    UNVENTED (VENT -FREE) GAS COMP A CT CLASSIC HEARTH ® DU AL BURNER FIREPLA CE OWNER’S OPERA TION AND INST ALLA TION MANU AL For more information, visit www .fmiproducts.com REMOTE-READ Y MODELS CDCFPRB , CDCFNRB, CDCFPRB-1, CDCFNRB-1 Shown with Optional Cabinet Mantel/Hearth Base Accessory W ARNING: If the information in this manual is not  ...

  • FMI CDCFPRB-1 - page 2

    www .fmiproducts.com 124979-01C 2 W ARNING: Improper   alteration, service or maintenance can cause     -   for correct installa ...

  • FMI CDCFPRB-1 - page 3

    www .fmiproducts.com 124979-01C 3 DANGER: Carbon monoxide     Early signs of carbon monoxid e poisoning resemble the u, with headaches, dizziness or nausea. If you have these signs, the ...

  • FMI CDCFPRB-1 - page 4

    www .fmiproducts.com 124979-01C 4 PRODUCT IDENTIFICA TION Ignitor Button Screen Fireplace Cabinet Log Control Knob Figure 1 - V ent-Free Compact Dual Flame Fireplace Hood Fireplace Cabinet Logs Ignitor Button Remote Control (Optional) Control Knob Hood OPTIONAL REMO TE CONTROL A CCESSORIES SAFETY Continued 5. Do not use this replace as a wood-bu ...

  • FMI CDCFPRB-1 - page 5

    www .fmiproducts.com 124979-01C 5 LOCAL CODES Install and use replace with care. Follow all local codes. In the absence of local codes, use the latest edition of The National Fuel Gas Code ANSI Z223.1/NFP A 54 *. *Available from: American National Standards Institute, Inc. 1430 Broadway New Y ork, NY 10018 National Fire Protection Association, I ...

  • FMI CDCFPRB-1 - page 6

    www .fmiproducts.com 124979-01C 6 strip and caulk around windows and doors to keep the cold air out and the warm air in. During heating months, home owners want their homes as airtight as possible. While it is good to make your home energy efcient, your home needs to breathe. Fresh air must enter your home. All fuel-burning ap- pliances need fre ...

  • FMI CDCFPRB-1 - page 7

    www .fmiproducts.com 124979-01C 7 AIR FOR COMB USTION AND VENTILA TION Continued All spaces in homes fall into one of the three following ventilation classications: 1. Unusually Tight Construction 2. Unconned Space 3. Conned Space The infor matio n on pages 6 throu gh 8 will help you classif y your space and provide adequa te ventilation. ...

  • FMI CDCFPRB-1 - page 8

    www .fmiproducts.com 124979-01C 8 AIR FOR COMB USTION AND VENTILA TION Continued The space in the previous example is a conned space because the actual Btu/Hr used is more than the maximum Btu/Hr the space can sup- port. Y ou must provide additional fresh air . Y our options are as follows: A. Rework worksheet, adding the space of an adjoining r ...

  • FMI CDCFPRB-1 - page 9

    www .fmiproducts.com 124979-01C 9 INST ALLA TION IMPORT ANT : Vent-free replaces add mois - ture to the air. Although this is benecial, installing replace in rooms without enough ventilation air may cause mildew to form from too much moisture. See Air for Combustion and V entilation, page 6. No te : Y our re pla ce is de si gn ed to be ...

  • FMI CDCFPRB-1 - page 10

    www .fmiproducts.com 124979-01C 10  W ARNING: Maintain the minimum clearances shown             ? ...

  • FMI CDCFPRB-1 - page 11

    www .fmiproducts.com 124979-01C 11 INST ALLA TION Continued 3. Instal l gas piping to repl ace loca tion . This installation includes an approved exible gas line (if allowed by local codes) after the equipment shutoff valve. The exible gas line must be the last item installed on the gas piping. 4. If you have not installed hood, follow ins ...

  • FMI CDCFPRB-1 - page 12

    www .fmiproducts.com 124979-01C 12 15" 18" 21" 23" 2 1 / 2 " 6" 8" 10" Note: A ll vertical measurements are from top of fireplace opening to bottom of mantel shelf. All measurements are in inches. W ARNING: Do not allow any combustible/noncombustible  ? ...

  • FMI CDCFPRB-1 - page 13

    www .fmiproducts.com 124979-01C 13 Inst allati on must include an equipmen t shut off val ve, uni on and plu gged 1/8" NPT tap. Loc ate NPT tap within reach for test gauge hook up. NPT tap must be upstream from heater (see Figure 14). IMPORT ANT : Install equipment shutoff valve in an accessi ble location. The equipment shutoff valve is for tu ...

