  • Carrier 23XRV - page 1

    Copyright 2010 Carrier Cor poration Form 23XR V -3PD Carrier’ s Ev ergreen ® 23XR V chiller is the world’ s first integ rated v ariable speed, water-cooled, screw chiller . It incorp or ates significant break- throughs in water-cooled chiller tech- nology to provide e xcellent reliability and achie v e superior efficiencies at true operating c ...

  • Carrier 23XRV - page 2

    2 V ariable speed capacity control elimi- nates slide valves, their associated loss- es, and their potential failure modes. Component count (both rotating and total) has been minimized assuring maximum relia bility under a wide range of operating conditions. High efficiency Per AHRI 550/590, chillers operate at design conditions less than one perce ...

  • Carrier 23XRV - page 3

    3 • Machine room cooling re quirements associated with air-cooled motors, which dissipate heat to the mechan- ical room. • High noise levels common with air- cooled motors, which radiate noise to the machine room and adjacent areas. • Shaft alignment problems that occur with open-drive designs during start- up and opera tion, when equipmen t ...

  • Carrier 23XRV - page 4

    4 feature also allows the machine to operate at reduced capacity, rather than shut down, when key safety limits are approached. Chilled liquid rese t — Reset can be accomplished manually or automatical- ly from the building management sys- tem. For a given capacity, reset allows operation at slower compresso r speeds, saving ener gy when war mer ...

  • Carrier 23XRV - page 5

    5 23XRV COMPRESSOR AND MOTOR WEIGHTS COMPONENT WEIGHTS LEGEND 23XR V HEA T EXCHANGER WEIGHTS COND — Condenser *Rigging weigh ts are for standard tube s of standard wall thickness (EDE and S pikefin 3, 0.025- in. [0.635 mm] wall). NO TE S : 1. Cooler incl udes the suction elbo w and 1 / 2 the distri b ut ion piping weight. 2. Condens er includes f ...

  • Carrier 23XRV - page 6

    6 ADDITIONAL WEIGHTS FOR 23XR V MARINE W A TERBOXES* 150 psig (1034 kPa) MARINE W A TERB OXES 300 psig (2068 kPa) MARINE W A TERB OXES *Add to cooler and condenser weights f or tota l weights. Cooler and condenser weights may be f ound in the 23XR V Heat Exchanger Weights tab le on page 5. The first dig it of the heat e xch anger code (first column ...

  • Carrier 23XRV - page 7

    7 *F actor y-installed. †Field-installed. ** S tandard waterbox nozzles are vi ctaulic type. Flanged nozzles are av ailable as an option with either nozzle-in-head type waterbo xes or marine waterbox es. ††Optional marine waterbox es av ailable for 23XR V heat exchanger frames 3-5 only . S tandard waterbo xes f or 23XR V are nozzle-in-head ty ...

  • Carrier 23XRV - page 8

    8 23XRV DIMENSIONS (NOZZLE-IN-HEAD W A TERBOX) 23XRV DIMENSIONS (MARINE W A TERBOX) *Assumes both cooler and condenser nozzles on same end of chiller . †1 or 3 pass length applies if c ooler is a 1 or 3 pa ss design. NO TE S : 1. S ervice access should be provided per America n S ociety of Heat- ing, Refrigerating, and Air Conditioning Engineers ...

  • Carrier 23XRV - page 9

    9 NOZZLE SIZE 23XR V HEA T EXCHANGER MIN/MAX FLOW RA TES* ENGLISH (GPM) *Flow rates based on standard tubes in the c ooler and condenser . Minimum flow based on tube velocity of 3 ft/sec (0.91 m/sec); maximum flow based on tube v elocity of 12 ft/sec (3.66 m/ sec). Consult the factory if variable primar y flow . SI (L/s) *Flow rates based on standa ...

  • Carrier 23XRV - page 10

    10 VFD FRAME SIZES *Maximum limits only . Additi onal applicatio n limits apply that will reduce these ampacities. AUXILIAR Y RA TINGS* *F actor y wired to VFD . †Minimum circuit ampacity of 15 amps. FRAME SIZE MAX INPUT CURRENT * MAX OUTPUT CUR RENT * AA 440 442 BA 520 442 BB 520 520 CC 60 8 60 8 ITEM V OL T A GE MAXIMUM PRO TECTIVE DEVICE SIZE ...

