    SINGLE-PACKAGE GAS HEATING/ELECTRIC COOLING UNITS Model 582A Sizes 018-060 1-1/2 to 5 Nominal Tons Low NOx Models Available Form No. PDS 582A.18.2 Single-Package Rooftop Units with. • Direct Spark Ignition • Low Sound Levels • AFUE ratings up to 81.1% • 10 SEER AVAILABLE OPTIONS One-piece heating and cooling units with low sound levels, eas ...

  • Bryant BRYANT 582A - page 2

    2 Low Sound Ratings ensure a quiet indoor and outdoor environ- ment with sound ratings as low as 7.5 bels. (See ARI capacity charts for individual values.) Easy-to-Service Cabinets provide easy single-panel acces- sibility to serviceable components during maintenance and installation. The basepan with integrated drain pan provides easy ground level ...

  • Bryant BRYANT 582A - page 3

    ARI* CAP ACITIES COOLING CAP ACITIES AND EFFICIENCIES UNIT 582A NOMINAL T ONS ST ANDARD CFM NET COOLING CAP ACITIES (Btuh) SEER† SOUND RA TINGS** (Bels) 018040 1 1 / 2 600 18,000 10.0 7.5 024040 024060 2 800 24,600 10.0 7.5 030040 030060 2 1 / 2 1000 28,800 10.0 7.5 036060 036090 3 1200 34,400 10.0 8.0 042060 042090 3 1 / 2 1400 42,000 10.0 8.0 0 ...

  • Bryant BRYANT 582A - page 4

    PHYSICAL DA T A UNIT SIZE 582A 018040 024040 024060 030040 030060 036060 036090 042060 042090 NOMINAL CAP ACITY (ton) 1 1 / 2 22 2 1 / 2 2 1 / 2 33 3 1 / 2 3 1 / 2 OPERA TING WEIGHT (lb) 249 280 280 280 280 314 314 355 355 COMPRESSOR(S) – QUANTITY Reciprocating-1 REFRIGERANT (R-22) Quantity (lb) 2.6 3.5 3.5 3.65 3.65 3.75 3.75 5.7 5.7 REFRIGERANT ...

  • Bryant BRYANT 582A - page 5

    OPTIONS AND ACCESSORIES F ACTORY -INST ALLED OPTIONS Louvered Grille provides hail guard and vandalism protection. A wire grille is standard on all models. See model number no- menclature for louvered grille options. Coil Options include copper/copper and vinyl-coated construc- tion for refrigerant coils. Units are shipped standard with copper tube ...

  • Bryant BRYANT 582A - page 6

    OPTIONS AND ACCESSORIES (cont) Economizer DAMPER BLADE MANUAL OUTSIDE AIR HOOD REPLACEMENT P ANEL Filter Rack Manual Outdoor Air Damper 6 ...

  • Bryant BRYANT 582A - page 7

    BASE UNIT DIMENSIONS – 582A018-042 REQ'D CLEARANCES FOR OPERA TION AND SER VICING. in. (mm) Evaporator coil access side .................. 3 6 (914) Power entry side (except for NEC requirements) ......... 3 6 (914) Unit top ........................... 3 6 (914) Side opposite ducts ..................... 3 6 (914) Duct panel ................. ...

  • Bryant BRYANT 582A - page 8

    BASE UNIT DIMENSIONS – 582A048-060 FLUE HOOD REQ'D CLEARANCES FOR OPERA TION AND SER VICING. in. (mm) Evaporator coil access side .................. 3 6 (914) Power entry side (except for NEC requirements) ......... 3 6 (914) Unit top ........................... 3 6 (914) Side opposite ducts ..................... 3 6 (914) Duct panel ....... ...