  • FMI CDCFPRB-1 - page 14

    www .fmiproducts.com 124979-01C 14 INST ALLA TION Continued We recommend that you install a sediment trap in supply line as shown in Figure 14, page 13. Locate sediment trap where it is within reach for cleaning. Install in piping system between fuel supply and heater . Locate sedi - ment trap where trapped matter is not likely to freeze. A sedimen ...

  • FMI CDCFPRB-1 - page 15

    www .fmiproducts.com 124979-01C 15 INST ALLA TION Continued CAUTION: Make sure exter-               ? ...

  • FMI CDCFPRB-1 - page 16

    www .fmiproducts.com 124979-01C 16      W ARNING: Read and fol -    Installation should be done by   ...

  • FMI CDCFPRB-1 - page 17

    www .fmiproducts.com 124979-01C 17 INST ALLA TION Continued   W ARNING: Read and fol -    Installation should be done by   ? ...

  • FMI CDCFPRB-1 - page 18

    www .fmiproducts.com 124979-01C 18                           ? ...

  • FMI CDCFPRB-1 - page 19

    www .fmiproducts.com 124979-01C 19 • If control knob does not pop out when released, contact a qualified service person or gas supplier for repairs. Note: If pilot goes out, repeat steps 4 through 8. 8. Slig ht ly pus h in and turn con tr ol kn ob coun - terclockwise to the ON position. 9. Set ame adjustment knob to any level between HI and LO ...

  • FMI CDCFPRB-1 - page 20

    www .fmiproducts.com 124979-01C 20 INSPECTING B URNERS Check pilot ame pattern and burner ame patterns often.    Figure 29 shows a correct pilot ame pattern. Figure 30 shows an incorrect pilot ame pat - tern. The incorrect pilot ame is not touching the thermocouple. This will c ...

  • FMI CDCFPRB-1 - page 21

    www .fmiproducts.com 124979-01C 21 We also recommend that you keep the burner tube and pilot assemb ly clean and free of dust and dirt. T o clean these parts we recommend using compressed air no greater than 30 PSI. Y our local computer store, hardware store or home center may carry compressed air in a can. If using compressed air in a can, please ...

  • FMI CDCFPRB-1 - page 22

    www .fmiproducts.com 124979-01C 22 TROUBLESHOO TING                  ? ...

  • FMI CDCFPRB-1 - page 23

    www .fmiproducts.com 124979-01C 23  1 . Control knob not fully pressed in 2. Contro l knob not pressed in long enough 3. Safety inter lock syste m has been triggered 4. Equi pme nt shuto f f valv e not fully open 5 . Pilot flame not touching thermocouple, which al - lows thermocouple to cool, causing pilot ...

  • FMI CDCFPRB-1 - page 24

    www .fmiproducts.com 124979-01C 24 TROUBLESHOO TING Continued  1. Residues from manufac- turing processes and log curing 2. Not enough air 3. Gas regulator defective 1. Turning control knob to HI position when burner is cold 2. Air in gas line 3. Air passageways on re - place blocked 4. Dirty or partiall ...

  • FMI CDCFPRB-1 - page 25

    www .fmiproducts.com 124979-01C 25 TROUBLESHOO TING Continued          ...

  • FMI CDCFPRB-1 - page 26

    www .fmiproducts.com 124979-01C 26 8 8 14 14 14 14 14 14 14 1 9 10 10 16 17 10 6 3 1 1 12 13 1 1 15 16 18 16 16 16 16 16 16 2 5 16 16 16 16 7 4 19 P ARTS  ...

  • FMI CDCFPRB-1 - page 27

    www .fmiproducts.com 124979-01C 27        1 ** Outer Casing T op • 1 2 ** Bafe • 1 3 ** Outer Casing • 1 4 104281-02 Firebox Hood • 1 5 ** Firebox T op • 1 6 ** Firebox Wrapper • 1 7 ** Outer Base • 1 8 102635-02 Front Left and Right Sides • ...

  • FMI CDCFPRB-1 - page 28

    www .fmiproducts.com 124979-01C 28 P ARTS   16 15 15 16 12 12 1 1 9 9 9 10 5 17 18 13 19 2 1 4 3 14 7 6 8 20 Natural Gas Only 9 21 22 ...

  • FMI CDCFPRB-1 - page 29

    www .fmiproducts.com 124979-01C 29 P ARTS REMOTE-READY MODELS This list contains replaceable parts used in your replace. When ordering parts, follow the instructions listed under Replacement Parts on page 30 of this manual.        1 1 1 1069-01 Dual Burner ...

