    Installation, Start-Up and Service Instructions CONTENTS Page SAFETY CONSIDERA TIONS ...................1 BEFORE INST ALLA TION .....................1 - 3 Rigging ......................................1 Placing Unit .................................3 Mounting Unit ...............................3 Compressor Mounting ........................3 INST A ...

  • Carrier 38AKS028-044 - page 2

    T able 1A — Physical Data — English UNIT 38AKS 028 034 044 COMPRESSOR Reciprocating Semi-Hermetic No. ...T ype 1...06E9265 1...06E9275 1...06E9299 No. Cyls (ea)...Speed, Rpm (60/50 Hz) 6...1750/1460 Capacity Steps 3 Oil Charge*, Pt 20.0 20.0 19.0 Oil Pressure Switch (psi) Set Points — Cutout 6 6 2 Differential — Cut-in 14 Max. Crankcase Hea ...

  • Carrier 38AKS028-044 - page 3

    Placing Unit — There must be 4 ft (1220 mm) for ser- vice on all sides of unit, and a minimum of 8 ft (2440 mm) clear air space above unit. For multiple units, allow 8 ft (2440 mm) separation between units for airflow and service. Mounting Unit — When unit is in proper location, use of mounting holes in base rails is recommended for securing u ...

  • Carrier 38AKS028-044 - page 4

    Receiver — No receiver is provided with the unit; it is recommended that one not be used. Piping Procedure — Do not remove run-around pipe from suction and liquid line stubs until piping connections are ready to be made. Pass nitrogen or other inert gas through piping while brazing, to prevent formation of copper oxide. Install field-supplied ...

  • Carrier 38AKS028-044 - page 5

    T able 2A — Refrigerant Piping Sizes — 60 Hz SINGLE SUCTION RISERS UNIT 38AKS LENGTH OF INTERCONNECTING PIPING, FT (M) 16-25 (4.9-7.6) 26-50 (7.9-15.2) 51-75 (15.5-22.8) 76-100 (23.2-30.5) 101-200 (30.8-60.9) LSL S L S L S L S 028 7 ⁄ 8 1 5 ⁄ 8 7 ⁄ 8 2 1 ⁄ 8 * 7 ⁄ 8 2 1 ⁄ 8 * 7 ⁄ 8 2 1 ⁄ 8 * 7 ⁄ 8 2 1 ⁄ 8 * 034 7 ⁄ 8 2 1 ? ...

  • Carrier 38AKS028-044 - page 6

    Power Supply — Electrical characteristics of available power supply must agree with unit nameplate rating. Supply voltage must be within limits shown in T able 3. IMPOR T ANT : Operating unit on improper supply volt- age, or with excessive phase imbalance, constitutes abuse and may af fect Carrier warranty . See Unbalanced 3-Phase Supply V oltage ...

  • Carrier 38AKS028-044 - page 7

    FIELD CONNECTIONS 1. Main Power — Bring wires from the fused disconnect switch through hole in bottom rail of unit to control box 11 12 (Fig. 6 and 7) and connect terminals , , and 13 line side of terminal block TB1 (see Fig. 8 and 9A or 9B). T o comply with NEC Article 440-14, the discon- nect must be located within sight from and readily ac- ce ...

  • Carrier 38AKS028-044 - page 8

    Fig. 6 — Dimensional Drawing, 38AKS028,034 LEGEND NEC — National Electrical Code VAV — V ariable Air V olume NOTES: 1. There must be minimum (2440 mm) 8 ft. clear air space above unit. 2. The approximate operating weight of the unit is: 50 AND 60 HZ UNIT WT (Lb) WT (Kg) 38AKS028 1650 748 38AKS028C 1804 818 38AKS034 1803 818 38AKS034C 2009 91 ...

  • Carrier 38AKS028-044 - page 9

    LEGEND NEC — National Electrical Code NOTES: 1. There must be minimum (2440 mm) 8 ft. clear air space above unit. 2. The approximate operating weight of the unit is: 50 HZ AND 60 HZ UNIT WT (Lb) WT (Kg) 38AKS044 2437 1 106 38AKS044C 2745 1246 Fig. 7 — Dimensional Drawing, 38AKS044 3. A ‘ ‘C’’ in the model number indicates unit has facto ...

  • Carrier 38AKS028-044 - page 10

    LEGEND AFS — Airflow Switch CB — Circuit Breaker EQUIP — Equipment FU — Fuse GND — Ground LLS1 — Liquid Line Solenoid for Solenoid Drop Control LLS2 — Liquid Line Solenoid for Capacity Control NEC — National Electrical Code, U.S.A. TB — T erminal Block TC — Thermostat Cooling Field Power Wiring Field Control Wiring Factory Inst ...

