    036-21342-002 Rev. E (0505) FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE ® TECHNICAL GUIDE STEAL TH SPLIT -SYSTEM HEAT PUMP 15 SEER MODELS: E4TS 030 THRU 060 (2.5 THRU 5 NOMINAL T ONS) Due to continuous produc t improvement, specifi c tions are subject to chan ge without notice. Visit us on the web at ww w .york.com f or the ...

  • York E4TS030 THRU 060 - page 2

    036-21342-002 Rev. E (0505 ) 2 Unitary Products Group SYSTEM OPERA TION This heat pump model is equippe d with both Y orkGuard V heat pump control and TS compressor control. The interface control 6CF board is used to bypass the first stage of heat when the outdoor temperature falls below ce rtain tempera- tures. The TS control board is used only to ...

  • York E4TS030 THRU 060 - page 3

    036-21342-002 Rev. E (0505) Unitary Products Group 3 Physical and Electrical Dat a MODEL E4TS030 E4TS036 E4TS048 E4TS060 UNIT SUPPL Y VOL T AGE 208/230-1-60 NORMAL VOL T AGE RANGE 1 1. Rated in accordance with ARI S tandard 1 10, utilizaton range “A”. 187 to 252 MIN. CIRCUIT AMP ACITY 14.8 18.3 28.0 34.4 MAX. OVERCURRENT DEVICE AMPS 2 2. Dual e ...

  • York E4TS030 THRU 060 - page 4

    036-21342-002 Rev. E (0505 ) 4 Unitary Products Group 1. Unit factory charge listed on the unit nameplate include s re frigerant for the condensor , the smallest evaporator and for 15 f eet of interconnecting line tubing. 2. V erify the TXV kit and the additional charge required for the s pecific evaporator coil in the system using the table above. ...

  • York E4TS030 THRU 060 - page 5

    036-21342-002 Rev. E (0505) Unitary Products Group 5 COOLING CAP ACITY - V ariable S peed Air Handler UNIT MODEL N1VS AIR HANDLER COIL MODEL 1 1. G2FD coils available with a factory installed horizontal drain pan. See price pages for specific model number . COOLING MODEL ELECTRIC HEA T KW 2 2. Single phase units require single phase 2HK heaters. W ...

  • York E4TS030 THRU 060 - page 6

    036-21342-002 Rev. E (0505 ) 6 Unitary Products Group E4TS036 P1XDB12V 17 G2F D046S17 1 690 20000 15200 14. 0 12.4 2 1220 35600 25800 10.8 P1XUB12V 17 G2FD046S17 1 660 19800 15000 14.0 12.5 2 1200 35400 25600 1 1.0 G1UA048S17 1 660 19800 15000 14. 0 12.5 2 1200 35400 25600 1 1.0 G1F A048S17 1 660 19800 15000 14.0 12.5 2 1200 35400 25600 1 1.0 P1DUB ...

  • York E4TS030 THRU 060 - page 7

    036-21342-002 Rev. E (0505) Unitary Products Group 7 E4TS048 P1XUC16V 21 G1UA060S21 1 880 23800 17600 14.0 12.6 2 1600 47000 33800 10.8 G1UA060S21 1 880 23800 17600 14.0 12.6 2 1600 47000 33800 10.8 P1DUC20V 21 G1UA060S21 1 900 24200 18000 14 .0 12.6 2 1610 47500 34200 10.9 G1F A060S21 1 900 24200 18000 14.0 12.6 2 1610 47500 34200 10.9 P1XUC20V 21 ...

  • York E4TS030 THRU 060 - page 8

    036-21342-002 Rev. E (0505 ) 8 Unitary Products Group HEA TING CAP ACITY - V ari able Spe ed Air Handler UNIT MODEL N1VS AIR HANDLER COIL MODEL 1 1. G2FD coils available with a factory installed horizontal drain pan. See price pages for specific model number . HEA TING MODEL ELECTRIC HEA T KW 2 2. Single phase units require single phase 2HK heaters ...