  • Carrier 23XRV - page 11

    11 Micropr ocessor contr ols Microprocessor controls provide the safety, interlock, ca- pacity control, indications and accessibility necessary to operate the chiller in a safe and efficient manne r . Control system The microprocessor control on each Carrier chiller is factory-mounted, factory-wired, and factory-tested to ensure machine protection ...

  • Carrier 23XRV - page 12

    12 Contr ols (cont) CONTROL P ANEL DISPLA Y (Front View) ICVC ENGLISH DI SPLA Y IN SI UNITS CONTROL P ANEL DISPLA Y (Front View) ICVC CHINESE D ISPLA Y IN METRIC UNIT S ...

  • Carrier 23XRV - page 13

    13 BLACK WHITE RED BLACK WHITE RED DRAIN WIRE DRAIN WIRE BLACK WHITE RED BLACK WHITE RED DRAIN WIRE GROUND DRAIN WIRE NO TE: Field-supplied ter minal strip must be located in control panel. LEGEND CCM — Chiller Control Module F actor y Wiring Field Wiring CCN COMMUNICA TION WIRING FOR M UL TIPLE CHILLERS (TYPICAL) a23-1649 ...

  • Carrier 23XRV - page 14

    14 Contro l sequence To s t a r t — Loca l start-up (man ual st art-up) is initiated by pressing the LOCAL or CCN menu softkey, which is indi- cated on the default inter nati onal chiller vis ual control (ICVC) screen. Time schedule 01 or 03, respectively, must be in the Occupied mode and the inter nal 15-minute start- to-start and the 1-minute s ...

  • Carrier 23XRV - page 15

    15 T ypical piping and wiring 1 1 1 6 7 8 TO CHILLED LIQUID PUMP TO CONDEN S ER LIQUID PUMP TO COOLING T OWER FAN 2 1 MAIN COMPRE SS OR MOTOR POWER FROM COOLING TOWER FROM LOAD TO COOLING TOWER TO LOAD 3 3 9 9 DRAIN 5 4 LEGEND 1— Disconnect 2— Unit-Mounted VFD/Control Center 3— Pressure Gages 4— Chilled Liquid Pump 5— Condenser Liquid Pum ...

  • Carrier 23XRV - page 16

    16 Contr ol wiring schematic 23XRV CO MPONENT ARRANGEMENT LEGEND CCM — Chiller Control Module CCN — Carrier Comfor t Network® ICVC — Internationa l Chiller Visual Controller GND — Gro und ...

  • Carrier 23XRV - page 17

    17 Application data F E Y Y * B G A VESSELS TYP . 0 ’ - 3 ” [76.2mm] ACCESSOR Y SOLEPLA TE 0 ’ -01/2” [1 3 mm] TYP . X X * VESSELS COND . COOLER C L C L C L C D  23XRV MACHINE FOOTPRINT * S ee detail on page 1 8 . 23XR V HEA T EXCHANGER SIZE DIMENSIONS (ft-in.) DIMENSIONS (mm) A BCDE F G A B C D E F G 30-32 12-10 3 / 4 5-4 1 / 4 0 0-3 ...

  • Carrier 23XRV - page 18

    18 Application data (cont) ELASTOMERIC P AD 23XRV ISOLA TION WITH ACCESSOR Y SOLEPLA TE P ACKAGE TYPICAL ISOLA T ION ST ANDARD ISOLA TION ACCESSORY SOLEPLA TE DET AIL VIEW X-X NO TE S : 1. Dimensions in ( ) are in millimeters. 2. Accessor y soleplate package includes 4 so leplates, 16 jacking scre ws and leveling pads. Requires isolation pac kage. ...

  • Carrier 23XRV - page 19

    19 12 11 10 9 8 7 6 5 4 3 2 1 23XRV NOZZLE ARRANGEMENTS NOZZLE-IN -HEAD W A TERBOXES FRAME 3 FRAMES 4 AND 5 NOZZLE ARRANGEMENT CODES FOR ALL 23XRV NOZZLE-I N-HEAD W A TERBOXES *Refer to certified drawings . PA S S COOLER W A TERBO XES In Out Arrangement Code * 1 8 5A 5 8 B 2 79 C 46 D 3 76 E 49 F PA S S CONDENSER W A TERBO XES In Out Arrangement Co ...