  • Carrier 38AKS028-044 - page 11

    BPR — Bypass Relay C— Contactor , Compressor DB — Circuit Breaker CR — Control Relay CM — Control Module EQUIP — Equipment FC — Fan Contactor Fig. 9A — Component Arrangement — 60 Hz FM — Fan Motor FU — Fuse GND — Ground LLSV — Liquid Line Solenoid V alve NEC — National Electrical Code (U.S.A.) TB — T erminal Block TRAN ...

  • Carrier 38AKS028-044 - page 12

    LEGEND BPR — Bypass Relay C— Contactor , Compressor CB — Circuit Breaker CR — Control Relay CM — Control Module EQUIP — Equipment FC — Fan Contactor FM — Fan Motor FU — Fuse GND — Ground LLSV — Liquid Line Solenoid V alve NEC — National Electrical Code (U.S.A.) TB — T erminal Block TDR — T ime Delay Relay TRAN — T rans ...

  • Carrier 38AKS028-044 - page 13

    ST ART -UP Initial Check Do not attempt to start the condensing unit, even mo- mentarily, until the following steps have been com- pleted. Compressor damage may result. 1. Check all auxiliary components, such as air -handling equip- ment, and other equipment. Consult the manufacturer ’ s instructions regarding any other equipment connected to the ...

  • Carrier 38AKS028-044 - page 14

    Fig. 10 — 38AKS028 Charging Chart, 50/60 Hz 14 ...

  • Carrier 38AKS028-044 - page 15

    Fig. 1 1 — 38AKS034 Charging Chart, 50/60 Hz 15 ...

  • Carrier 38AKS028-044 - page 16

    Fig. 12 — 38AKS044 Charging Chart, 50/60 Hz 16 ...

  • Carrier 38AKS028-044 - page 17

    FOR SER VICING ONL Y — T o speed up the 5-minute anti- short cycle, a temporary jumper may be placed between ter- minals T1 and T6 of the control module. This jumper must be removed after servicing is com- plete. Failure to remove this jumper is considered abu- sive treatment and will void the Carrier warranty. Bypass Relay (BPR) — All units ar ...

  • Carrier 38AKS028-044 - page 18

    COMPRESSOR END AND RIGHT -SIDE VIEW TRAN2 CB1 CB2 TB3 FC3 FC2 FC CM CR1 TRAN1 TB2 C1 COMPRESSOR END, CONTROL P ANEL REMOVED OIL PRESSURE SAFETY SWITCH COMPRESSOR END, LEFT -SIDE ACCESS DOOR (JUNCTION BOX COVER REMOVED) LIQUID LINE SERVICE VA LV E COMPRESSOR END, RIGHT -SIDE ACCESS DOOR Fig. 13 — 38AKS Unit with Access Panels Removed 18 ...

  • Carrier 38AKS028-044 - page 19

    Fan Adjustment — Adjust fan as shown in Fig. 14. Oil Charge — Compressors are factory charged with oil as follows: COMPRESSOR AMOUNT pints (liters) 06E9265 20.0 (9.4) 06E9275 20.0 (9.4) 06E9299 19.0 (9.0) When additional oil or a complete charge is required, use only Carrier-approved compressor oil: Petroleum Specialities Inc. ................. ...

  • Carrier 38AKS028-044 - page 20

    Oil Pressure Safety Switch (OPS) — The OPS in the control circuit stops the compressor and unit, if proper oil pressure dif ferential is not established at start-up or main- tained during operation. If OPS stops the unit, determine the cause and correct before restarting unit. Failure to do so will constitute abuse. Equipment failur e due to abus ...

  • Carrier 38AKS028-044 - page 21

    TROUBLESHOOTING SYMPTOM AND PROBABLE CAUSE PROBABLE REMEDY COMPRESSOR DOES NOT RUN 1. Control circuit breaker tripped 1. Reset control circuit breaker 2. Power line open 2. Reset circuit breaker 3. Oil pressure switch tripped 3. Reset oil pressure switch at unit 4. Safety device tripped 4. Reset control circuit with thermostat 5. Contactor stuck op ...

  • Carrier 38AKS028-044 - page 22

    P ACKAGED SERVICE TRAINING Our packaged service training programs provide an excellent way to increase your knowledge of the equipment discussed in this manual. Product programs cover: • Unit Familiarization • Installation Overview • Maintenance • Operating Sequence A large selection of product, theory , and skills programs is available. Al ...

