Manuel d’utilisation Venmar 700 cfm

24 pages 2.17 mb
Télécharger

Aller à la page of 24

Summary
  • Venmar 700 cfm - page 1

    Light Commer cial Heat Recovery V entilators VB0002 VB0003 VB0001 600 cfm 700 cfm 1200 cfm Installation, Operation and Service Instructions 06/00 04597 ...

  • Venmar 700 cfm - page 2

    Page 2 Contents 1 Safety Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 2 Installation 2.1 Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 2.2 Mounting Location Requirements . . . . . . . . . . . . . . . . . . . . ...

  • Venmar 700 cfm - page 3

    Page 3 1 Safety Considerations Hazards may exist within this equipment because it contains electrical and powerful moving components. Only qualified service personnel should install or service this equipment. Untrained personnel can perform basic maintenance such as maintaining filters. Observe precautions marked in literature and on labels attache ...

  • Venmar 700 cfm - page 4

    Page 4 The supply and exhaust ducts connected to outside, as well as any ducts passing through an unconditioned space, must have a minimum insulation value of R5. In addition, a continuous integral vapor barrier over the duct insulation must be used. Air balancing dampers are recommended for both supply and exhaust ducts to allow for adjustment of ...

  • Venmar 700 cfm - page 5

    Page 5 2.8 Electrical Connections Power A terminal block and strain relief bushing or a junction box is provided for line voltage to make the necessary power connections. The electrical requirements are as follows: Control Box Access For Low Speed Setting (600 cfm/1200 cfm only) Disconnect power to the unit. Remove the four screws securing the cove ...

  • Venmar 700 cfm - page 6

    Page 6 Recirculation Defr ost Module (Optional - Factory Installed) The Recirculation Defrost Module is only available with the 600 cfm and 1200 cfm units. The defrost cycle is electronically controlled in response to the outside temperature 23°F to -22°F (-5°C to -30°C). On a call for defrost, the supply air damper in the recirculation module ...

  • Venmar 700 cfm - page 7

    Page 7 4.2 Balancing Procedur e Before proceeding with balancing, all windows, overhead doors and walk-in doors should be closed and exhaust systems should be turned off. The connections between the flow stations and the ducts must be sealed with tape. Mount the magnehelic gauge in a convenient location where it is level and will not vibrate or be ...

  • Venmar 700 cfm - page 8

    Page 8 Allow the heat recovery core to soak for three hours in warm water and mild soap. Rinse under a heavy stream of water . Fans Blower wheels and fan housing should be checked for dirt build-up. If they appear dirty , it may be necessary to remove the blower assembly and then vacuum the dust out through the fan mouth. See the following page for ...

  • Venmar 700 cfm - page 9

    Page 9 3/8" (10mm) Threaded Rod (Supplied by others) Rubber Vibration Isolater Cabinet Mounted U Channel Wooden Curb (Supplied by others) Bolt to Floor Space must be left to allow connection of drain lines with adequate slope for drainage Dry Contacts Dry Contacts VD0003A Space must be left to allow connection of drain lines with adequate slop ...

  • Venmar 700 cfm - page 10

    Page 10 8.000" [203] 4.000" [102] 8.000" [203] 3.535" [90] 4.000" [102] 28.005" [71 1] 14.000" [356] 5.859" [149] 13.375" [340] 23.500" [597] 2.750" [70] 14.000" [356] 6.500" [165] 8.000" [203] 8.000" [203] 14.103" [358] 7.705" [196] 4.000" [102] 24.500" ...

  • Venmar 700 cfm - page 11

    28.12" [714] 14.00" [356] 4.00" [102] 1.75" [44] 8.00" [203] 2.75" [70] 19.207" [488] 5.125" [130] Access Door Strap Mounting Location Drain Fitting NOTE: For units with the reversed door option, interior components will appear as a mirror image of the above diagram. 49.550" [1259] Line Power Control Box ...

  • Venmar 700 cfm - page 12

    Page 12 41.206" [1047] 40.326" [1024] 20.000" [508] 5.715" [145] 20.620" [524] 14.250" [362] 34.000" [864] 5.125" [130] 19.207" [488] 4.028" [102] 1 1.325" [288] 12.000" [305] 15.000" [381] 20.000" [508] 4.000" [102] 2.750" [70] 1 1.000" [279] 20.000" [508] 9. ...