  • Bryant BRYANT 582A - page 9

    ACCESSOR Y DIMENSIONS UNIT SIZE 582A ODS ORDER NUMBER A in. [mm] B in. [mm] C in. [mm] D in. [mm] FLA T CURB 018-042 CPRFCURB006A00 8 [203] 1 1 27 / 32 [301] 30 5 / 8 [778] 28 3 / 4 [730] CPRFCURB007A00 14 [356] 1 1 27 / 32 [301] 30 5 / 8 [778] 28 3 / 4 [730] 048,060 CPRFCURB008A00 8 [203] 15 27 / 32 [402] 42 1 / 8 [1070] 40 1 / 4 [1022] CPRFCURB00 ...

  • Bryant BRYANT 582A - page 10

    SELECTION PROCEDURE (with example) I DETERMINE COOLING AND HEA TING REQUIRE- MENTS A T DESIGN CONDITIONS: Given: Required Cooling Capacity (TC) .......... 34,000 Btuh Btuh Sensible Heat Capacity (SHC) ....... 25,000 Btuh Btuh Required Heating Capacity ......... 60,000 Btuh Condenser Entering Air T emperature ............9 5 F Indoor-Air T emperatur ...

  • Bryant BRYANT 582A - page 11

    PERFORMANCE DA T A NET COOLING CAP ACITIES 582A018 TEMP (F) OUTDOOR-AIR ENTERING CONDENSER EV APORA T OR AIR—CFM/BF 525/0.118 Evaporator Air—Ewb (F) 62 67 72 62 67 72 62 67 72 85 TC 15.7 18.5 20.9 16.5 19.2 21.5 17.2 19.8 21.9 SHC 13.5 1 1.6 9.5 14.9 12.7 10.2 16.2 13.6 10.7 kW 1.75 1.80 1.83 1.77 1.81 1.84 1.78 1.82 1.85 95 TC 14.5 17.3 19.9 1 ...

  • Bryant BRYANT 582A - page 12

    PERFORMANCE DA T A (cont) NET COOLING CAP ACITIES (cont) 582A036 TEMP (F) OUTDOOR-AIR ENTERING CONDENSER EV APORA T OR AIR—CFM/BF 1050/0.095 Evaporator Air—Ewb (F) 62 67 72 62 67 72 62 67 72 85 TC 31.8 35.3 38.7 32.7 36.1 39.5 33.4 36.8 40.1 SHC 29.1 24.2 19.0 31.4 26.0 20.0 33.4 27.6 21.0 kW 3.48 3.57 3.66 3.50 3.59 3.68 3.52 3.61 3.70 95 TC 3 ...

  • Bryant BRYANT 582A - page 13

    PERFORMANCE DA T A (cont) NET COOLING CAP ACITIES (cont) 582A060 TEMP (F) OUTDOOR-AIR ENTERING CONDENSER EV APORA T OR AIR – CFM/BF 1750/0.039 Evaporator Air – Ewb (F) 62 67 72 62 67 72 62 67 72 85 TC 53.9 61.5 69.3 56.1 63.6 71.1 58.0 65.2 72.4 SHC 48.8 41.4 33.4 53.7 45.2 35.7 58.0 48.8 37.9 kW 6.12 6.33 6.52 6.21 6.38 6.57 6.25 6.42 6.62 95 ...

  • Bryant BRYANT 582A - page 14

    PERFORMANCE DA T A (cont) DR Y COIL AIR DELIVER Y*—HORIZONT AL AND DOWNFLOW DISCHARGE (Deduct 10% for 208 v) 230 AND 460 VOL T Unit 582A Motor Speed External Static Pressure (in. wg) 0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 018 Low W atts 227 212 196 177 165 153 CFM 1082 1016 929 796 668 428 ————— ————— Med W atts ——— ...

  • Bryant BRYANT 582A - page 15

    PERFORMANCE DA T A (cont) ECONOMIZER/1-IN. FIL TER PRESSURE DROP UNIT 582A PRESSURE DROP (in. wg) 018-042 0.12 048, 060 0.24 WET COIL PRESSURE DROP UNIT 582A AIRFLOW (CFM) PRESSURE DROP (in. wg) 018 500 0.049 600 0.070 700 0.095 024 700 0.077 800 0.100 900 0.127 030 900 0.065 1000 0.080 1 100 0.097 036 1 100 0.084 1200 0.100 1300 0.177 042 1300 0.1 ...