  • Carrier 23XRV - page 20

    20 Application data (cont) 23XR V NOZZLE ARRANGEMENTS (cont) MARINE W A TERBOXES FRAME 3 NOZZLE ARRANGEMENT CODES PA S S COOLER W A TERBO XES PA S S CONDENSER W A TERBOXES In Out Arrangement Code In Out Arrangement Code 1 8 5A 1 —— — 5 8 B— — — 2 79 C 2 10 12 R 46 D 1 3 S 3 76 E 3 —— — 49 F — — — FRAMES 4, AND 5 NOZZLE ARRAN ...

  • Carrier 23XRV - page 21

    21 23XRV W A TERBOX NOZZLE SIZES (Nozzle-In-Head and Marine W aterboxes RELIEF V AL VE LOCA TIONS * Coolers without optional isolat ion require 2 relief valves . NO TE: All valv es reliev e at 1 8 5 psig (1275 kPa). FRAME SIZE PRESSURE psig (kPa) PA S S NOMINAL PIPE SIZE (in.) A C TU AL PIPE ID (in.) Cooler Condenser Cooler Condenser 3 150/300 (103 ...

  • Carrier 23XRV - page 22

    22 V ent and drain connections Nozzle-in-head waterboxes have vent and drain connec- tions on covers. Marine waterboxes have vent and drain connections on waterbox shells. Provide high points of the chille r piping system with vents and the low points with drains. If shutoff valves are provid- ed in the main liquid pipes near the unit, a min imal a ...

  • Carrier 23XRV - page 23

    23 Insulation 23XR V MINIMUM FIELD-INST ALLED INSULA TION REQUIREMENTS Factory insulation — Ther mal insulation is factory- provided to the following areas: • Cooler (not including waterbox) • Suction line • Compressor and motor • Oil cooling line and oil retur n system line (oil and refrig- erant lines at or near evapo rator pressure are ...

  • Carrier 23XRV - page 24

    24 V ariable Speed Scre w Chiller HV AC Guide Specifications Size Range: 300 to 550 T ons (1055 to 1934 kW) Nominal Carrier Model Number: 23XR V Part 1 — General 1.01 SYSTEM DESCRIPTION A. Microprocessor -controlled l iquid chiller shall use a semi-her metic screw compressor using refrigerant HFC-134a only. Chiller refrigerant shall not have a pl ...

  • Carrier 23XRV - page 25

    25 D. Unit sh all be shipped with fir mly attached labels that indicate name of manufacturer , chiller model num- ber , chiller serial numb er , and refrigerant used. E. If the unit is to be exported, the manufacturer shall provide sufficient protection against sea water corro- sion, making the unit suitable for shipment in a standard open top ocea ...

  • Carrier 23XRV - page 26

    26 equipment to dissipate the motor heat as per the following for mula: Btuh = (FLkW motor) (0.05) (3413) Btuh = (FLkW motor) (171) and, alter nately T ons = Btuh/12,000 The additional piping, va lves, air -handling equipment, insulation, wiring, switchgear changes, ductwork, and coo rdination with other trades shall be the responsibility of the me ...

  • Carrier 23XRV - page 27

    27 input ter minals as the point of common cou- pling (PCC). b. The VFD full load effici ency shall meet or exceed 97% at 100% VFD rated ampacity. c. Active rectifier shall regulate unity displace- ment power factor to 0.99 or higher . d. V oltage boost capability to provide full mo tor voltage at reduced line voltage conditions. e. The VFD shall f ...

  • Carrier 23XRV - page 28

    28 liquid refrigerant to a reduced temperature, thereby increasing the refrigeration cycle efficiency. F . Refrigerant Flow Control: T o improve part load efficiency, liquid refrigerant shall be metered from the condenser to the cooler using a float-type metering valve to maintain the proper liquid level of refrigerant in the heat exchangers under ...

  • Carrier 23XRV - page 29

    29 displayed infor ming the operator that the chiller is operating in ramp loading mode. l. Chilled Water Reset: The control center shall allow re set of the chilled water temperature set point based on any one of the following criteria: 1) Chilled water reset base d on an exter nal 4 to 20 mA signal. 2) Chilled water reset based on a remote temper ...

