    GENERAL The outdoor units are completely piped and wired at the fac- tory and are shipped ready for immediate installation. Only the interconnecting liquid and suction lines, sight glasses, control wiring, and the main power wiring are required to complete the installation. Every unit is dehydrated, evacu - ated, leak tested and pressure tested at ...

  • York E1FB240 - page 2

    2 Unitary Products Group 035-16192-001-A-1001 E 1 F B 2 5 8 A PRODUCT NOMENCLATURE PRODUCT GENERATION 1 = First Generation PRODUCT CA TEGOR Y E = S plit-System Heat Pump Outdoor Unit PRODUCT IDENTIFIER FB = Outdoor Unit VOL TAGE CODE 25 = 208/230-3-60 46 = 460-3-60 NOMINAL COOLING CAP ACITY 180 = 15 T on 240 = 20 T on F ACTOR Y INST ALLED HEA T A = ...

  • York E1FB240 - page 3

    LIMIT ATIONS These units must be installed in accordance with all national and local safety codes. If no local codes apply , installation must conform with the appropriate national codes. See T able 1 for unit application data. Units are designed to meet National Safety Code S tandards. If components are to be added to a unit to meet local codes, t ...

  • York E1FB240 - page 4

    CAUTION: LENGTH OF FORKS MUST BE A MINIMUM OF 54" (when lifting from the compressor end of the unit) and a MINIMUM OF 42" (when lifting from the front or rear of the unit). Remove the nesting brackets from the four corners on top of the unit. All screws that are removed to take these brackets of f must be replaced on the unit. CLEARANCES ...

  • York E1FB240 - page 5

    Unitary Products Group 5 035-16192-001-A-1001 INDOOR UNIT OUTDOOR UNIT TERMINALS ON HEAT PUMP TH ERMOSTAT 1 1 Control wiring (24-v olt) refe r to elect rical d ata to deter mine th e prope r wire s ize. T ABLE 3 - ELECTRICAL DA T A 1 Maximum fuse or maximum circuit breaker (HACR type per NEC). 2 Based on three 75°C insulated copper conductors in c ...

  • York E1FB240 - page 6

    6 Unitary Products Group 035-16192-001-A-1001 All dimensions are in inches. They are subject to change without notice. Certified dimensions will be provided upon request. CLEARANCES Overhead (T op) 1 120" Front (Piping and Access Panels) 30" Left Side 24" Right Side 24" Rear 24" Bottom 2 0" 1 Units must be installed ou ...

  • York E1FB240 - page 7

    and/or drafts. Circulation of air to the thermost at should not be blocked by curtains, drapes, furniture, partitions, etc. Some installations may require a locking cover to protect the thermostat from tampering and/or damage. Both the manual and the auto changeover thermostats have non-adjustable, voltage-type anticip ators for both cooling and he ...

  • York E1FB240 - page 8

    3. T urn the stem in (or clockwise) between 1/4 and 1/2 turn to open the access port. As soon as some internal pressure is relieved, close the ac- cess port. DO NOT remove the entire holding charge. NOTE: The copper disc on the liquid connection will prevent any internal pressure from being relieved through the main port of the liquid line stop val ...

  • York E1FB240 - page 9

    4. After the disc has been removed, burnish the external sur - faces and clean the internal surfaces as outlined above. 5. Move the dry nitrogen supply back to the access port on the liquid line service valve. 6. Braze the liquid line to the liquid connection on the indoor unit while maintaining a minimum flow of dry nitrogen through the liquid lin ...

  • York E1FB240 - page 10

    10 Unitary Products Group 035-16192-001-A-1001 FIG . 5 - EXTENDING THE SERVICE POR TS ALTERNA TE CHARGING METHODS If you are starting a unit when the ambient temperature is higher or lower than those shown in Figures 7 through 15, either of the following methods may be used. Method 1: Determine the total weight of the refrigerant for the total syst ...

  • York E1FB240 - page 11

    GENERAL During the cooling cycle, when the reversing valve solenoids becomes energized, operation will be the same as any conven - tional air conditioning system. During the heating cycle, when the reversing valve solenoids becomes de-energized, compressor discharge gas will be di - verted to the indoor coil and the outdoor coil will become the eva ...

  • York E1FB240 - page 12

    through the defrost control boards and safety switches to energize relays RY1 and R Y2, which in turn will energize contactors 1M & 3M, starting the compressors. Contactors 2M and 4M are energized through the NO contact s on auxil - iary contactors 1M-AUX and 3M-AUX in order to start the outdoor fan motors. 4. Relays RY1 and R Y2 prevent the el ...

  • York E1FB240 - page 13

    OPERATION BELOW 0 ° F OUTDOOR TEMPERA - TURE 1. At 0 ° F outdoor temperature, the low temperature compres - sor cutoff thermost at TH1 and TH3 contacts 1 and 3 will open, de-energizing contactor 1M and 3M which shuts down the compressor . Contacts 1 and 2 of thermostat TH1 and TH3 are closed when contacts 1 and 3 are open. This feature allows the ...

  • York E1FB240 - page 14

    CRANKCASE HEA TER The crankcase heaters must be energized at least 8 hours bef - ore starting the compressor . T o energize the crankcase heat - ers, the main disconnect switch must be closed. During this 8 hour period, the system switch on the room thermostat must be “OFF” to prevent the compressor from starting. CAUTION: DO NOT A TTEMPT TO ST ...

