    FORM NO . P1 1 -763 R EV . 1 Supersedes F orm No. P1 1 -763 P ACKAGE H EA T P UMP U NITS RJNA- HIGH EFFICIENCY SERIES NOMINAL SIZES 3-5 TONS [10.6-17.6 kW] *Unit shown with optional louver panels installed. “CERTIFIED UNDER THE A.R.I. CERTIFICA TION PROGRAM—A.R.I. ST ANDARD 240” ISO 9001:2000 ...

  • Rheem RJNA Series - page 2

    2 T ABLE OF CONTENTS I nt r od uc ti on .................................................................................................. 3-4 Mo d el Id en t if ic a ti on Op t io ns............................................................................ 5-6 General Data R JN A- S er ie s ....................................................... ...

  • Rheem RJNA Series - page 3

    3 INTRODUCTION These qualit y features are included in the Rhe em Outdoor P acka g e Heat Pumps Evaporator Coil/Filter Access Optional Electric Heater Kit Compressor Access Control Box Access Blower Access ...

  • Rheem RJNA Series - page 4

    4 INTRODUCTION INTRODUCTION ENGI NEERI NG FEA TURES RJNA- Series P ackage He at Pumps 1. All models fe ature Copeland ® Scr oll ® compressors offering maximum r eliabilit y , ef ficiency , and quiet operati on. 2. One-piece top o ver the indoor se ction with drip lip, dra wn painted b ase pan, and 1 " [25.4 mm] raised fl anges for s upply/re ...

  • Rheem RJNA Series - page 5

    5 MODEL IDENTIFICA TION—RJNA- SERIES R JNA—A0 3 6JK 0 0 0 Electric Heat 000 = No Resistance Hea t 010 = 10 kW Resistance Hea t 015 = 15 kW Resistance Hea t 020 = 20 kW Resistance Hea t Drive P ackage K = Direct Driv e L = Belt Driv e M = Belt Driv e—High Static Electrical Designation J = 208-230 V , 1 PH, 60 Hz C = 208-230 V , 3 PH, 60 Hz D = ...

  • Rheem RJNA Series - page 6

    6 OPTIONS—RJNA- SERIES Option Code Low Ambient Reduced Height Baserails AA Side Flow AD AF x AK x Hail Guard x x BD x x CK x x x BX x AL x No Options Freeze Stat Time Delay x BS x F ACT OR Y I NST ALLED OPTION CODES FOR RJNA (3-5 T on) [1 0.6- 1 7 .6 kW] (A036, A042, A0 48, A060) Example: RJNA-A060CK000 XX X (where XX is factory installed option) ...

  • Rheem RJNA Series - page 7

    7 GENERAL DA T A—RJNA- SERIES Model RJNA- Series A036CK A036CL A036CM A036DK Cooling Performance 1 Gross Cooling Capacity Btu [kW] 37,600 [11] 37,600 [11] 37,600 [11] 37,600 [11] EER/SEER 2 11.6/13 11.6/13 11.6/13 11.6/13 Nominal CFM/ARI Rated CFM [L/s] 1200/1200 [566/566] 1200/1200 [566/566] 1200/1200 [566/566] 1200/1200 [566/566] ARI Net Coolin ...

  • Rheem RJNA Series - page 8

    8 GENERAL DA T A—RJNA- SERIES Model RJNA- Series A036DL A036DM A036JK A042CK Cooling Performance 1 Gross Cooling Capacity Btu [kW] 37,600 [11] 37,600 [11] 37,600 [11] 42,500 [12.5] EER/SEER 2 11.6/13 11.6/13 11.6/13 11.8/13 Nominal CFM/ARI Rated CFM [L/s] 1200/1200 [566/566] 1200/1200 [566/566] 1200/1200 [566/566] 1400/1400 [661/661] ARI Net Cool ...

