    990 -1060B 12/2005 APC Smart-UPS ® RT 1000/2000 VA 220/230/240 V AC Tower/ Rack Mount 2U Uninterr uptible Pow er Suppl y User Manual English ...

  • APC SURT2000XLI-1BNDL - page 2

    ...

  • APC SURT2000XLI-1BNDL - page 3

    1 990 -1060B 12/ 2005 1: S AF E T Y I NFORMA TION American Po wer Conversion Corporation (APC) is the leading national and internatio nal manufac- turer of state-of-the- art uninterrupt ible power su pplies, redundant switches, powe r manag ement soft- ware, an d related equipment. APC products protect hardw are, software, and data from the threat ...

  • APC SURT2000XLI-1BNDL - page 4

    990 -1060B 12/2005 2 • In order to maintain compliance with the EMC directive, output cords attached to the UPS should n ot exceed 10 meters in length. D EENERGIZING S AFE T Y • If the equ ip ment has an internal energy source (b attery), the output may be en er gized when the unit is not connected to an AC power ou tlet. • To deenergize pl u ...

  • APC SURT2000XLI-1BNDL - page 5

    3 990 -1060B 12/ 2005 2: I NS T A LLA TION U NPACKING Inspect the UPS upon receipt. A PC designed robust packag ing for your product. How e ver, accidents and damag e may occur during s hipment. Notify the carrier and dealer if there is damage. The packaging is rec yclable; save it for reu se or dispose of it properly . Check the packag e co ntents ...

  • APC SURT2000XLI-1BNDL - page 6

    990 -1060B 12/2005 4 I NSTALLA TIO N 1. A TTACH THE S UPP ORT F EET If the UPS is to be operated in To wer Configuration the suppor t feet must be attached for proper stabilit y. 1. Locate the two feet an d t he plastic bag con tain- ing the four screws pac ked with the UPS. 2. Gently la y the UPS on it s side a s shown. 3. Use the screws to attach ...

  • APC SURT2000XLI-1BNDL - page 7

    5 990 -1060B 12/ 2005 3. C ONNECT THE B ATTERY 1. To connect the battery , push the batter y conn ec- tor into the receptacle in the battery co mpart- ment. Press firmly to ensure a tight connection. You will hear a “snap” when the connector is seated properly . 2. Push the battery cables and white cord into the space with the battery connector ...

  • APC SURT2000XLI-1BNDL - page 8

    990 -1060B 12/2005 6 6. T URN ON THE UPS Make sure the battery is co nnected be fore turning on the U PS! P ress the button on the front panel to power up your UPS. This will power up connected equipment if that equipment is turned on. The UPS charges its batter y when it is connected to utility po wer. The battery char ges full y dur ing t he fi r ...

  • APC SURT2000XLI-1BNDL - page 9

    7 990 -1060B 12/ 2005 3: O PE R A T ION I NDICATORS AND C ONTROLS The UPS power con trol and operating indicators are located on the front display panel. The inpu t and output conn ectors are on the rear panel. F RONT P ANE L Fo r Pos i t io n O n l y | The ON and OFF buttons pow er the UPS and act as master controls for the conn ected equipment if ...

  • APC SURT2000XLI-1BNDL - page 10

    990 -1060B 12/2005 8 O PERATION Power On Press and release the button to supply po w er to the UPS and conn ected equipment. Cold Start When the UPS is off and there is no utility power, use the cold start feature to apply power to th e connected equipment fr om the UPS’s batter y. Cold start is not a normal condition. To cold start the unit, pus ...

  • APC SURT2000XLI-1BNDL - page 11

    9 990 -1060B 12/ 2005 U TILITY P OWER During normal operation, the UPS monitors the utility power and delivers po wer to the conn ected equip me nt. If your syste m is e xp erie nci ng exc essi ve p eri od s of hi gh or l o w volta ge, have a cer tifie d electrician check your facility for electrical problems. If the problem continues, contact the ...