  • York E1FB240 - page 15

    Unitary Products Group 15 035-16192-001-A-1001 150 200 250 300 350 400 50 60 70 80 90 S u c t i o n P r essu re ( p si g ) D i sc h a rg e P ressu re ( p si g ) 115 °F 105 °F 95 °F 85 °F 75 °F ODDB 150 200 250 300 350 400 450 50 60 70 80 90 S u c t i o n P ressu re ( p si g ) D i sc h a rg e P r essu re ( p si g ) 115 °F 105 °F 95 °F 85 °F ...

  • York E1FB240 - page 16

    16 Unitary Products Group 035-16192-001-A-1001 FIG . 9 - HEA TING MODE CHARGING CHART A T 4800 CFM - EFB180A 50 100 150 200 250 300 350 400 30 40 50 60 70 80 90 S u c t i o n P ressu re ( p si g ) D i sc h a rg e P ressu re ( p si g ) 80 °F 70 °F 60 °F IDDB FIG . 10 - HEA TING MODE CHARGING CHART A T 6000 CFM - EFB180A 50 100 150 200 250 300 350 ...

  • York E1FB240 - page 17

    Unitary Products Group 17 035-16192-001-A-1001 FIG . 1 1 - HEA TING MODE CHARGING CHART A T 6600 CFM - EFB180A 50 100 150 200 250 300 350 400 30 40 50 60 70 80 90 S u c ti o n P ressu re ( p si g ) D i sc h a rg e P ressu re ( p si g ) 80 °F 70 °F 60 °F IDDB FIG . 12 - HEA TING MODE CHARGING CHART A T 6400 CFM - EFB240A 50 100 150 200 250 300 35 ...

  • York E1FB240 - page 18

    18 Unitary Products Group 035-16192-001-A-1001 FIG . 13 - HEA TING MODE CHARGING CHART A T 7000 CFM - EFB240A 50 100 150 200 250 300 350 30 40 50 60 70 80 90 S u c t i o n P ressu re ( p si g ) D i sc h a rg e P ressu re ( p si g ) 80 °F 70 °F 60 °F IDDB FIG . 14 - HEA TING MODE CHARGING CHART A T 7600 CFM - EFB240A 50 100 150 200 250 300 350 40 ...

  • York E1FB240 - page 19

    NOTES Unitary Products Group 19 035-16192-001-A-1001 ...

  • York E1FB240 - page 20

    Unitary Products Group 5005 Y ork Drive, Norman, Oklahoma 73069 Subject to change without notice. Printed in U.S.A Copyright  by Y ork International Corporation 2001. All Rights Reserved. Code: SBY 035-16192-001-A-1001 Supersedes: 035-16192-000 (0601) ...

Fabricante York Categoría Heat Pump

Los documentos del dispositivo York E1FB240 que obtenemos del fabricante se pueden dividir en varios grupos. Entre ellos están::
- dibujos técnicos York
- manuales de instrucciones E1FB240
- hojas de producto York
- folletos informativos
- o etiquetas energéticas York E1FB240
Todos son importantes, pero lo más importante desde el punto de vista del usuario de un dispositivo lo encontraremos en el manual de instrucciones York E1FB240.

Un conjunto de documentos determinado como manual de instrucciones se divide también en tipos más detallados, tales como: instrucciones de montaje York E1FB240, instrucciones de servicio, instrucciones cortas o instrucciones de usuario York E1FB240. Dependiendo de la situación debes buscar el documento que necesitas. En nuestra página puedes consultar el manual de instrucciones más popular del producto York E1FB240.

Manuales de instrucciones parecidos

El manual de instrucciones del dispositivo York E1FB240, ¿cómo debería ser?
El manual de instrucciones, también determinado como el manual de usuario o simplemente instrucciones, es un documento técnico que tiene como objetivo ayudar a los usuarios a utilizar York E1FB240. Las instrucciones normalmente las realiza un escritor técnico pero en un lenguaje comprensible para todos los usuarios de York E1FB240.

El manual de instrucciones completo de York debe contener unos elementos básicos. Una parte de ellos es menos importante, como por ejemplo: la portada / la página principal o las páginas de autor. Sin embargo, lo demás debe facilitarnos la información más importante desde el punto de vista del usuario.

1. Introducción y pistas sobre cómo orientarse con el manual York E1FB240 - Al principio de cada manual se deben encontrar las indicaciones acerca de la manera de usar un manual de instrucciones. Debe contener información sobre dónde encontrar el índice York E1FB240, preguntas frecuentes o problemas más comunes – son los apartados más buscados por los usuarios de cada manual de instrucciones.
2. Índice - listados de todos los consejos acerca de York E1FB240 que encontraremos en el documento
3. Consejos de uso de las funciones básicas del dispositivo York E1FB240 - que deben facilitarnos los primeros pasos durante el uso de York E1FB240
4. Troubleshooting - una secuencia sistematizada de acciones que nos ayudará a diagnosticar los problemas más importantes con York E1FB240
5. FAQ - las preguntas frecuentes
6. Datos de contacto Información acerca de cómo encontrar los datos de contacto del fabricante / servicio de York E1FB240 en cada país si no somos capaces de solucionar el problema por nuestra cuenta.

¿Tienes una pregunta acerca de York E1FB240?

Utiliza el formulario que se encuentra abajo

Si con la ayuda del manual de instrucciones encontrado no has podido solucionar tu problema con York E1FB240, haz una pregunta utilizando el formulario que se encuentra abajo. Si alguno de los usuarios ha tenido un problema parecido con York E1FB240 probablemente compartirá una forma de solucionarlo.

Copia el texto de la imagen

Comentarios (0)