    FieldPoint ™ Operating Instructions FP-AI-110 and cFP-AI-110 Eight-Channel, 16-Bit Analog Input M odules These operating instructions descri be ho w to install and use the FP-AI-110 and cFP-AI-110 analog input modules (referred to inclusiv ely as the [c]FP-A I-110). F or information about configuring and accessing the [c]F P- AI-110 ov er a netwo ...

  • National Instruments cFP-Al-110 - page 2

    FP-AI-110 and cFP-AI-110 2 ni.com T o install the FP- AI-110, refer to Figure 1 and complete the follow ing steps: 1. Slide the terminal base key to either position X (used for an y module) or position 1 (used for the FP- AI-110). 2. Align the FP- AI-110 alignmen t sl ots with the guide rails on the terminal base. 3. Press firmly to seat the FP- AI ...

  • National Instruments cFP-Al-110 - page 3

    © National Instruments Corp. 3 FP-AI-110 and cFP-AI-110 (10 lb ⋅ in.) of torque. The nylon coating on the screws pre vents them from loosening. Figure 2. Installing the cFP-AI-110 Wiring the [c]FP-AI-110 The FP-TB- x terminal base ha s connections for each of the eight input channels and for an external power su pply to power field de vice s. Th ...

  • National Instruments cFP-Al-110 - page 4

    FP-AI-110 and cFP-AI-110 4 ni.com is 2 A or less and the maximum current through any V SUP terminal is 1 A or less . Install a 2 A maximum, fast-acting fuse between t he external power supply and the V terminal on each channel. The wiring diagrams in this document sho w fuses where appropriate. T able 1 lists the terminal assign ments for the signa ...

  • National Instruments cFP-Al-110 - page 5

    © National Instruments Corp. 5 FP-AI-110 and cFP-AI-110 T aking Measurements with the [c]FP-AI-110 The [c]FP- AI-110 has eight single- ended input cha nnels. All eight channels share a common ground referen ce that is isolated from other modules in the FieldPoint system. Figure 3 shows the analog input circuitry on one channel. Figure 3. FP- AI-11 ...

  • National Instruments cFP-Al-110 - page 6

    FP-AI-110 and cFP-AI-110 6 ni.com Figure 5 sho ws how to connect a v oltage source with an extern al power supply to one channel of the [c]FP-AI-110. Figure 5. Voltage Source with Ex ternal Powe r Supply Measuring Current with the [c]FP-AI-110 The input ranges for current sources are 0 –20, 4 –20, and ± 20 mA. The module reads current flowing ...

  • National Instruments cFP-Al-110 - page 7

    © National Instruments Corp. 7 FP-AI-110 and cFP-AI-110 Figure 6. Current Source without External Power Supply Figure 7 sho ws how to connect a cu rrent sour ce with an external power supply to one channel of the [c]FP-AI-110. Figure 7. Current Source with Ex ternal Power Supply Input Ranges T o prev ent inaccurate readings, c hoose an input range ...

  • National Instruments cFP-Al-110 - page 8

    FP-AI-110 and cFP-AI-110 8 ni.com Overranging The [c]FP- AI-110 has an overranging feature that meas ures a little beyond the nominal values of each rang e. For example, the actual measurement limit of the ± 10 V range is ± 10.4 V . The overrang ing feature enables the [c]FP- AI-110 to compensate for field de vices with span errors of up to + 4% ...

  • National Instruments cFP-Al-110 - page 9

    © National Instruments Corp. 9 FP-AI-110 and cFP-AI-110 sampling rate is faster than th e rate at which the network module polls the [c]FP-AI-110 for data. Status Indicators The [c]FP-AI-110 has tw o green status LEDs, POWER and READY . After you insert the [c] FP-AI-110 into a terminal base or backplane and apply po wer to th e connected network ...