  • Bryant BRYANT 582A - page 16

    TYPICAL PIPING AND WIRING V ertical Discharge *NEC – National Electrical Code Horizontal Discharge 16 INDOOR THERMOST A T DISCONNECT PER NEC* FROM POWER SOURCE RETURN AIR T OP CO VER FROM GAS LINE *NEC - NA TIONAL ELECTRICAL CODE Horizontal Discharge ...

  • Bryant BRYANT 582A - page 17

    17 APPLICATION DATA 1. CONDENSATE TRAP —A 2-in. condensate trap must be field supplied. 2. DUCTWORK —Secure downflo w discharge ductwork to roof curb . For horizontal discharge applications , attach ductwork to unit with flanges. 3. T O CONVERT A UNIT TO DOWNFLO W DISCHARGE — Units are equipped with f actor y-installed inser ts in the down ...

  • Bryant BRYANT 582A - page 18

    TYPICAL WIRING SCHEMA TIC, 582A018-060; 208/230-1-60 LEGEND BR — Blower Relay C— Contactor CAP — Capacitor COMP — Compressor Motor CR — Combustion Relay EQUIP — Equipment FS — Flame Sensor FU — Fuse GND — Ground GVR — Gas V alve Relay HS — Hall Effect Sensor HV — High Voltage T ransformer TRAN I— Ignitor IDM — Induced-Dr ...

  • Bryant BRYANT 582A - page 19

    TYPICAL WIRING SCHEMA TIC, 582A030-060; 208/230-3-60 LEGEND AHA — Adjustable Heat Anticipator BR — Blower Relay C— Contactor CAP — Capacitor COMP — Compressor Motor CR — Combustion Relay CS — Centrifugal Switch EQUIP — Equipment FS — Fusible Link FU — Fuse GND — Ground GV — Gas V alve GVR — Gas V alve Relay HS — Hall Eff ...

  • Bryant BRYANT 582A - page 20

    TYPICAL WIRING SCHEMA TIC, 582A036-060; 460-3-60 LEGEND AHA — Adjustable Heat Anticipator BR — Blower Relay C— Contactor CAP — Capacitor COMP — Compressor Motor CR — Combustion Relay CS — Centrifugal Switch EQUIP — Equipment FS — Fusible Link FU — Fuse GND — Ground GV — Gas V alve GVR — Gas V alve Relay HS — Hall Effect ...

  • Bryant BRYANT 582A - page 21

    ELECTRICAL DA T A UNIT SIZE 582A V -PH-Hz VOL T AGE RANGE COMPRESSOR COND F AN MOTOR INDOOR F AN MOTOR POWER SUPPL Y Min Max RLA LRA FLA FLA MCA MOCP* 018 208/230-1-60 187 253 9.0 45.0 0.8 1.8 13.9 20 024 208/230-1-60 187 253 12.8 61.0 0.8 2.0 18.8 30 030 208/230-1-60 187 253 14.4 73.0 0.8 2.0 20.8 30 036 042 208/230-1-60 187 253 18.6 105.0 1.6 3.8 ...

  • Bryant BRYANT 582A - page 22

    CONTROLS OPERA TING SEQUENCE Heating — When the thermostat calls for heating, terminal “W” is energized, starting the induced-draft motor . When the hall- effect sensor on the induced-draft motor senses that it has reached the required speed, the burner ignition sequence be- gins. The indoor (evaporator) fan motor (IFM) is energized 45 second ...

  • Bryant BRYANT 582A - page 23

    GUIDE SPECIFICA TIONS P ACKAGED HEA TING/COOLING UNITS CONST ANT VOLUME APPLICA TION HV AC GUIDE SPECIFICA TIONS SIZE RANGE: 1 1 / 2 TO 5 TONS, NOMINAL COOLING 40,000 T O 130,000 BTUH, NOMINAL HEA TING INPUT BRY ANT MODEL NUMBER: 582A P ART 1 — GENERAL SYSTEM DESCRIPTION Outdoor rooftop mounted or ground level installed, gas heating/electric cool ...