  • APC SURT2000XLI-1BNDL - page 12

    990 -1060B 12/2005 10 B ATTERY P OWER If the utility power fails, the UPS can pro vide power to the connected equipment from its internal batteries for a finite period. The UPS sounds an alarm—four beeps every 30 secon ds—while operat- ing on battery. The alarm stops when the UPS returns to onli ne operation. On Battery When the On Battery indi ...

  • APC SURT2000XLI-1BNDL - page 13

    11 990-1 060B 12/20 05 R EAR P ANE L TVSS Ground Input Plug Computer Interface Port Fan External Battery Connector Port Outlets B ASIC C ONNE CTORS Computer Inter- face Port Power management sof t ware and interface k its can be used with the UPS. Use only interface ki ts su pplied or appro ved by APC. If used, conn ec t the interface cable to th e ...

  • APC SURT2000XLI-1BNDL - page 14

    990 -1060B 12/2005 12 O N B ATTERY O PERATION The UPS s witches to battery operation auto matically and an internal alarm sounds (periodic b eeps) if the utility power fails. Press t he ON button (front panel) to silence the UPS alar m until low batter y (for the cu rrent outage only). You can change the audible indicator if you are u sing Po werCh ...

  • APC SURT2000XLI-1BNDL - page 15

    13 990-1 060B 12/20 05 N OTE : S ETTING THESE ITEMS REQUIRES SOFTWARE , OPTION AL HA RDWARE , OR CONFIGURATION IN T ERM INAL M ODE . F UNCTION F ACTORY D EFAULT U SER S ELECTABLE C HOICES D ESCRIPTION Sync hronized Turn-on Delay 0 seconds 20, 60 , 120, 240 , 480, 720, 96 0 sec- onds The UPS will w ait the specified tim e after the retur n of utilit ...

  • APC SURT2000XLI-1BNDL - page 16

    990 -1060B 12/2005 14 4: T RANSPORT , M AINTENANCE , AND T ROUB LESHOOT ING T RANSPORTING YOUR UPS Alway s DISCONNECT THE B ATTERY before shipping in co mpliance with U.S. Departm e nt of Trans portation (DOT) regul ations . The battery may rem ai n in the UPS; it does not have to be removed. This require ment applies w hether the UPS is shi pped a ...

  • APC SURT2000XLI-1BNDL - page 17

    15 990-1 060B 12/20 05 R EPLACING THE B ATTERY P ACK This UPS has an easy to replace, h ot-s wappable battery pack. Replacement is a safe procedure, is o- lated from electrical hazards . You may leave the UPS and c onnected equipment on while replacing the battery. See your dealer or cont act APC for in formation on replacem ent batter y packs . Th ...

  • APC SURT2000XLI-1BNDL - page 18

    990 -1060B 12/2005 16 T ROUBLESHOOTING Use the chart belo w to solve minor UPS installation pro blems. Refer to the APC web site www.apc.com for assistance with complex UPS problems. P ROBLEM AND P OSSIBLE C AUS E S OLUTION UPS WILL NOT TURN ON ON bu tton no t pushe d. Pre ss the ON button o nce to powe r the UP S and the equipm ent. UPS not con ne ...

  • APC SURT2000XLI-1BNDL - page 19

    17 990-1 060B 12/20 05 S ERVICE 1. Revi e w the problem s discussed in t he Troubleshoot ing section of th is manual to eliminate com- mon probl ems. 2. Verify that no circuit break ers are tripped. A tripped circuit break er is the most common prob- lem. 3. If th e problem persists, call APC Cust o mer Servi ce or visit the APC w ebsite (www.apc.c ...

  • APC SURT2000XLI-1BNDL - page 20

    990 -1060B 12/2005 18 5: C ON T A CT , R EGUL A TORY , A ND W AR R AN T Y I NFOR MA TION C ONTACTING AP C Refer to the information pro vided at the APC Internet site: http:/ / www.apc.com/su pport R EGULATORY A GE NCY A PPROVALS N 3 94 B ME 61 D ECLARATION OF C ONF ORM ITY ...