  • Venmar 700 cfm - page 13

    Page 13 8.00" [203] 1.75" [44] 10.00" [254] 20.00" [508] 2.75" [70] Alimentation électrique Borniers 49.550" [1259] Localisation de la courroie de fixation Aspiration d’air frais Évacuation d’air vicié 5.125" [130] Noyau de récupération de chaleur Option de porte inversée Porte d’accès 15.00" [38 ...

  • Venmar 700 cfm - page 14

    Page 14 10.000" [254] Dimensions in [ ] are in millimeters Center of gravity Direction of airflow HRV700i LBS Kg 32.74 14.85 68.46 31.05 35.20 15.97 73.60 33.38 210.00 1.875" [48] EXHAUST AIR OPENING SUPPL Y AIR OPENING 20.750" [527] 8.000" [203] 10.750" [273] 7.500" [191] 10.605" [269] 12.104" [307] 2.157&qu ...

  • Venmar 700 cfm - page 15

    Page 15 Flow Measuring Station (FMS) Balancing Damper Canvas Vibration Isolator Min. 12" (305mm) Min. 30" (762mm) Reverse Door Option Exhaust Air From Building Fresh Air From Outside Min. 8" (203mm) (Optional) Canvas Vibration Isolator Min. 12" (305mm) VP0001A Min.12" (304mm) Flow Measuring Station (FMS) Balancing Damper (n ...

  • Venmar 700 cfm - page 16

    Page 16 T o Drain Copper or Plastic Pipe Plastic Drain Fittings Plastic Hose W ater T rap Coupler 3/4"NPT Note: All hose, pipe & couplers to be supplied by others TD i All hose, pipe, and couplers to be supplied by others. Plastic Hose W ater T rap 3/4" NPT T o Drain Copper or Plastic Pipe Plastic Drain Fitting Note: T o Drain Coupler ...

  • Venmar 700 cfm - page 17

    Page 17 WALL CONTROL CLASS 2 VOL T AGE Black OCCUPIED TIMER/ SENSOR F F LOW COMMON HIGH Red Green Y ellow NOTE: Connections are all dry contacts except wall control and 24V AC power supply . Use of 24V AC circuit requires isolating contacts (ex. thermostat) to prevent interconnection of Class 2 outputs. VE0002A W all Control JUMPER WALL CONTROL CLA ...

  • Venmar 700 cfm - page 18

    Page 18 JUMPER (factory installed) OCC. CONTROL (field installed) NSB Timer V enmar PN 1604128 1 M 234 5 JUMPER WALL CONTROL CLASS 2 VOL T AGE Black OCCUPIED TIMER/ SENSOR F F LOW COMMON HIGH Red Green Y ellow NOTE: Connections are all dry contacts except wall control and 24V AC power supply . Use of 24V AC circuit requires isolating contacts (ex. ...

  • Venmar 700 cfm - page 19

    Page 19 Control cover plate Control box Remote control access plate Remote wiring terminal block HRV Cabinet VE0001A R ed Low Speed (Red) Remove power before installing or removing JU1-F Extended Defrost Jumper 12 pin 2 pin Med Speed (Blue) Low T o Medium, move the fork connector: T o change the minimum speed setting from from here to here LOW SPEE ...

  • Venmar 700 cfm - page 20

    Page 20 Although the 600 cfm, 700 cfm and 1200 cfm models have good efficiencies, the supply air could be colder than the ambient room air . It is possible to eliminate the discomfort associated with this temperature difference by installing an electric duct heater . This will temper the air before it is distributed throughout the building. The tab ...

  • Venmar 700 cfm - page 21

    Page 21 Appendix H Wiring Diagram Wiring Diagram for 600 cfm unit INTERLOCK (FF) W ALL CONTROL BLACK VE0023A 48445 POWER CONTROL BOARD -t 8 9 10 11 12 13 14 T7 1 2 3 4 5 6 7 T7 BL BL G R Y BK J3 1 J3 2 J3 8 J3 7 J3 6 J3 9 W ALL CONTROL RED OCC./ UNOCC. REMOTE F AN COMMON AUTOTRANSFORMER AL TERNA TE WIRING FOR LOW SPEED AUTOTRANSFORMER OPTION INPUT ...

  • Venmar 700 cfm - page 22

    Page 22 Appendix H Continued Wiring Diagram Wiring Diagram for 700 cfm unit VE0024A J1 6 J1 9 J1 2 K7 J1 3 LO GND L1 NEUT 120VCA 60Hz COLOR CODE 110 VOL TS LOW VOL T AGE AND FIELD WIRE J1 8 1 2 3 4 5 6 7 T7 INTERLOCK (FF) W ALL CONTROL BLACK 8 9 10 11 12 13 14 T7 W ALL CONTROL RED OCC./ UNOCC. REMOTE F AN CONTROL BOX W ALL CONTROL GREEN W ALL CONTR ...