  • Rheem RJNA Series - page 9

    9 GENERAL DA T A—RJNA- SERIES Model RJNA- Series A042CL A042CM A042DK A042DL Cooling Performance 1 Gross Cooling Capacity Btu [kW] 42,500 [12.5] 42,500 [12.5] 42,500 [12.5] 42,500 [12.5] EER/SEER 2 11.8/13 11.8/13 11.8/13 11.8/13 Nominal CFM/ARI Rated CFM [L/s] 1400/1400 [661/661] 1400/1400 [661/661] 1400/1400 [661/661] 1400/1400 [661/661] ARI Ne ...

  • Rheem RJNA Series - page 10

    10 GENERAL DA T A—RJNA- SERIES Model RJNA- Series A042DM A042JK A048CK A048CL Cooling Performance 1 Gross Cooling Capacity Btu [kW] 42,500 [12.5] 42,500 [12.5] 49,500 [14.5] 49,500 [14.5] EER/SEER 2 11.8/13 11.8/13 11.65/13 11.65/13 Nominal CFM/ARI Rated CFM [L/s] 1400/1400 [661/661] 1400/1400 [661/661] 1600/1600 [755/755] 1600/1600 [755/755] ARI ...

  • Rheem RJNA Series - page 11

    11 GENERAL DA T A—RJNA- SERIES Model RJNA- Series A048CM A048DK A048DL A048DM Cooling Performance 1 Gross Cooling Capacity Btu [kW] 49,500 [14.5] 49,500 [14.5] 49,500 [14.5] 49,500 [14.5] EER/SEER 2 11.65/13 11.65/13 11.65/13 11.65/13 Nominal CFM/ARI Rated CFM [L/s] 1600/1600 [755/755] 1600/1600 [755/755] 1600/1600 [755/755] 1600/1600 [755/755] A ...

  • Rheem RJNA Series - page 12

    12 GENERAL DA T A—RJNA- SERIES Model RJNA- Series A048JK A060CK A060CL A060CM Cooling Performance 1 Gross Cooling Capacity Btu [kW] 49,500 [14.5] 63,500 [18.6] 64,000 [18.8] 64,000 [18.8] EER/SEER 2 11.65/13 11.55/13 11.55/13 11.55/13 Nominal CFM/ARI Rated CFM [L/s] 1600/1600 [755/755] 2000/2000 [944/944] 2000/2000 [944/944] 2000/2000 [944/944] A ...

  • Rheem RJNA Series - page 13

    13 GENERAL DA T A—RJNA- SERIES Model RJNA- Series A060DL A060DM A060JK Cooling Performance 1 Gross Cooling Capacity Btu [kW] 64,000 [18.8] 64,000 [18.8] 63,500 [18.6] EER/SEER 2 11.55/13 11.55/13 11.55/13 Nominal CFM/ARI Rated CFM [L/s] 2000/2000 [944/944] 2000/2000 [944/944] 2000/2000 [944/944] ARI Net Cooling Capacity Btu [kW] 61,500 [18] 61,50 ...

  • Rheem RJNA Series - page 14

    14 GENERAL DA T A—RJNA- SERIES NOTES: 1 . Cooling Pe r forma nce is rated a t 95° F ambient, 80° F entering dry bulb, 67 ° F entering we t bulb. Gross cap acit y does not include the effect of f an motor he at. ARI capacity is net and include s the ef f ect of fan mot or heat. Units ar e suitable for opera tion to  20% of nominal cfm. Units ...

  • Rheem RJNA Series - page 15

    COOLING PERFORMANCE D A T A—RJNA-A036 HEA TI NG PERF ORMANCE D A T A—RJNA-A036 DR —Depression ratio dbE —Entering air dr y bulb wbE—Enter ing air wet bulb T ot al —T ot al capacit y x 1 0 00 BTUH Sens —Sensible capacit y x 1 0 00 BTUH Power—K W input NOTES: ➀ When the entering air dr y bulb is other than 80°F [27°C], adjust the ...