  • APC SURT2000XLI-1BNDL - page 21

    19 990-1 060B 12/20 05 L IMITED W ARRA NTY American Power Conv ersion (APC) warrants its produ cts to be free from defects in materials an d workmansh ip for a period of tw o years from the dat e of purchase. Its obligation under t his warranty is limited to repairing or replacing, at its o wn sole option, any such defective products. T o obtain se ...

Fabricant APC Catégorie Uninterruptible power supply (

Les documents que nous recevons du fabricant de l'appareilAPC SURT2000XLI-1BNDL peuvent être divisés en plusieurs groupes. Ceux-ci sont, entre autres:
- dessins techniques APC
- manuels d’utilisations SURT2000XLI-1BNDL
- fiches produit APC
- dépliants
- ou étiquettes-énergie APC SURT2000XLI-1BNDL
Tous sont importants, mais les informations les plus importantes du point de vue de l'utilisation de l'appareil se trouvent dans le manuel d’utilisation APC SURT2000XLI-1BNDL.

Un groupe de documents appelé manuels d’utilisation est également divisé en types plus spécifiques, tels que: Manuels d’installation APC SURT2000XLI-1BNDL, manuels d’entretien, brefs manuels ou manuels de l’utilisateur APC SURT2000XLI-1BNDL. Selon vos besoins, vous devriez chercher le document dont vous avez besoin. Sur notre site, vous pouvez voir le manuel le plus populaire d’utilisation du produit APC SURT2000XLI-1BNDL.

Manuels d’utilsiation similaires

Manuel d’utilisation complet de l’appareil APC SURT2000XLI-1BNDL, quelle devrait-elle être?
Le manuel d’utilisation, également appelé le mode d’emploi, ou tout simplement le manuel, est un document technique destiné à aider à utiliser APC SURT2000XLI-1BNDL par les utilisateurs. Des manuels sont généralement écrits par un rédacteur technique, mais dans un langage accessible à tous les utilisateurs APC SURT2000XLI-1BNDL.

Le manuel d’utilisation complet APC, devrait inclure plusieurs éléments de base. Certains d'entre eux sont moins importants, tels que: la couverture / page de titre ou pages d'auteur. Cependant, la partie restante, devrait nous fournir des informations importantes du point de vue de l'utilisateur.

1. Introduction et des conseils sur la façon d'utiliser le manuel APC SURT2000XLI-1BNDL - Au début de chaque manuel, nous devrions trouver des indices sur la façon d'utiliser le document. Il doit contenir des informations sur l'emplacement de la table des matières APC SURT2000XLI-1BNDL, FAQ ou des problèmes les plus fréquents - les points qui sont les plus souvent recherchés par les utilisateurs de chaque manuel
2. Table des matières - index de tous les conseils pour lAPC SURT2000XLI-1BNDL qui peuvent être trouvés dans le document courant
3. Conseils sur la façon d'utiliser les fonctions de base de l’appareil APC SURT2000XLI-1BNDL - qui devraient nous aider dans les premières étapes lors de l'utilisation APC SURT2000XLI-1BNDL
4. Troubleshooting - séquence systématique des activités qui nous aideront à diagnostiquer et ensuite résoudre les principaux problèmes de APC SURT2000XLI-1BNDL
5. FAQ - questions fréquemment posées
6. Détails du contact Informations sur l'endroit où chercher le contact avec le fabricant / service APC SURT2000XLI-1BNDL dans un pays donné, si le problème ne peut être résolu par nous-mêmes.

Avez-vous une question à propos de APC SURT2000XLI-1BNDL?

Utiliser le formulaire ci-dessous

Si vous n’avez pas résolu votre problème avec APC SURT2000XLI-1BNDL, avec l'aide du manuel que vous avez trouvé, posez une question en utilisant le formulaire ci-dessous. Si un utilisateur a eu un problème similaire avec APC SURT2000XLI-1BNDL il est probable qu’il a envie de partager la façon de le résoudre.

Réécrire le texte de l'image

Commentaires (0)