  • National Instruments cFP-Al-110 - page 10

    FP-AI-110 and cFP-AI-110 10 ni.com working v oltages of 250 V rms 1 . Safety standards (such as those published by UL and IEC) requir e the use of double insulation between hazardous voltages and an y human-accessi ble parts or circuits. Never try to use any isolation produ ct between human-accessible parts (such as DIN rails or monito ring station ...

  • National Instruments cFP-Al-110 - page 11

    © National Instruments Corp. 11 FP-AI-110 and cFP-AI-110 • Operate the [c]FP-AI-110 only at or belo w Pollution Degree 2. Pollution Degree 2 means th at only nonconductiv e pollution occurs in most case s. Occasionally , howe ver , a temporary conductivity caused by conde nsation must be e xpected. • Operate the [c]FP-AI-110 at or below Measur ...

  • National Instruments cFP-Al-110 - page 12

    FP-AI-110 and cFP-AI-110 12 ni.com Safety Guidelines for Hazardous V oltages If hazardous voltages are connected to the module, take the follow ing precautions. A hazardous voltage is a v oltage greater than 42.4 V peak or 60 VDC to earth ground. Caution Ensure that hazardous voltage wiring is performed only by qualified personnel adhering to local ...

  • National Instruments cFP-Al-110 - page 13

    © National Instruments Corp. 13 FP-AI-110 and cFP-AI-110 Effecti ve resolution by inpu t signal range and f ilter setting Input charac teristics by f ilter setting Normal-mode rejection .. .............. ..... 95 dB (with 50/60 Hz filter) Nonlinearity .......... ........... ......... ........ 0.0015% (monotonicity 1 guaranteed ov er the operating ...

  • National Instruments cFP-Al-110 - page 14

    FP-AI-110 and cFP-AI-110 14 ni.com Input current 25 °C........... ...................... .......... 400 pA typ, 1 nA max 70 °C ............. ........... ........... ........ 3 nA typ, 15 nA max Input noise (with 50 or 60 Hz filter enabled) ± 60 mV range ...... ........... ........... . ± 3 LSB 1 peak-to-peak ± 300 mV range ...... ........... . ...

  • National Instruments cFP-Al-110 - page 15

    © National Instruments Corp. 15 FP-AI-110 and cFP-AI-110 Note Full scale is the maximum value of the nominal input range. F or example, for the ± 10 V input range, full scale is 10 V and ± 0.01% of full scale is 1 mV . Gain error drift ........... ......... ........... ... ± 20 ppm/°C Offset error drift W ith 50 or 60 Hz filte r enabled ...... ...

  • National Instruments cFP-Al-110 - page 16

    FP-AI-110 and cFP-AI-110 16 ni.com Physical Char acteristics Indicators ............ ........... ........... ........ Green POWER and READY indicators W eight FP-AI-110..... ............. .............. ... 140 g (4.8 oz) cFP-AI-110 ....... ............ .............. 110 g (3.7 oz) Power Requirements Power from network module ............ 350 mW S ...

  • National Instruments cFP-Al-110 - page 17

    © National Instruments Corp. 17 FP-AI-110 and cFP-AI-110 Operating shock (IEC 60068-2-27)........... ........... ........ 50 g, 3 ms half sine, 18 shocks at 6 orientations; 30 g, 11 ms half sine, 18 shocks at 6 orientations Safety This product is designed to meet the requirements of the following standards of safety for electric al equipment for m ...

  • National Instruments cFP-Al-110 - page 18

    FP-AI-110 and cFP-AI-110 18 ni.com CE Compliance This product meets the essentia l requirements of applicable European Directi ves, as amended for CE ma rking, as follows: Lo w-V oltage Directi ve (s afety). ..... ... 73/23/EEC Electromagnet ic Compatibility Directiv e (EMC) ... ........... ......... ........ 89/336/EEC Note Refer to the Declaratio ...

  • National Instruments cFP-Al-110 - page 19

    © National Instruments Corp. 19 FP-AI-110 and cFP-AI-110 Where to Go for Support For more information about settin g up the FieldPoint system, refer to these National Instruments documents: • FieldPoint network module user manual • Other FieldPo int I/O m odule operating instructions • FieldPoint terminal base and connector block operating i ...