  • Rheem RJNA Series - page 16

    COOLING PERFORMANCE D A T A—RJNA-A0 42 HEA TI NG PERF ORMANCE D A T A—RJNA-A042 DR —Depression ratio dbE —Entering air dr y bulb wbE—Enter ing air wet bulb T ot al —T ot al capacit y x 1 0 00 BTUH Sens —Sensible capacit y x 1 0 00 BTUH Power—K W input NOTES: ➀ When the entering air dr y bulb is other than 80°F [27°C], adjust the ...

  • Rheem RJNA Series - page 17

    COOLING PERFORMANCE D A T A—RJNA-A0 48 DR —Depression ratio dbE —Entering air dr y bulb wbE—Enter ing air wet bulb T ot al —T ot al capacit y x 1 0 00 BTUH Sens —Sensible capacit y x 1 0 00 BTUH Power—K W input NOTES: ➀ When the entering air dr y bulb is other than 80°F [27°C], adjust the sensible capacit y from the table by addin ...

  • Rheem RJNA Series - page 18

    COOLING PERFORMANCE D A T A—RJNA-A060 HEA TI NG PERF ORMANCE D A T A—RJNA -A060 DR —Depression ratio dbE —Entering air dr y bulb wbE—Enter ing air wet bulb T ot al —T ot al capacit y x 1 0 00 BTUH Sens —Sensible capacit y x 1 0 00 BTUH Power—K W input NOTES: ➀ When the entering air dr y bulb is other than 80°F [27°C], adjust the ...

  • Rheem RJNA Series - page 19

    External Static Pressure—Inches W .C. [kPa] CFM [L/s] Air Delivery/RPM/Watts—208 Volts Side Discharge—W et Coil 4.0 [14.07] Low Blower Size/ Motor HP [w] & # of Speeds Nominal Cooling Capacity T ons [kW] 3.5 [12.30] Factory Motor Speed 1400/1800 Manufacturer Recommended Air -Flow Range (Min/Max) CFM Motor Speed 10x10 1/2 HP [373] 3 Speed ...

  • Rheem RJNA Series - page 20

    20 AIRFLOW PERFORMANCE—RJNA- SERIES 825 Models RJNA-A036 [10.55 kW] & A042 [12.31 kW]—Heat Pump (13 SEER) External Static Pressure—Inches of Water [kPa] 0.1 [.02] 0.2 [.05] 0.3 [.07] 0.4 [.10] 0.5 [.12] 0.6 [.15] 0.7 [.17] 0.8 [.20] 0.9 [.22] 1.0 [.25] 1.1 [.27] 1.2 [.30] 1.3 [.32] 1.4 [.35] 1.5 [.37] RPM W RPM W RPM W RPM W RPM W RPM W R ...

  • Rheem RJNA Series - page 21

    BEL T -DRIVE AI RFL OW P ERFORMANCE COMPONENT AIR RESI ST AN CE NOTES: 1 . Performance shown with dr y coil, st andard 1" [25.4 mm] filters & side discharge. Add component resistance to determine tot al E.S.P . 2. St andard CFM @ .075 lbs./cu . f t. 3. Motor ef ficiency = 80% 4. BHP = Watt s x Motor Eff. 74 6 [ ] Des igna tes Met ric C onv ...

  • Rheem RJNA Series - page 22

    ELECTRICAL DA T A – RJNA SERIES Minimum Circuit Ampacity 19/19 Unit Information Unit Operating Voltage Range 187-253 Minimum Overcurrent Protection Device Size 25/25 Maximum Overcurrent Protection Device Size 25/25 Compressor Motor No. 1 Volts 208/230 Phase 3 HP 2.5 RPM 3450 Amps (RLA) 9.6/9.6 Amps (LRA) 77/77 Condenser Motor No. 1 Volts 208/230 ...

  • Rheem RJNA Series - page 23

    ELECTRICAL DA T A – RJNA SERIES Minimum Circuit Ampacity Minimum Overcurrent Protection Device Size 22/22 25/25 Maximum Overcurrent Protection Device Size 30/30 Compressor Motor No. 1 Volts 208/230 Phase 3 HP 3.5 RPM 3450 Amps (RLA) 12.4/12.4 Amps (LRA) Unit Information Unit Operating Voltage Range 88/88 187-253 Condenser Motor No. 1 Volts 208/23 ...