  • Bryant BRYANT 582A - page 24

    GUIDE SPECIFICA TIONS (cont) K. Electrical Requirements: All unit power wiring shall enter the unit cabinet at a single location. L. Motors: 1. Compressor motors shall be of the refrigerant-cooled type with line-break thermal and current overload protection. 2. All fan motors shall have permanently lubricated bear- ings, and inherent, automatic res ...

Fabricante Bryant Categoría Heating System

Los documentos del dispositivo Bryant BRYANT 582A que obtenemos del fabricante se pueden dividir en varios grupos. Entre ellos están::
- dibujos técnicos Bryant
- manuales de instrucciones BRYANT 582A
- hojas de producto Bryant
- folletos informativos
- o etiquetas energéticas Bryant BRYANT 582A
Todos son importantes, pero lo más importante desde el punto de vista del usuario de un dispositivo lo encontraremos en el manual de instrucciones Bryant BRYANT 582A.

Un conjunto de documentos determinado como manual de instrucciones se divide también en tipos más detallados, tales como: instrucciones de montaje Bryant BRYANT 582A, instrucciones de servicio, instrucciones cortas o instrucciones de usuario Bryant BRYANT 582A. Dependiendo de la situación debes buscar el documento que necesitas. En nuestra página puedes consultar el manual de instrucciones más popular del producto Bryant BRYANT 582A.

Manuales de instrucciones parecidos

El manual de instrucciones del dispositivo Bryant BRYANT 582A, ¿cómo debería ser?
El manual de instrucciones, también determinado como el manual de usuario o simplemente instrucciones, es un documento técnico que tiene como objetivo ayudar a los usuarios a utilizar Bryant BRYANT 582A. Las instrucciones normalmente las realiza un escritor técnico pero en un lenguaje comprensible para todos los usuarios de Bryant BRYANT 582A.

El manual de instrucciones completo de Bryant debe contener unos elementos básicos. Una parte de ellos es menos importante, como por ejemplo: la portada / la página principal o las páginas de autor. Sin embargo, lo demás debe facilitarnos la información más importante desde el punto de vista del usuario.

1. Introducción y pistas sobre cómo orientarse con el manual Bryant BRYANT 582A - Al principio de cada manual se deben encontrar las indicaciones acerca de la manera de usar un manual de instrucciones. Debe contener información sobre dónde encontrar el índice Bryant BRYANT 582A, preguntas frecuentes o problemas más comunes – son los apartados más buscados por los usuarios de cada manual de instrucciones.
2. Índice - listados de todos los consejos acerca de Bryant BRYANT 582A que encontraremos en el documento
3. Consejos de uso de las funciones básicas del dispositivo Bryant BRYANT 582A - que deben facilitarnos los primeros pasos durante el uso de Bryant BRYANT 582A
4. Troubleshooting - una secuencia sistematizada de acciones que nos ayudará a diagnosticar los problemas más importantes con Bryant BRYANT 582A
5. FAQ - las preguntas frecuentes
6. Datos de contacto Información acerca de cómo encontrar los datos de contacto del fabricante / servicio de Bryant BRYANT 582A en cada país si no somos capaces de solucionar el problema por nuestra cuenta.

¿Tienes una pregunta acerca de Bryant BRYANT 582A?

Utiliza el formulario que se encuentra abajo

Si con la ayuda del manual de instrucciones encontrado no has podido solucionar tu problema con Bryant BRYANT 582A, haz una pregunta utilizando el formulario que se encuentra abajo. Si alguno de los usuarios ha tenido un problema parecido con Bryant BRYANT 582A probablemente compartirá una forma de solucionarlo.

Copia el texto de la imagen

Comentarios (0)