB, or T4HB T op Discharge unH / t2HB, t3HB , or t4HB SyStEM PErforMAncE d A t A Model Cooling Heating Outdoor Indoor Air Handler Btuh SEER SHR EER Btuh HSPF COP T2HB8800 (2) UNH24 36000 13 0.72 12.1 26800 7.7 3.3 T2HB8400 (2) UNH24 42000 13 0.68 11.9 32000 7.7 3.2 T2HB4400 ...

  • EMI T2HB - page 31

    www .enviromaster .com 31 multi-zone Heat Pump Condensing units emi’S HigH Seer ProduCT line eV aPora TorS CondenSerS wLC/wLH High wall Evaporator CAC/CAH Cassette Evaporator S1C & S1H Single Zone Side Discharge S2C & S2H Dual Zone Side Discharge T2C, T3C & T4C T2H, T3H & T4H 2, 3, & 4 Zone Top Discharge UNC/UNH Universal Evap ...

  • EMI T2HB - page 32

    Phone: 1-800-228-9364 Fax: 1-800-232-9364 5780 Success Drive, Rome, NY 13440 ...

Fabricante EMI Categoría Heat Pump

Los documentos del dispositivo EMI T2HB que obtenemos del fabricante se pueden dividir en varios grupos. Entre ellos están::
- dibujos técnicos EMI
- manuales de instrucciones T2HB
- hojas de producto EMI
- folletos informativos
- o etiquetas energéticas EMI T2HB
Todos son importantes, pero lo más importante desde el punto de vista del usuario de un dispositivo lo encontraremos en el manual de instrucciones EMI T2HB.

Un conjunto de documentos determinado como manual de instrucciones se divide también en tipos más detallados, tales como: instrucciones de montaje EMI T2HB, instrucciones de servicio, instrucciones cortas o instrucciones de usuario EMI T2HB. Dependiendo de la situación debes buscar el documento que necesitas. En nuestra página puedes consultar el manual de instrucciones más popular del producto EMI T2HB.

Manuales de instrucciones parecidos

El manual de instrucciones del dispositivo EMI T2HB, ¿cómo debería ser?
El manual de instrucciones, también determinado como el manual de usuario o simplemente instrucciones, es un documento técnico que tiene como objetivo ayudar a los usuarios a utilizar EMI T2HB. Las instrucciones normalmente las realiza un escritor técnico pero en un lenguaje comprensible para todos los usuarios de EMI T2HB.

El manual de instrucciones completo de EMI debe contener unos elementos básicos. Una parte de ellos es menos importante, como por ejemplo: la portada / la página principal o las páginas de autor. Sin embargo, lo demás debe facilitarnos la información más importante desde el punto de vista del usuario.

1. Introducción y pistas sobre cómo orientarse con el manual EMI T2HB - Al principio de cada manual se deben encontrar las indicaciones acerca de la manera de usar un manual de instrucciones. Debe contener información sobre dónde encontrar el índice EMI T2HB, preguntas frecuentes o problemas más comunes – son los apartados más buscados por los usuarios de cada manual de instrucciones.
2. Índice - listados de todos los consejos acerca de EMI T2HB que encontraremos en el documento
3. Consejos de uso de las funciones básicas del dispositivo EMI T2HB - que deben facilitarnos los primeros pasos durante el uso de EMI T2HB
4. Troubleshooting - una secuencia sistematizada de acciones que nos ayudará a diagnosticar los problemas más importantes con EMI T2HB
5. FAQ - las preguntas frecuentes
6. Datos de contacto Información acerca de cómo encontrar los datos de contacto del fabricante / servicio de EMI T2HB en cada país si no somos capaces de solucionar el problema por nuestra cuenta.

¿Tienes una pregunta acerca de EMI T2HB?

Utiliza el formulario que se encuentra abajo

Si con la ayuda del manual de instrucciones encontrado no has podido solucionar tu problema con EMI T2HB, haz una pregunta utilizando el formulario que se encuentra abajo. Si alguno de los usuarios ha tenido un problema parecido con EMI T2HB probablemente compartirá una forma de solucionarlo.

Copia el texto de la imagen

Comentarios (0)