    CATALOG NO. 6200.51O Effective: 04-09-07 Replaces: 05-15-05 Models 2100-4001 P/N 240251 Rev. 16 INST ALLA TION AND OPERA TING INSTRUCTIONS RA YTHERM TM COMMMERCIAL SWIMMING POOL HEA TER Models P-926 to P-1826 and P-2100 to P-4001 This manual should be maintained in legible condition and kept adjacent to the heater or in a safe place for future refe ...

  • Raypak P-926, P-1826, P-2100, P-4001 - page 2

    Content s SECTION 1: RECEIVING EQUIPMENT SECTION 2: GENERAL SPECIFICATIONS SECTION 3: INSTALLATION INSTRUCTIONS Code Requirements Base Installation Clearances Combustion Air Venting Connections Gas Supply Connections Water connections Controls Wiring Diagrams SECTION 4: SERVICING INSTRUCTIONS General Location of Controls Start-Up Procedures Inspect ...

  • Raypak P-926, P-1826, P-2100, P-4001 - page 3

    12" Minimu m 12" M inimum 4" Minimum HEA TER Sheet Metal 24 Gauge IMPORTANT NOTICE These instructions are intended for the use of qualified personnel only, specifically trained and experienced in the installation of this type of heating equipment and related system components. Installation and service personnel may be required by som ...

  • Raypak P-926, P-1826, P-2100, P-4001 - page 4

    4 Fig. #8245 CLEARANCES ALL HEATERS For clearances from combustible surfaces, see chart below. We require a minimal vertical clearance of three feet between the upper surface of the flue outlet to a non- combustible material. MINIMUM CLEARANCES FROM COMBUSTIBLE CONSTRUCTION INDOOR HEATERS Top - 24" *Vent - 6" Back - 24" Right Side - ...

  • Raypak P-926, P-1826, P-2100, P-4001 - page 5

    5' MIN 2' MIN 10' OR LESS 2' MIN VENT CAP VENT PIPE DRAFT HOOD HEA TER For protection against rain or blockage by snow, the vent pipe must terminate with a vent cap which complies with the local codes or, in the absence of such codes, to the latest edition of the National Fuel Gas Code, ANSI Z223.1/NFPA 54. The discharge opening ...

  • Raypak P-926, P-1826, P-2100, P-4001 - page 6

    (a) Seal any unused openings in the common venting system. (b) Visually inspect the venting system for proper size and horizontal pitch and determine there is no blockage or restriction, leakage, corrosion and other deficiencies which could cause an unsafe condition. (c) Insofar as is practical, close all building doors and windows and all doors be ...

  • Raypak P-926, P-1826, P-2100, P-4001 - page 7

    GAS PRESSURE REGULATOR The gas pressure regulator is preset and sealed at 4 in. WC for natural gas, and 11 in. WC for propane gas. Between the gas valve and the burners is a 1/8" pipe plug. The pressure at this point, taken with a manometer, should be about 3.7 in. WC natural gas and 10.5 in. WC propane gas. If an adjustment is needed, remove ...

  • Raypak P-926, P-1826, P-2100, P-4001 - page 8

    When local codes permit the use of less than four feet high temperature piping or two elbows, provisions should be made to always shut the heater off a minimum of 15 minutes prior to pump shut down in order to carry away residual heat and prevent damage to the low temperature piping. A fireman switch included in the time clock may be used for this ...

  • Raypak P-926, P-1826, P-2100, P-4001 - page 9

    9 MODELS 1287/1336 - 1758/1826 Inlet/Outlet Header 2-1/2" Inlet 2-1/2" Outlet 1-1/2" Slip Ball Valve 2" Slip Ball Valve 3" Outlet Fig. #9270 Fig. #9200 Pump 3" Inlet 2 H.P. Pump Inlet/Outlet Header MODELS 2100-4001 FLOW RATES/WATER CONNECTIONS MODEL CONNECTION SIZE MIN GPM MAX GPM 926-1223 * 6 0 120 1287-1826 2-1/2&quo ...

  • Raypak P-926, P-1826, P-2100, P-4001 - page 10

    10 Raypak recommends the installation of an air bleed vent at a suitable location (usually the highest point) to remove air from the piping system. These units should be available at your local wholesale supplier. Raypak does not provide this item. CAUTION: Power to the heater should be interlocked with the main system pump to make sure the heater ...