  • Carrier 23XRV - page 30

    30 manual rotation of the lead chiller and a stag- gered restart of the chillers after a power fail- ure. The lead/lag system shall include load balancing if configured to do so. H. Electrical Requirements: 1. Electrical contractor shall supply and in stall main electrical power line, disconnect switches, circuit breakers, and electrical protection ...

  • Carrier 23XRV - page 31

    31 11. Cooler and Condenser T ubes: Contact a local Carrier Representa tive for other tube offerings. 12. Cooler and Condenser Passes: Unit manufacturer shall provide the cooler a nd/ or condenser with 1, 2 or 3 pass co nfiguration on the water side. 13. Nozzle-In-Head, 300 psig (2068 kPa): Unit manufacturer shall fur nish nozzle-in-head style wate ...

  • Carrier 23XRV - page 32

    Manufacturer reserves the right to dis continue, or change at any time, specifications or designs without notice and without inc urring obligations. Pg 32 Catalog No . 04-52230002-01 Printed in U . S .A. Form 23XRV -3PD Replaces: 23XR V -2PD S ection 9 Ta b 9 a Carrier Cor poration • S yracuse, New Y or k 13221 910 5-10 ...

Fabricante Carrier Categoría Water Dispenser

Los documentos del dispositivo Carrier 23XRV que obtenemos del fabricante se pueden dividir en varios grupos. Entre ellos están::
- dibujos técnicos Carrier
- manuales de instrucciones 23XRV
- hojas de producto Carrier
- folletos informativos
- o etiquetas energéticas Carrier 23XRV
Todos son importantes, pero lo más importante desde el punto de vista del usuario de un dispositivo lo encontraremos en el manual de instrucciones Carrier 23XRV.

Un conjunto de documentos determinado como manual de instrucciones se divide también en tipos más detallados, tales como: instrucciones de montaje Carrier 23XRV, instrucciones de servicio, instrucciones cortas o instrucciones de usuario Carrier 23XRV. Dependiendo de la situación debes buscar el documento que necesitas. En nuestra página puedes consultar el manual de instrucciones más popular del producto Carrier 23XRV.

Manuales de instrucciones parecidos

El manual de instrucciones del dispositivo Carrier 23XRV, ¿cómo debería ser?
El manual de instrucciones, también determinado como el manual de usuario o simplemente instrucciones, es un documento técnico que tiene como objetivo ayudar a los usuarios a utilizar Carrier 23XRV. Las instrucciones normalmente las realiza un escritor técnico pero en un lenguaje comprensible para todos los usuarios de Carrier 23XRV.

El manual de instrucciones completo de Carrier debe contener unos elementos básicos. Una parte de ellos es menos importante, como por ejemplo: la portada / la página principal o las páginas de autor. Sin embargo, lo demás debe facilitarnos la información más importante desde el punto de vista del usuario.

1. Introducción y pistas sobre cómo orientarse con el manual Carrier 23XRV - Al principio de cada manual se deben encontrar las indicaciones acerca de la manera de usar un manual de instrucciones. Debe contener información sobre dónde encontrar el índice Carrier 23XRV, preguntas frecuentes o problemas más comunes – son los apartados más buscados por los usuarios de cada manual de instrucciones.
2. Índice - listados de todos los consejos acerca de Carrier 23XRV que encontraremos en el documento
3. Consejos de uso de las funciones básicas del dispositivo Carrier 23XRV - que deben facilitarnos los primeros pasos durante el uso de Carrier 23XRV
4. Troubleshooting - una secuencia sistematizada de acciones que nos ayudará a diagnosticar los problemas más importantes con Carrier 23XRV
5. FAQ - las preguntas frecuentes
6. Datos de contacto Información acerca de cómo encontrar los datos de contacto del fabricante / servicio de Carrier 23XRV en cada país si no somos capaces de solucionar el problema por nuestra cuenta.

¿Tienes una pregunta acerca de Carrier 23XRV?

Utiliza el formulario que se encuentra abajo

Si con la ayuda del manual de instrucciones encontrado no has podido solucionar tu problema con Carrier 23XRV, haz una pregunta utilizando el formulario que se encuentra abajo. Si alguno de los usuarios ha tenido un problema parecido con Carrier 23XRV probablemente compartirá una forma de solucionarlo.

Copia el texto de la imagen