  • York E4TS030 THRU 060 - page 9

    036-21342-002 Rev. E (0505) Unitary Products Group 9 HEA TING CAP ACITY - V ariable Speed Furnace UNIT MODEL V ARIABLE SPEED FURNACE MODEL WC O I L M O D E L HEA TING ST AGE (# CYL) RA TED CFM NET MBH 1,2 HSPF 3 COP 4 @ 47 F 47 OD 17 OD E4TS030 P1XDB12V075 17 G2FD046S17 1 580 12800 - - 3.58 2 580 24000 14000 8.3 3.38 2 1040 26200 15200 8.6 3.56 P1X ...

  • York E4TS030 THRU 060 - page 10

    036-21342-002 Rev. E (0505 ) 10 Unitary Products Group E4TS036 P1DUB16V080 17 G2FD046S17 1 650 17000 - - 3.54 2 650 31000 18400 8.0 3.30 2 1200 34600 20600 8.4 3.56 G1UA048S17 1 650 17200 - - 3.58 2 650 31400 18600 8.0 3.32 2 1200 35000 20800 8.4 3.58 G1F A048S17 1 650 17200 - - 3.58 2 650 31400 18600 8.0 3.32 2 1200 35000 20800 8.4 3.58 P1XUC16V07 ...

  • York E4TS030 THRU 060 - page 11

    036-21342-002 Rev. E (0505) Unitary Products Group 11 E4TS036 P1XUC20V095 21 G1UA048S21 1 625 16600 - - 3.48 2 625 31800 18800 7.9 3.34 2 1200 35400 21000 8 .3 3.60 G1F A048S21 1 625 16600 - - 3.48 2 625 31800 18800 7.9 3.34 2 1200 35400 21000 8 .3 3.60 G2FD048S21 1 625 16800 - - 3.52 2 625 32000 19000 8.0 3.38 2 1200 35600 21200 8 .4 3.64 G1UA060S ...

  • York E4TS030 THRU 060 - page 12

    036-21342-002 Rev. E (0505 ) 12 Unitary Products Group ACCESSORIES Refer to Price Manual for specific model numbers. TXV Kit - Factory specified and required for p roper unit per- formance. E4TS030 = 1 TV0701 E4TS036 = 1 TV0702 E4TS048 = 1 TV0703 E4TS060 = 1 TV0703 Room Thermostat - Matching 2-S tage cooling thermostats are available to provide fea ...

  • York E4TS030 THRU 060 - page 13

    036-21342-002 Rev. E (0505) Unitary Products Group 13 Multipliers for determining th e performance with other indoor sections . HIGH CFM LOW CFM NOTE: KW RA TING IS FO R OUTDOOR AND INDOOR UNITS. COOLING PERFORMANCE DA T A E4TS030S06A WITH N1VSC1606 / G2FD048S21 - HIGH CFM 2-CYLINDER OPERA TION CONDENSER ENTERING AIR TEMPERA TURE ID CFM 980 1065 12 ...

  • York E4TS030 THRU 060 - page 14

    036-21342-002 Rev. E (0505 ) 14 Unitary Products Group Multipliers for determining th e performance with other indoor sections . HIGH CFM NOTE: KW RA TING I S FOR OUTDOOR AND INDOOR UNITS. COOLING PERFORMANCE DA T A E4TS036S06A WITH N1VSC1606 / G2FD048S21 - HIGH CFM 2-CYLINDER OPERA TION CONDENSER ENTERING AIR TEMPERA TURE ID CFM 1000 1 185 1350 ID ...

  • York E4TS030 THRU 060 - page 15

    036-21342-002 Rev. E (0505) Unitary Products Group 15 Multipliers for determining th e performance with other indoor sections . LOW CFM NOTE: KW RA TING IS FO R OUTDOOR AND INDOOR UNITS. COOLING PERFORMANCE DA T A E4TS036S06A WITH N1VSC1606 / G2FD048S21 - LOW CFM 1-CYLINDER OPERA TION CONDENSER ENTERING A IR TEMPERA TURE ID CFM 680 770 860 ID DB (? ...