  • Raypak P-926, P-1826, P-2100, P-4001 - page 11

    Note: The drawings and instructions above show only one of several acceptable ways of installing the dry well into main system loop. The use of saddle clamps and “Weld O Lets” (shown in Fig. 10) are acceptable. Follow clamp manufacturer’s instructions. MOUNTING WELL INTO SYSTEM RETURN LOOP PIPE - FRONT-MOUNTED LOOP: Note: For more detail on p ...

  • Raypak P-926, P-1826, P-2100, P-4001 - page 12

    4. If the heater inlet temperature remains less than 100°F and Valve "A" is fully open, leave Valve "A" fully open and throttle Valve "B" until the heater inlet temperature rises to within the range of 100°F-105°F. 5. The resultant heater outlet temperature should be in the range of 120-130°F. 6. As the pool temper ...

  • Raypak P-926, P-1826, P-2100, P-4001 - page 13

    Models 2100 thru 4001 13 PIPING CONFIGURATIONS FOR RAYTHERM COMMERCIAL POOL HEATERS Fig # 9268 Fig # 9269 BLENDED WATER TEMPERATURE (THERMOMETER AT HEATER INLET) HEATER OUTLET TEMPERATURE THERMOMETER HEATER THERMOSTAT RECOMMENDED FIELD INSTALLED ISOLATION VALVES FOR SERVICE T I T o T c ...

  • Raypak P-926, P-1826, P-2100, P-4001 - page 14

    14 EXTERNAL AUXILIARY BYPASS VALVE (Where Required) 926-1223 Models only An auxiliary bypass valve should be used when flow rates exceed 120 GPM (usually a high performance pump size larger than two HP will exceed this flow rate). This valve is required to complement the function of the automatic bypass valve, particularly when starting the heater ...

  • Raypak P-926, P-1826, P-2100, P-4001 - page 15

    15 HIGH & LOW GAS PRESSURE SWITCHES Pressure switches sense either high or low gas pressure and automatically shut down burners if abnor- mal pressures exsist. Standard on Models 3001-4001. PRESSURE SWITCH GAS MANIFOLD Fig. #8236 ELECTRICAL WIRING CAUTION: Label all wires prior to disconnection when servicing controls. Wiring errors can cause i ...

  • Raypak P-926, P-1826, P-2100, P-4001 - page 16

    16 WIRING DIAGRAM MODELS 926 - 1223 ...

  • Raypak P-926, P-1826, P-2100, P-4001 - page 17

    17 WIRING DIAGRAM MODELS 1287-1826 ...

  • Raypak P-926, P-1826, P-2100, P-4001 - page 18

    WIRING DIAGRAM MODELS 2100-2500 18 ...

  • Raypak P-926, P-1826, P-2100, P-4001 - page 19

    WIRING DIAGRAM MODELS 3001-4001 19 ...

  • Raypak P-926, P-1826, P-2100, P-4001 - page 20

    TEMPERATURE CONTROL The pool water temperature is controlled by the pool thermostat. The heater water temperature high limit is controlled by the manual reset high limit. PRESSURE SWITCH The pressure switch, or heater actuator, ensures that the heater operates only when the filter pump is in operation. It is factory set at 1.75 PSI for deck level i ...

  • Raypak P-926, P-1826, P-2100, P-4001 - page 21

    ADJUSTMENT KNOB Fig. # 8069.1 PRESSURE SWITCH ADJUSTMENT RANGE HEAT EXCHANGER HEIGHT 5' Max 5' Max Fig. # 8152.0 NOTE: If heater is installed outside of the limits shown, a flow switch must be used in place of the pressure switch when mounted and wired adjacent to the heater. TWO-SPEED PUMPS In some cases, the flow on the low speed is ins ...

  • Raypak P-926, P-1826, P-2100, P-4001 - page 22

    AFTER START-UP Pilot System Checkout Procedure 1. Turn on power to the ignition systems and turn gas supply off. 2. Check ignition module as follows: a. Set the thermostat above pool water temperature to turn heater on. b. Watch for continuous spark at the pilot burner. c. Time the spark operation. Time must be within the lockout timing period (15 ...

