    1 © 201 1 Emerson Climate T echnologies Printed in the U.S.A. AE8-1385 Application Enginee ring BULLE TIN Application Enginee ring BULLE TIN Safety Safety Instructions ................................................................. 2 Safety Icon Explanation ........................................................ 2 Instructions Pertaining to Ris ...

  • Emerson AE8-1385 - page 2

    2 © 201 1 Emerson Climate T echnologies Printed in the U.S.A. AE8-1385 Application Enginee ring BULLE TIN Safety Instructions Copeland Scroll ® compressors with CoreSense ™ Diagnostics technology are manufactured according to the latest U.S. and European Safety Standards. Particular emphasis has been placed on the user's safety . Safey ico ...

  • Emerson AE8-1385 - page 3

    3 © 201 1 Emerson Climate T echnologies Printed in the U.S.A. AE8-1385 Application Enginee ring BULLE TIN ELECTRICAL SHOCK HAZARD • Disconnect and lock out power before servicing. • Discharge all capacitors before servicing. • Use compressor with grounded system only . • Molded electrical plug must be used when required. • Refer to origi ...

  • Emerson AE8-1385 - page 4

    4 © 201 1 Emerson Climate T echnologies Printed in the U.S.A. AE8-1385 Application Enginee ring BULLE TIN INTRODUCTION Overview CoreSense ™ Diagnostics is a breakthrough innovation for troubleshooting residential air conditioning and heat pump systems. The CoreSense Diagnostics module is easily installed in the unit electrical panel near the com ...

  • Emerson AE8-1385 - page 5

    5 © 201 1 Emerson Climate T echnologies Printed in the U.S.A. AE8-1385 Application Enginee ring BULLE TIN OPERA TION Compressor Protection The CoreSense Diagnostics module utilizes proprietary algorithms to protect the compressor and system from repeated trips of system pressure controls and the compressor internal overload. The protection termina ...

  • Emerson AE8-1385 - page 6

    6 © 201 1 Emerson Climate T echnologies Printed in the U.S.A. AE8-1385 Application Enginee ring BULLE TIN off. This event will cause a lockout of the compressor and indicates that the module is mis-wired or the contactor coil is shorted to ground. NOTICE Code 10 is not speci fi ed on the module label. Resetting Alert Codes When the CoreSense Diag ...

  • Emerson AE8-1385 - page 7

    7 © 201 1 Emerson Climate T echnologies Printed in the U.S.A. AE8-1385 Application Enginee ring BULLE TIN ALERT TRIP / LOCK POWER 1 Long Run Time 2 Compressor (Pressure) Trip 3 Pressure Switch Cycling 4 Locked Rotor 5 Compressor (Mod Run) Trip 6 Open Start Circuit 7 Open Run Circuit 8 Welded Contactor 9 Low Voltage DC SOL operating range: 18-28VDC ...

  • Emerson AE8-1385 - page 8

    8 © 201 1 Emerson Climate T echnologies Printed in the U.S.A. AE8-1385 Application Enginee ring BULLE TIN 2- S t a g e Th e rmo s tat I ndoor Uni t O utdoor Uni t C R Y1 Y2 C R L Y Y2 L DC So l en o i d S ole noi d CoreSense Hi gh / Low Pr essu re S wi t ch CC C o m p r esso r Conta c t or C R Y1 Y2 L C R Y1 Y2 L Prot Figure 4 Wiring Diagram ...

  • Emerson AE8-1385 - page 9

    9 © 201 1 Emerson Climate T echnologies Printed in the U.S.A. AE8-1385 Application Enginee ring BULLE TIN Alert Code Alert Condition Lockout Level Lockout Indication Normal Run Solid Green Normal operation, no trip. N/A N/A Code1 Y ellow Flash 1 Long run time. Compressor is running for more than 18 hours at full load. (Code1 is disabled in Heat Pu ...

  • Emerson AE8-1385 - page 10

    10 © 201 1 Emerson Climate T echnologies Printed in the U.S.A. AE8-1385 Application Enginee ring BULLE TIN Status Description T roubleshooting Information Solid Green “RUN” Module has power and operating normally Supply voltage is present at module terminals Solid Red “TRIP” Thermostat demand signal Y is present, but the compressor is not ...