  • York E4TS030 THRU 060 - page 16

    036-21342-002 Rev. E (0505 ) 16 Unitary Products Group Multipliers for determining th e performance with other indoor sections . HIGH CFM LOW CFM NOTE: KW RA TING I S FOR OUTDOOR AND INDOOR UNITS. COOLING PERFORMANCE DA T A E4TS048S06A WITH N1VSD2006 / G2FD060S24 - HIGH CFM 2-CYLINDER OPERA TION CONDENSER ENTERING AIR TEMPERA TURE ID CFM 1420 1600 ...

  • York E4TS030 THRU 060 - page 17

    036-21342-002 Rev. E (0505) Unitary Products Group 17 Multipliers for determining th e performance with other indoor sections . HIGH CFM LOW CFM NOTE: KW RA TING IS FO R OUTDOOR AND INDOOR UNITS. COOLING PERFORMANCE DA T A E4TS060S06A WITH N1VSD2006 / G2FD061S24 - HIGH CFM 2-CYLINDER OPERA TION CONDENSER ENTERING A IR TEMPERA TURE ID CFM 1540 1860 ...

  • York E4TS030 THRU 060 - page 18

    036-21342-002 Rev. E (0505 ) 18 Unitary Products Group For notes see Page 1 1. Multipliers for determining th e performance with other indoor sections . 2-CYLINDER OPERA TION 1-CYLINDER OPERA TION NOTE: KW RA TING I S FOR OUTDOOR AND INDOOR UNITS. HEA TING PERFORMANCE DA T A E4TS030S06A WITH N1VSC1606 / G2FD048S21 - HIGH CFM 2-CYLINDER OPERA TION I ...

  • York E4TS030 THRU 060 - page 19

    036-21342-002 Rev. E (0505) Unitary Products Group 19 For notes see Page 1 1. Multipliers for determining th e performance with other indoor sections . 2-CYLINDER OPERA TION NOTE: KW RA TING IS FO R OUTDOOR AND INDOOR UNITS. HEA TING PERFORMANCE DA T A E4TS036S06A WITH N1VSC1606 / G2FD048S21 - HIGH CFM 2-CYLINDER OPERA TION ID CFM 1000 1 185 1350 O ...

  • York E4TS030 THRU 060 - page 20

    036-21342-002 Rev. E (0505 ) 20 Unitary Products Group For notes see Page 1 1. Multipliers for determining th e performance with other indoor sections . 1-CYLINDER OPERA TION NOTE: KW RA TING I S FOR OUTDOOR AND INDOOR UNITS. HEA TING PERFORMANCE DA T A E4TS036S06A WITH N1VSC1606 / G2FD048S21 - LOW CFM 1-CYLINDER OPERA TION ID CFM 670 770 860 OD DB ...

  • York E4TS030 THRU 060 - page 21

    036-21342-002 Rev. E (0505) Unitary Products Group 21 For notes see Page 1 1. Multipliers for determining th e performance with other indoor sections . 2-CYLINDER OPERA TION 1-CYLINDER OPERA TION NOTE: KW RA TING IS FO R OUTDOOR AND INDOOR UNITS. HEA TING PERFORMANCE DA T A E4TS048S06A WITH N1VSD2006 / G2FD060S24 - HIGH CFM 2-CYLINDER OPERA TION ID ...

  • York E4TS030 THRU 060 - page 22

    036-21342-002 Rev. E (0505 ) 22 Unitary Products Group For notes see Page 1 1. Multipliers for determining th e performance with other indoor sections . 2-CYLINDER OPERA TION 1-CYLINDER OPERA TION NOTE: KW RA TING I S FOR OUTDOOR AND INDOOR UNITS. HEA TING PERFORMANCE DA T A E4TS060S06A WITH N1VSD2006 / G2FD061S21 - HIGH CFM 2-CYLINDER OPERA TION I ...