  • Venmar 700 cfm - page 23

    Page 23 Appendix H Continued Wiring Diagram Wiring Diagram for 1200 cfm unit INTERLOCK (FF) W ALL CONTROL BLACK VE0022A . . . . . . JU1 J4 2 1 A B C D E F G 1 2 3 4 5 6 7 8 9 J3 F F I OC OL Y R G B 4 7 6 9 48445 POWER CONTROL BOARD J1 3 2 1 8 1 2 3 J2 COMM. N/C N/O -t DEFROST TEMP . SENSOR 8 9 10 11 12 13 14 T7 1 2 3 4 5 6 7 T7 BL BL G R Y BK J3 1 ...

  • Venmar 700 cfm - page 24

    For technical assistance and warranty information, please call your local supplier . Appendix I T rouble Shooting SYMPTOMS POSSIBLE CAUSES SOLUTIONS Inside air is too dry Over ventilation - speed setting Adjust speed setting too high Dehumidistat setting is too low Set dehumidistat control in a higher position (if applicable) Persistent condensatio ...

Fabricant Venmar Catégorie Ventilation Hood

Les documents que nous recevons du fabricant de l'appareilVenmar 700 cfm peuvent être divisés en plusieurs groupes. Ceux-ci sont, entre autres:
- dessins techniques Venmar
- manuels d’utilisations 700 cfm
- fiches produit Venmar
- dépliants
- ou étiquettes-énergie Venmar 700 cfm
Tous sont importants, mais les informations les plus importantes du point de vue de l'utilisation de l'appareil se trouvent dans le manuel d’utilisation Venmar 700 cfm.

Un groupe de documents appelé manuels d’utilisation est également divisé en types plus spécifiques, tels que: Manuels d’installation Venmar 700 cfm, manuels d’entretien, brefs manuels ou manuels de l’utilisateur Venmar 700 cfm. Selon vos besoins, vous devriez chercher le document dont vous avez besoin. Sur notre site, vous pouvez voir le manuel le plus populaire d’utilisation du produit Venmar 700 cfm.

Manuels d’utilsiation similaires

Manuel d’utilisation complet de l’appareil Venmar 700 cfm, quelle devrait-elle être?
Le manuel d’utilisation, également appelé le mode d’emploi, ou tout simplement le manuel, est un document technique destiné à aider à utiliser Venmar 700 cfm par les utilisateurs. Des manuels sont généralement écrits par un rédacteur technique, mais dans un langage accessible à tous les utilisateurs Venmar 700 cfm.

Le manuel d’utilisation complet Venmar, devrait inclure plusieurs éléments de base. Certains d'entre eux sont moins importants, tels que: la couverture / page de titre ou pages d'auteur. Cependant, la partie restante, devrait nous fournir des informations importantes du point de vue de l'utilisateur.

1. Introduction et des conseils sur la façon d'utiliser le manuel Venmar 700 cfm - Au début de chaque manuel, nous devrions trouver des indices sur la façon d'utiliser le document. Il doit contenir des informations sur l'emplacement de la table des matières Venmar 700 cfm, FAQ ou des problèmes les plus fréquents - les points qui sont les plus souvent recherchés par les utilisateurs de chaque manuel
2. Table des matières - index de tous les conseils pour lVenmar 700 cfm qui peuvent être trouvés dans le document courant
3. Conseils sur la façon d'utiliser les fonctions de base de l’appareil Venmar 700 cfm - qui devraient nous aider dans les premières étapes lors de l'utilisation Venmar 700 cfm
4. Troubleshooting - séquence systématique des activités qui nous aideront à diagnostiquer et ensuite résoudre les principaux problèmes de Venmar 700 cfm
5. FAQ - questions fréquemment posées
6. Détails du contact Informations sur l'endroit où chercher le contact avec le fabricant / service Venmar 700 cfm dans un pays donné, si le problème ne peut être résolu par nous-mêmes.

Avez-vous une question à propos de Venmar 700 cfm?

Utiliser le formulaire ci-dessous

Si vous n’avez pas résolu votre problème avec Venmar 700 cfm, avec l'aide du manuel que vous avez trouvé, posez une question en utilisant le formulaire ci-dessous. Si un utilisateur a eu un problème similaire avec Venmar 700 cfm il est probable qu’il a envie de partager la façon de le résoudre.

Réécrire le texte de l'image

Commentaires (0)