  • Raypak P-926, P-1826, P-2100, P-4001 - page 23

    SERVICING PROCEDURES TUBE CLEANING PROCEDURE (TYPICAL) Establish a regular inspection schedule, the fre- quency depending on the local water condition and severity of service. Do not let the tubes clog up solidly. Clean out deposits over 1/16" in thickness. Although the illustration shows the mechanical clean- ing procedure of a small boiler, ...

  • Raypak P-926, P-1826, P-2100, P-4001 - page 24

    5. Remove heat exchanger corner brackets. 6. Remove combustion chamber clips at the four corners of the heat exchanger. 7. Lift heat exchanger straight up using caution not to damage refractory. HEAT EXCHANGER REASSEMBLY 1. Heat exchanger header O-rings should be replaced with new ones. 2. Install inlet-outlet and return water headers and install h ...

  • Raypak P-926, P-1826, P-2100, P-4001 - page 25

    CONTROL WELL REPLACEMENT Remove top, sensing bulb and clip. Collapse well tube at the open end and with a chisel, push through into the header, and remove the well through header. Insert a new well and roll into place. If a roller is not available, solder the well in place with silver solder. IMMERSION WELL 25 Fig. #8126.0 TUBE REPLACEMENT PROCEDUR ...

  • Raypak P-926, P-1826, P-2100, P-4001 - page 26

    MODELS 926-1223 UNITHERM GOVERNOR INLET/OUTLET HEADER OUTLET INLET Fig. #8224.0 GASKET UNITHERM GOVERNOR WITH POWER ELEMENT MODELS 1287-1826 (Models prior to Jan. '95) DOUBLE EXTERNAL U.G. MODELS 2100-4001 (Models prior to Jan. '95) EXTERNAL U.G. To test operation of Unitherm Governor, place in hot water and watch for movement against spr ...

  • Raypak P-926, P-1826, P-2100, P-4001 - page 27

    SECTION 5 / TROUBLESHOOTING GUIDE IMPORTANT NOTICE These instructions are primarily intended for the use of qualified personnel specifically trained and experienced in the installation of this type of heating equipment and related system components. Installation and service personnel may be required by some states to be licensed. Persons not qualif ...

  • Raypak P-926, P-1826, P-2100, P-4001 - page 28

    Outer jacket very hot (paint blistered) *Broken refractory caused by shipping damage or improper combustion………………………….. Excessive sooting of heat exchanger…………………………... Calculate temperature in °F/hr……... Filter not running long enough…….... Dirty filter…………………………….. Gas line or ...

  • Raypak P-926, P-1826, P-2100, P-4001 - page 29

    WARNING HIGH VOLTAGE For qualified Technicians ONLY NOTE: Some heaters may be equipped with an ignition module that shuts off pilot gas if pilot fails to light. To reset, interrupt power to heater. NOTE: Before troubleshooting, familiarize yourself with the start-up and checkout procedure. Check line voltage power, low voltage transformer, limit co ...

  • Raypak P-926, P-1826, P-2100, P-4001 - page 30

    SECTION 6 / REPLACEMENT PARTS LIST NOTE: To supply the correct part it is important that you state the model number, serial number and type of gas when applicable. Any part returned for replacement under standard company warranties must be properly tagged with RAYPAK return parts tag, completely filled in with the heater serial number, model number ...

  • Raypak P-926, P-1826, P-2100, P-4001 - page 31

    MODELS: 926/962, 1083/1125, 1178/1223, 1287/1336, 1414/1468, 1571/1631, 1758/1826 31 2-C ...

  • Raypak P-926, P-1826, P-2100, P-4001 - page 32

    32 ...

  • Raypak P-926, P-1826, P-2100, P-4001 - page 33

    33 ...

  • Raypak P-926, P-1826, P-2100, P-4001 - page 34

    MODELS: 2100, 2500, 3001, 3500, 4001 34 ...

  • Raypak P-926, P-1826, P-2100, P-4001 - page 35

    35 ...

  • Raypak P-926, P-1826, P-2100, P-4001 - page 36

    36 ...

  • Raypak P-926, P-1826, P-2100, P-4001 - page 37

    37 LIMITED W ARRANTY RA YTHERM TYPE P SIZES 0926-4001 SCOPE: Raypak, Inc. (“Raypak”) warrants to the original owner that all parts of this heater which are actually manufactured by Raypak will be free from failure under normal use and service for the specified warranty periods and subject to the conditions set forth in this W arranty . Labor ch ...