  • National Instruments cFP-Al-110 - page 20

    © 2003–2005 Nati onal Instruments Corp. All rights reserved. 373280A-01 Jun05 National Instruments, NI, n i.com, and LabVIEW are trademarks of National I nstruments Corporation. Refer to the Terms of Use section on ni.com/legal for more information about National Instruments tra demarks. Other product and company names ment ioned herein are trad ...

Fabricant National Instruments Catégorie Music Mixer

Les documents que nous recevons du fabricant de l'appareilNational Instruments cFP-Al-110 peuvent être divisés en plusieurs groupes. Ceux-ci sont, entre autres:
- dessins techniques National Instruments
- manuels d’utilisations cFP-Al-110
- fiches produit National Instruments
- dépliants
- ou étiquettes-énergie National Instruments cFP-Al-110
Tous sont importants, mais les informations les plus importantes du point de vue de l'utilisation de l'appareil se trouvent dans le manuel d’utilisation National Instruments cFP-Al-110.

Un groupe de documents appelé manuels d’utilisation est également divisé en types plus spécifiques, tels que: Manuels d’installation National Instruments cFP-Al-110, manuels d’entretien, brefs manuels ou manuels de l’utilisateur National Instruments cFP-Al-110. Selon vos besoins, vous devriez chercher le document dont vous avez besoin. Sur notre site, vous pouvez voir le manuel le plus populaire d’utilisation du produit National Instruments cFP-Al-110.

Manuel d’utilisation complet de l’appareil National Instruments cFP-Al-110, quelle devrait-elle être?
Le manuel d’utilisation, également appelé le mode d’emploi, ou tout simplement le manuel, est un document technique destiné à aider à utiliser National Instruments cFP-Al-110 par les utilisateurs. Des manuels sont généralement écrits par un rédacteur technique, mais dans un langage accessible à tous les utilisateurs National Instruments cFP-Al-110.

Le manuel d’utilisation complet National Instruments, devrait inclure plusieurs éléments de base. Certains d'entre eux sont moins importants, tels que: la couverture / page de titre ou pages d'auteur. Cependant, la partie restante, devrait nous fournir des informations importantes du point de vue de l'utilisateur.

1. Introduction et des conseils sur la façon d'utiliser le manuel National Instruments cFP-Al-110 - Au début de chaque manuel, nous devrions trouver des indices sur la façon d'utiliser le document. Il doit contenir des informations sur l'emplacement de la table des matières National Instruments cFP-Al-110, FAQ ou des problèmes les plus fréquents - les points qui sont les plus souvent recherchés par les utilisateurs de chaque manuel
2. Table des matières - index de tous les conseils pour lNational Instruments cFP-Al-110 qui peuvent être trouvés dans le document courant
3. Conseils sur la façon d'utiliser les fonctions de base de l’appareil National Instruments cFP-Al-110 - qui devraient nous aider dans les premières étapes lors de l'utilisation National Instruments cFP-Al-110
4. Troubleshooting - séquence systématique des activités qui nous aideront à diagnostiquer et ensuite résoudre les principaux problèmes de National Instruments cFP-Al-110
5. FAQ - questions fréquemment posées
6. Détails du contact Informations sur l'endroit où chercher le contact avec le fabricant / service National Instruments cFP-Al-110 dans un pays donné, si le problème ne peut être résolu par nous-mêmes.

Avez-vous une question à propos de National Instruments cFP-Al-110?

Utiliser le formulaire ci-dessous

Si vous n’avez pas résolu votre problème avec National Instruments cFP-Al-110, avec l'aide du manuel que vous avez trouvé, posez une question en utilisant le formulaire ci-dessous. Si un utilisateur a eu un problème similaire avec National Instruments cFP-Al-110 il est probable qu’il a envie de partager la façon de le résoudre.

Réécrire le texte de l'image

Commentaires (0)