  • York E4TS030 THRU 060 - page 23

    036-21342-002 Rev. E (0505) Unitary Products Group 23 MA TCHING INDOOR COMPONENTS G1UA UPFLOW G2FD* MUL TI-POSITION (UPFLOW , HORIZONT AL AND DOWNFLOW) G1F A FULL CASED AIR HANDLERS - FOR NON-FURNACE APPLICA TIONS N1VS MODULAR BLOWER (UPFLOW , HORIZONT AL AND DOWNFLOW) F2FV F AN COIL UNITS (UPFLOW , HORIZONT AL) G2FD COIL ...

  • York E4TS030 THRU 060 - page 24

    Subject to change without notice. Printed in U .S.A. 036-21342-002 Rev. E (0505) Copyright © by Y ork International Corp. 2005. All rights reser ved. Supersedes: 036-21342-002 Rev . D (1 104) Unitary 5005 Norman Product Y ork OK Group Drive 73069 NOTES ...

Fabricante York Categoría Heat Pump

Los documentos del dispositivo York E4TS030 THRU 060 que obtenemos del fabricante se pueden dividir en varios grupos. Entre ellos están::
- dibujos técnicos York
- manuales de instrucciones E4TS030 THRU 060
- hojas de producto York
- folletos informativos
- o etiquetas energéticas York E4TS030 THRU 060
Todos son importantes, pero lo más importante desde el punto de vista del usuario de un dispositivo lo encontraremos en el manual de instrucciones York E4TS030 THRU 060.

Un conjunto de documentos determinado como manual de instrucciones se divide también en tipos más detallados, tales como: instrucciones de montaje York E4TS030 THRU 060, instrucciones de servicio, instrucciones cortas o instrucciones de usuario York E4TS030 THRU 060. Dependiendo de la situación debes buscar el documento que necesitas. En nuestra página puedes consultar el manual de instrucciones más popular del producto York E4TS030 THRU 060.

Manuales de instrucciones parecidos

El manual de instrucciones del dispositivo York E4TS030 THRU 060, ¿cómo debería ser?
El manual de instrucciones, también determinado como el manual de usuario o simplemente instrucciones, es un documento técnico que tiene como objetivo ayudar a los usuarios a utilizar York E4TS030 THRU 060. Las instrucciones normalmente las realiza un escritor técnico pero en un lenguaje comprensible para todos los usuarios de York E4TS030 THRU 060.

El manual de instrucciones completo de York debe contener unos elementos básicos. Una parte de ellos es menos importante, como por ejemplo: la portada / la página principal o las páginas de autor. Sin embargo, lo demás debe facilitarnos la información más importante desde el punto de vista del usuario.

1. Introducción y pistas sobre cómo orientarse con el manual York E4TS030 THRU 060 - Al principio de cada manual se deben encontrar las indicaciones acerca de la manera de usar un manual de instrucciones. Debe contener información sobre dónde encontrar el índice York E4TS030 THRU 060, preguntas frecuentes o problemas más comunes – son los apartados más buscados por los usuarios de cada manual de instrucciones.
2. Índice - listados de todos los consejos acerca de York E4TS030 THRU 060 que encontraremos en el documento
3. Consejos de uso de las funciones básicas del dispositivo York E4TS030 THRU 060 - que deben facilitarnos los primeros pasos durante el uso de York E4TS030 THRU 060
4. Troubleshooting - una secuencia sistematizada de acciones que nos ayudará a diagnosticar los problemas más importantes con York E4TS030 THRU 060
5. FAQ - las preguntas frecuentes
6. Datos de contacto Información acerca de cómo encontrar los datos de contacto del fabricante / servicio de York E4TS030 THRU 060 en cada país si no somos capaces de solucionar el problema por nuestra cuenta.

¿Tienes una pregunta acerca de York E4TS030 THRU 060?

Utiliza el formulario que se encuentra abajo

Si con la ayuda del manual de instrucciones encontrado no has podido solucionar tu problema con York E4TS030 THRU 060, haz una pregunta utilizando el formulario que se encuentra abajo. Si alguno de los usuarios ha tenido un problema parecido con York E4TS030 THRU 060 probablemente compartirá una forma de solucionarlo.

Copia el texto de la imagen

Comentarios (0)