  • Raypak P-926, P-1826, P-2100, P-4001 - page 38

    Raypak, Inc. , 2151 Eastman Avenue, Oxnard, CA 913030 (805) 278-5300 FAX (800) 872-9725 Raypak Canada LTD , 2805 Slough Street, Mississauga, Ontario, Canada L4T 1G2 (905) 677-7999 FAX (905) 677-8036 Litho in U.S.A. www .raypak.com ...

Fabricant Raypak Catégorie Swimming Pool Heater

Les documents que nous recevons du fabricant de l'appareilRaypak P-926, P-1826, P-2100, P-4001 peuvent être divisés en plusieurs groupes. Ceux-ci sont, entre autres:
- dessins techniques Raypak
- manuels d’utilisations P-926, P-1826, P-2100, P-4001
- fiches produit Raypak
- dépliants
- ou étiquettes-énergie Raypak P-926, P-1826, P-2100, P-4001
Tous sont importants, mais les informations les plus importantes du point de vue de l'utilisation de l'appareil se trouvent dans le manuel d’utilisation Raypak P-926, P-1826, P-2100, P-4001.

Un groupe de documents appelé manuels d’utilisation est également divisé en types plus spécifiques, tels que: Manuels d’installation Raypak P-926, P-1826, P-2100, P-4001, manuels d’entretien, brefs manuels ou manuels de l’utilisateur Raypak P-926, P-1826, P-2100, P-4001. Selon vos besoins, vous devriez chercher le document dont vous avez besoin. Sur notre site, vous pouvez voir le manuel le plus populaire d’utilisation du produit Raypak P-926, P-1826, P-2100, P-4001.

Manuels d’utilsiation similaires

Manuel d’utilisation complet de l’appareil Raypak P-926, P-1826, P-2100, P-4001, quelle devrait-elle être?
Le manuel d’utilisation, également appelé le mode d’emploi, ou tout simplement le manuel, est un document technique destiné à aider à utiliser Raypak P-926, P-1826, P-2100, P-4001 par les utilisateurs. Des manuels sont généralement écrits par un rédacteur technique, mais dans un langage accessible à tous les utilisateurs Raypak P-926, P-1826, P-2100, P-4001.

Le manuel d’utilisation complet Raypak, devrait inclure plusieurs éléments de base. Certains d'entre eux sont moins importants, tels que: la couverture / page de titre ou pages d'auteur. Cependant, la partie restante, devrait nous fournir des informations importantes du point de vue de l'utilisateur.

1. Introduction et des conseils sur la façon d'utiliser le manuel Raypak P-926, P-1826, P-2100, P-4001 - Au début de chaque manuel, nous devrions trouver des indices sur la façon d'utiliser le document. Il doit contenir des informations sur l'emplacement de la table des matières Raypak P-926, P-1826, P-2100, P-4001, FAQ ou des problèmes les plus fréquents - les points qui sont les plus souvent recherchés par les utilisateurs de chaque manuel
2. Table des matières - index de tous les conseils pour lRaypak P-926, P-1826, P-2100, P-4001 qui peuvent être trouvés dans le document courant
3. Conseils sur la façon d'utiliser les fonctions de base de l’appareil Raypak P-926, P-1826, P-2100, P-4001 - qui devraient nous aider dans les premières étapes lors de l'utilisation Raypak P-926, P-1826, P-2100, P-4001
4. Troubleshooting - séquence systématique des activités qui nous aideront à diagnostiquer et ensuite résoudre les principaux problèmes de Raypak P-926, P-1826, P-2100, P-4001
5. FAQ - questions fréquemment posées
6. Détails du contact Informations sur l'endroit où chercher le contact avec le fabricant / service Raypak P-926, P-1826, P-2100, P-4001 dans un pays donné, si le problème ne peut être résolu par nous-mêmes.

Avez-vous une question à propos de Raypak P-926, P-1826, P-2100, P-4001?

Utiliser le formulaire ci-dessous

Si vous n’avez pas résolu votre problème avec Raypak P-926, P-1826, P-2100, P-4001, avec l'aide du manuel que vous avez trouvé, posez une question en utilisant le formulaire ci-dessous. Si un utilisateur a eu un problème similaire avec Raypak P-926, P-1826, P-2100, P-4001 il est probable qu’il a envie de partager la façon de le résoudre.

Réécrire le texte de l'image

Commentaires (0)