  • Emerson AE8-1385 - page 11

    11 © 201 1 Emerson Climate T echnologies Printed in the U.S.A. AE8-1385 Application Enginee ring BULLE TIN Y ellow “ALERT” Flash Code 4 Locked Rotor 1. Run capacitor has failed 2. Low line voltage (contact utility if voltage at disconnect is low) • Check wiring connections 3. Excessive liquid refrigerant in compressor 4. Compressor bearings ...

  • Emerson AE8-1385 - page 12

    12 © 201 1 Emerson Climate T echnologies Printed in the U.S.A. AE8-1385 Application Enginee ring BULLE TIN Red “LOCKOUT” Flash Code 5 Y ellow Off Compressor (Moderate Run) T rip Compressor is locked out after 4 consecutive or 10 total compressor (moderate run) trip events 1. Evaporator blower is not running • Check blower relay coil and cont ...

Fabricante Emerson Categoría Air Conditioner

Los documentos del dispositivo Emerson AE8-1385 que obtenemos del fabricante se pueden dividir en varios grupos. Entre ellos están::
- dibujos técnicos Emerson
- manuales de instrucciones AE8-1385
- hojas de producto Emerson
- folletos informativos
- o etiquetas energéticas Emerson AE8-1385
Todos son importantes, pero lo más importante desde el punto de vista del usuario de un dispositivo lo encontraremos en el manual de instrucciones Emerson AE8-1385.

Un conjunto de documentos determinado como manual de instrucciones se divide también en tipos más detallados, tales como: instrucciones de montaje Emerson AE8-1385, instrucciones de servicio, instrucciones cortas o instrucciones de usuario Emerson AE8-1385. Dependiendo de la situación debes buscar el documento que necesitas. En nuestra página puedes consultar el manual de instrucciones más popular del producto Emerson AE8-1385.

Manuales de instrucciones parecidos

El manual de instrucciones del dispositivo Emerson AE8-1385, ¿cómo debería ser?
El manual de instrucciones, también determinado como el manual de usuario o simplemente instrucciones, es un documento técnico que tiene como objetivo ayudar a los usuarios a utilizar Emerson AE8-1385. Las instrucciones normalmente las realiza un escritor técnico pero en un lenguaje comprensible para todos los usuarios de Emerson AE8-1385.

El manual de instrucciones completo de Emerson debe contener unos elementos básicos. Una parte de ellos es menos importante, como por ejemplo: la portada / la página principal o las páginas de autor. Sin embargo, lo demás debe facilitarnos la información más importante desde el punto de vista del usuario.

1. Introducción y pistas sobre cómo orientarse con el manual Emerson AE8-1385 - Al principio de cada manual se deben encontrar las indicaciones acerca de la manera de usar un manual de instrucciones. Debe contener información sobre dónde encontrar el índice Emerson AE8-1385, preguntas frecuentes o problemas más comunes – son los apartados más buscados por los usuarios de cada manual de instrucciones.
2. Índice - listados de todos los consejos acerca de Emerson AE8-1385 que encontraremos en el documento
3. Consejos de uso de las funciones básicas del dispositivo Emerson AE8-1385 - que deben facilitarnos los primeros pasos durante el uso de Emerson AE8-1385
4. Troubleshooting - una secuencia sistematizada de acciones que nos ayudará a diagnosticar los problemas más importantes con Emerson AE8-1385
5. FAQ - las preguntas frecuentes
6. Datos de contacto Información acerca de cómo encontrar los datos de contacto del fabricante / servicio de Emerson AE8-1385 en cada país si no somos capaces de solucionar el problema por nuestra cuenta.

¿Tienes una pregunta acerca de Emerson AE8-1385?

Utiliza el formulario que se encuentra abajo

Si con la ayuda del manual de instrucciones encontrado no has podido solucionar tu problema con Emerson AE8-1385, haz una pregunta utilizando el formulario que se encuentra abajo. Si alguno de los usuarios ha tenido un problema parecido con Emerson AE8-1385 probablemente compartirá una forma de solucionarlo.

Copia el texto de la imagen

Comentarios (0)