  • FMI CDCFPRB-1 - page 30

    www .fmiproducts.com 124979-01C 30 SPECIFICA TIONS  • Rating (V ariable): 17,000/26,000 Btu/Hr • T ype Gas: Propane/LP • Ignition: Piezo • Manifold Pressure: 8" W .C. • Inlet Gas Pressure (in. of water): Max - 14" W .C., Min* - 1 1" W.C.  ...

  • FMI CDCFPRB-1 - page 31

    www .fmiproducts.com 124979-01C 31 ACCESSORIES THERMOST A T -CONTROLLED      Provides better heat distribu - tion. Makes replace more efcient. Automati - cally turns off and on as needed. CORNER MANTEL WITH FULL HEARTH BASE  ...

  • FMI CDCFPRB-1 - page 32

    124979-01 Rev . C 06/10 WARRANTY KEEP THIS WARRANTY FMI PRODUCTS, LL C LIMITED WARRANTIES  Standard Warranty: FMI PRODUCTS, LLC warrants this new product and any parts thereof to be free from defects in material and workmanship for a period of two (2) years from the date of rst purchase from an authorized deal ...

Fabricant FMI Catégorie Indoor Fireplace

Les documents que nous recevons du fabricant de l'appareilFMI CDCFPRB-1 peuvent être divisés en plusieurs groupes. Ceux-ci sont, entre autres:
- dessins techniques FMI
- manuels d’utilisations CDCFPRB-1
- fiches produit FMI
- dépliants
- ou étiquettes-énergie FMI CDCFPRB-1
Tous sont importants, mais les informations les plus importantes du point de vue de l'utilisation de l'appareil se trouvent dans le manuel d’utilisation FMI CDCFPRB-1.

Un groupe de documents appelé manuels d’utilisation est également divisé en types plus spécifiques, tels que: Manuels d’installation FMI CDCFPRB-1, manuels d’entretien, brefs manuels ou manuels de l’utilisateur FMI CDCFPRB-1. Selon vos besoins, vous devriez chercher le document dont vous avez besoin. Sur notre site, vous pouvez voir le manuel le plus populaire d’utilisation du produit FMI CDCFPRB-1.

Manuels d’utilsiation similaires

Manuel d’utilisation complet de l’appareil FMI CDCFPRB-1, quelle devrait-elle être?
Le manuel d’utilisation, également appelé le mode d’emploi, ou tout simplement le manuel, est un document technique destiné à aider à utiliser FMI CDCFPRB-1 par les utilisateurs. Des manuels sont généralement écrits par un rédacteur technique, mais dans un langage accessible à tous les utilisateurs FMI CDCFPRB-1.

Le manuel d’utilisation complet FMI, devrait inclure plusieurs éléments de base. Certains d'entre eux sont moins importants, tels que: la couverture / page de titre ou pages d'auteur. Cependant, la partie restante, devrait nous fournir des informations importantes du point de vue de l'utilisateur.

1. Introduction et des conseils sur la façon d'utiliser le manuel FMI CDCFPRB-1 - Au début de chaque manuel, nous devrions trouver des indices sur la façon d'utiliser le document. Il doit contenir des informations sur l'emplacement de la table des matières FMI CDCFPRB-1, FAQ ou des problèmes les plus fréquents - les points qui sont les plus souvent recherchés par les utilisateurs de chaque manuel
2. Table des matières - index de tous les conseils pour lFMI CDCFPRB-1 qui peuvent être trouvés dans le document courant
3. Conseils sur la façon d'utiliser les fonctions de base de l’appareil FMI CDCFPRB-1 - qui devraient nous aider dans les premières étapes lors de l'utilisation FMI CDCFPRB-1
4. Troubleshooting - séquence systématique des activités qui nous aideront à diagnostiquer et ensuite résoudre les principaux problèmes de FMI CDCFPRB-1
5. FAQ - questions fréquemment posées
6. Détails du contact Informations sur l'endroit où chercher le contact avec le fabricant / service FMI CDCFPRB-1 dans un pays donné, si le problème ne peut être résolu par nous-mêmes.

Avez-vous une question à propos de FMI CDCFPRB-1?

Utiliser le formulaire ci-dessous

Si vous n’avez pas résolu votre problème avec FMI CDCFPRB-1, avec l'aide du manuel que vous avez trouvé, posez une question en utilisant le formulaire ci-dessous. Si un utilisateur a eu un problème similaire avec FMI CDCFPRB-1 il est probable qu’il a envie de partager la façon de le résoudre.

Réécrire le texte de l'image

Commentaires (0)