    P RODUCT S PECIFICA TIONS SS-PCB50 www .goodmanmfg.com 6/06 Supersedes 12/05 S ELF -C ONT AINED P ACKAGE A IR C ONDITIONER The PCB Commercial 50 Hz self-contained packaged air conditioner is designed for ground-level or rooftop application. PCB C OMMERCIAL S ERIES 50 Hz C OOLING C AP ACITY : 90,000 TO 180,000 BTU/ H 7½, 10, AND 15 T ON [26.4 kW to ...

  • Franklin SS-PCB50 - page 2

    2 SS-PCB50 P RODUCT S PECIFICA TIONS S PECIFICA TIONS PCB090-5 PCB120-5 PCB180-5 T otal Cooling - BTU/h (kW) 88,400 (25.9) 118,600 (34.8) 172,000 (50.4) Sensible Cooling - BTU/h¹ (kW) 67,100 (19.7) 89,200 (26.1) 131,000 (38.4) EER² 8.9 9.7 8.5 Indoor Blower (Qty .) 2 2 2 T ype Belt Belt Belt Size - D x W (mm) 12 x 12 (305 x 305) 12 x 15 (305 x 38 ...

  • Franklin SS-PCB50 - page 3

    SS-PCB50 3 P RODUCT S PECIFICA TIONS UNIT SIZE A - HEIGHT B - SUPPL Y AIR C - RETURN AIR 090 36” (914 mm) 12½” (318 mm) 179/16” (446 mm) 120,180 52” (1321 mm) 20¼” (514 mm) 2513/16” (656 mm) D IMENSIONS All dimensions in inches and millimeters. Drawings are not to scale. Note: The Horizontal Conversion K it is required to convert a fa ...

  • Franklin SS-PCB50 - page 4

    4 SS-PCB50 P RODUCT S PECIFICA TIONS E LECTRICAL C ONNECTIONS Main power entrance location (with electric heat installed) Control wiring entrance location Main power entrance location (without electric heat installed) Note: Single-point wiring is available at location #1 when heat kit is installed. See installation instructions for heat kits. 1– ...

  • Franklin SS-PCB50 - page 5

    SS-PCB50 5 P RODUCT S PECIFICA TIONS CFM EXTERNAL ST A TIC PRESSURE (INCHES W .C.) SEE NOTE (3) 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 2600 669 0.44 816 0.59 916 0.75 1004 0.92 1084 1.09 1157 1.28 1226 1.47 1291 1.67 2800 734 0.53 847 0.69 944 0.85 1030 1.03 1109 1.21 1181 1.40 1249 1.60 1312 ...

  • Franklin SS-PCB50 - page 6

    6 SS-PCB50 P RODUCT S PECIFICA TIONS Motor Sheave - Adjustable Factory Setting F an Sheave - Fixed T wo T urns Opens Motor Sheave T urns Open 0 1 2 3 4 5 F an RPM 3.0 HP Motor 1242 1186 1129 1073 1016 960 Note: Allow ±5% variation in blower RPM due to pulley manufacturing tolerances. Conversion F actor: 1 CFM = 0.472 L/S 1” W .C. = 2.5 M Bar 1 H ...

  • Franklin SS-PCB50 - page 7

    SS-PCB50 7 P RODUCT S PECIFICA TIONS Motor Sheave - Adjustable Factory Setting F an Sheave - Fixed 2 T urns Opens Motor Sheave T urns Open 012345 F an RPM 5.0 HP Motor 1400 1446 1273 1209 1146 1082 Note: Allow ±5% variation in blower RPM due to pulley manufacturing tolerances. Conversion F actor: 1 CFM = 0.472 L/S 1” W .C. = 2.5 M Bar 1 HP = 0.7 ...

  • Franklin SS-PCB50 - page 8

    8 SS-PCB50 P RODUCT S PECIFICA TIONS INDOOR AIR CONDENSER AIR TEMPERA TURE 75°F 85°F 95°F 105°F 115°F SCFM WB To t a l Kbtuh Sens Kbtuh Kw To t a l Kbtuh Sens Kbtuh Kw To t a l Kbtuh Sens Kbtuh Kw To t a l Kbtuh Sens Kbtuh Kw To t a l Kbtuh Sens Kbtuh Kw 2550 72 111.8 52.8 8.36 104.6 49.6 9.29 97.5 46.3 10.23 90.3 43.0 11.17 83.1 39.7 12.10 67 ...

  • Franklin SS-PCB50 - page 9

    SS-PCB50 9 P RODUCT S PECIFICA TIONS INDOOR AIR CONDENSER AIR TEMPERA TURE 23.9°C 29.4°C 35.0°C 40.6°C 46.1°C L/S WB T otal Cap. Sens Cap. Kw T otal Cap. Sens Cap. Kw T otal Cap. Sens Cap. Kw T otal Cap. Sens Cap. Kw T otal Cap. Sens Cap. Kw 2246 22.2 64.17 29.53 16.42 60.17 28.00 18.63 56.17 26.48 20.83 52.17 24.95 23.04 48.17 23.43 25.25 19. ...