  • Carrier 38AKS028-044 - page 23

    ST ART -UP CHECKLIST (Remove and store in job file) A. Preliminary Information OUTDOOR: MODEL NO. SERIAL NO. INDOOR: AIR HANDLER MANUF ACTURER MODEL NO. SERIAL NO. ADDITIONAL ACCESSORIES B. Pre-Start-Up OUTDOOR UNIT IS THERE ANY SHIPPING DAMAGE? (Y/N) IF SO, WHERE: WILL THIS DAMAGE PREVENT UNIT ST ART -UP? (Y/N) CHECK POWER SUPPL Y . DOES IT AGREE ...

  • Carrier 38AKS028-044 - page 24

    C. Start-Up CHECK EV APORA TOR F AN SPEED AND RECORD. CHECK CONDENSER F AN SPEED AND RECORD. AFTER A T LEAST 10 MINUTES RUNNING TIME, RECORD THE FOLLOWING MEASUREMENTS: OIL PRESSURE SUCTION PRESSURE SUCTION LINE TEMP DISCHARGE PRESSURE DISCHARGE LINE TEMP ENTERING CONDENSER AIR TEMP LEA VING CONDENSER AIR TEMP EV AP ENTERING AIR DB TEMP EV AP ENTER ...

Fabricant Carrier Catégorie Air Conditioner

Les documents que nous recevons du fabricant de l'appareilCarrier 38AKS028-044 peuvent être divisés en plusieurs groupes. Ceux-ci sont, entre autres:
- dessins techniques Carrier
- manuels d’utilisations 38AKS028-044
- fiches produit Carrier
- dépliants
- ou étiquettes-énergie Carrier 38AKS028-044
Tous sont importants, mais les informations les plus importantes du point de vue de l'utilisation de l'appareil se trouvent dans le manuel d’utilisation Carrier 38AKS028-044.

Un groupe de documents appelé manuels d’utilisation est également divisé en types plus spécifiques, tels que: Manuels d’installation Carrier 38AKS028-044, manuels d’entretien, brefs manuels ou manuels de l’utilisateur Carrier 38AKS028-044. Selon vos besoins, vous devriez chercher le document dont vous avez besoin. Sur notre site, vous pouvez voir le manuel le plus populaire d’utilisation du produit Carrier 38AKS028-044.

Manuels d’utilsiation similaires

Manuel d’utilisation complet de l’appareil Carrier 38AKS028-044, quelle devrait-elle être?
Le manuel d’utilisation, également appelé le mode d’emploi, ou tout simplement le manuel, est un document technique destiné à aider à utiliser Carrier 38AKS028-044 par les utilisateurs. Des manuels sont généralement écrits par un rédacteur technique, mais dans un langage accessible à tous les utilisateurs Carrier 38AKS028-044.

Le manuel d’utilisation complet Carrier, devrait inclure plusieurs éléments de base. Certains d'entre eux sont moins importants, tels que: la couverture / page de titre ou pages d'auteur. Cependant, la partie restante, devrait nous fournir des informations importantes du point de vue de l'utilisateur.

1. Introduction et des conseils sur la façon d'utiliser le manuel Carrier 38AKS028-044 - Au début de chaque manuel, nous devrions trouver des indices sur la façon d'utiliser le document. Il doit contenir des informations sur l'emplacement de la table des matières Carrier 38AKS028-044, FAQ ou des problèmes les plus fréquents - les points qui sont les plus souvent recherchés par les utilisateurs de chaque manuel
2. Table des matières - index de tous les conseils pour lCarrier 38AKS028-044 qui peuvent être trouvés dans le document courant
3. Conseils sur la façon d'utiliser les fonctions de base de l’appareil Carrier 38AKS028-044 - qui devraient nous aider dans les premières étapes lors de l'utilisation Carrier 38AKS028-044
4. Troubleshooting - séquence systématique des activités qui nous aideront à diagnostiquer et ensuite résoudre les principaux problèmes de Carrier 38AKS028-044
5. FAQ - questions fréquemment posées
6. Détails du contact Informations sur l'endroit où chercher le contact avec le fabricant / service Carrier 38AKS028-044 dans un pays donné, si le problème ne peut être résolu par nous-mêmes.

Avez-vous une question à propos de Carrier 38AKS028-044?

Utiliser le formulaire ci-dessous

Si vous n’avez pas résolu votre problème avec Carrier 38AKS028-044, avec l'aide du manuel que vous avez trouvé, posez une question en utilisant le formulaire ci-dessous. Si un utilisateur a eu un problème similaire avec Carrier 38AKS028-044 il est probable qu’il a envie de partager la façon de le résoudre.

Réécrire le texte de l'image

Commentaires (0)