  • Franklin SS-PCB50 - page 10

    10 SS-PCB50 P RODUCT S PECIFICA TIONS INDOOR AIR CONDENSER AIR TEMPERA TURE 75°F 85°F 95°F 105°F 115°F SCFM WB To t a l Kbtuh Sens Kbtuh Kw To t a l Kbtuh Sens Kbtuh Kw To t a l Kbtuh Sens Kbtuh Kw To t a l Kbtuh Sens Kbtuh Kw To t a l Kbtuh Sens Kbtuh Kw 4760 72 219.0 100.8 16.42 205.3 95.6 18.63 191.7 90.4 20.83 178.0 85.1 23.04 164.4 79.9 2 ...

  • Franklin SS-PCB50 - page 11

    SS-PCB50 11 P RODUCT S PECIFICA TIONS F ACT OR Y S UPPLIED A CCESSORIES T HERMOST A T (CHT90-120) T wo-stage cool and two-stage heat thermostat with subbase, Manual changeover , Fan ON or AUT O. Note: A variety of thermostat con fi gurations can be used on this equipment based on the application needs. For example our CHTS36-60 can be used if two- ...

  • Franklin SS-PCB50 - page 12

    12 SS-PCB50 P RODUCT S PECIFICA TIONS Q UALITY M AKES THE D IFFERENCE ! All of our systems are designed and manufactured with the same high-quality standards, regardless of size or ef fi ciency . W e have designed these units to signi fi cantly reduce the most frequent causes of product failure. They are simple to service and forgiving to operate ...

Fabricante Franklin Categoría Air Conditioner

Los documentos del dispositivo Franklin SS-PCB50 que obtenemos del fabricante se pueden dividir en varios grupos. Entre ellos están::
- dibujos técnicos Franklin
- manuales de instrucciones SS-PCB50
- hojas de producto Franklin
- folletos informativos
- o etiquetas energéticas Franklin SS-PCB50
Todos son importantes, pero lo más importante desde el punto de vista del usuario de un dispositivo lo encontraremos en el manual de instrucciones Franklin SS-PCB50.

Un conjunto de documentos determinado como manual de instrucciones se divide también en tipos más detallados, tales como: instrucciones de montaje Franklin SS-PCB50, instrucciones de servicio, instrucciones cortas o instrucciones de usuario Franklin SS-PCB50. Dependiendo de la situación debes buscar el documento que necesitas. En nuestra página puedes consultar el manual de instrucciones más popular del producto Franklin SS-PCB50.

Manuales de instrucciones parecidos

El manual de instrucciones del dispositivo Franklin SS-PCB50, ¿cómo debería ser?
El manual de instrucciones, también determinado como el manual de usuario o simplemente instrucciones, es un documento técnico que tiene como objetivo ayudar a los usuarios a utilizar Franklin SS-PCB50. Las instrucciones normalmente las realiza un escritor técnico pero en un lenguaje comprensible para todos los usuarios de Franklin SS-PCB50.

El manual de instrucciones completo de Franklin debe contener unos elementos básicos. Una parte de ellos es menos importante, como por ejemplo: la portada / la página principal o las páginas de autor. Sin embargo, lo demás debe facilitarnos la información más importante desde el punto de vista del usuario.

1. Introducción y pistas sobre cómo orientarse con el manual Franklin SS-PCB50 - Al principio de cada manual se deben encontrar las indicaciones acerca de la manera de usar un manual de instrucciones. Debe contener información sobre dónde encontrar el índice Franklin SS-PCB50, preguntas frecuentes o problemas más comunes – son los apartados más buscados por los usuarios de cada manual de instrucciones.
2. Índice - listados de todos los consejos acerca de Franklin SS-PCB50 que encontraremos en el documento
3. Consejos de uso de las funciones básicas del dispositivo Franklin SS-PCB50 - que deben facilitarnos los primeros pasos durante el uso de Franklin SS-PCB50
4. Troubleshooting - una secuencia sistematizada de acciones que nos ayudará a diagnosticar los problemas más importantes con Franklin SS-PCB50
5. FAQ - las preguntas frecuentes
6. Datos de contacto Información acerca de cómo encontrar los datos de contacto del fabricante / servicio de Franklin SS-PCB50 en cada país si no somos capaces de solucionar el problema por nuestra cuenta.

¿Tienes una pregunta acerca de Franklin SS-PCB50?

Utiliza el formulario que se encuentra abajo

Si con la ayuda del manual de instrucciones encontrado no has podido solucionar tu problema con Franklin SS-PCB50, haz una pregunta utilizando el formulario que se encuentra abajo. Si alguno de los usuarios ha tenido un problema parecido con Franklin SS-PCB50 probablemente compartirá una forma de solucionarlo.

Copia el texto de la imagen

Comentarios (0)