  • Rheem RJNA Series - page 24

    24 UNITS WITH HEA TER KITS—RJNA- SERIES * A10C+ * A10C+ 7.2/9.6 24.56/32.75 20.0/23.1 44/48 45/45 50/50 * A20C+ 14.4/19.2 49.13/65.51 40.1/46.2 69/76 70/70 80/80 * A12C+ 8.4/11.2 28.66/38.21 23.4/27.0 48/52 50/50 60/60 * A15C+ 10.8/14.4 36.84/49.13 30.1/34.7 56/62 60/60 70/70 *A21C+ 14.4/19.2 49.13/65.51 40.1/46.2 69/76 70/70 80/80 7.2/9.6 A036CK ...

  • Rheem RJNA Series - page 25

    25 UNITS WITH HEA TER KITS—RJNA- SERIES * A10C+ * A10C+ 7.2/9.6 24.56/32.75 20.0/23.1 43/47 45/45 50/50 * A20C+ 14.4/19.2 49.13/65.51 40.1/46.2 68/75 70/70 80/80 * A12C+ 8.4/11.2 28.66/38.21 23.4/27.0 47/51 50/50 60/60 * A15C+ 10.8/14.4 36.84/49.13 30.1/34.7 55/61 60/60 70/70 * A21C+ 14.4/19.2 49.13/65.51 40.1/46.2 68/75 70/70 80/80 7.2/9.6 A036C ...

  • Rheem RJNA Series - page 26

    26 UNITS WITH HEA TER KITS—RJNA- SERIES * A10C+ * A10C+ 7.2/9.6 24.56/32.75 20.0/23.1 44/48 45/45 50/50 * A20C+ 14.4/19.2 49.13/65.51 40.1/46.2 69/76 70/70 80/80 * A12C+ 8.4/11.2 28.66/38.21 23.4/27.0 48/52 50/50 60/60 * A15C+ 10.8/14.4 36.84/49.13 30.1/34.7 56/62 60/60 70/70 * A21C+ 14.4/19.2 49.13/65.51 40.1/46.2 69/76 70/70 80/80 7.2/9.6 A036C ...

  • Rheem RJNA Series - page 27

    27 UNITS WITH HEA TER KITS—RJNA- SERIES * A10D+ * A10D+ 9.6 32.75 11.6 24 25 25 * A20D+ 19.2 65.51 23.1 38 40 40 * A12D+ 11.2 38.21 13.5 26 30 30 * A15D+ 14.4 49.13 17.3 31 35 35 *A21D+ 19.2 65.51 23.1 38 40 40 9.6 A036DK No Heat — — — 9 15 15 32.75 11.6 24 * A06D+ 5.6 19.10 6.7 18 20 20 25 25 * A20D+ 19.2 65.51 23.1 39 40 40 * A12D+ 11.2 3 ...

  • Rheem RJNA Series - page 28

    28 UNITS WITH HEA TER KITS—RJNA- SERIES * A10D+ * A10D+ 9.6 32.75 11.6 24 25 25 * A20D+ 19.2 65.51 23.1 38 40 40 * A12D+ 11.2 38.21 13.5 26 30 30 * A15D+ 14.4 49.13 17.3 31 35 35 *A21D+ 19.2 65.51 23.1 38 40 40 9.6 A036DL No Heat — — — 9 15 15 32.75 11.6 24 * A06D+ 5.6 19.10 6.7 18 20 20 25 25 * A20D+ 19.2 65.51 23.1 39 40 40 * A12D+ 11.2 3 ...

  • Rheem RJNA Series - page 29

    29 UNITS WITH HEA TER KITS—RJNA- SERIES * A10D+ * A10D+ 9.6 32.75 11.6 24 25 25 * A20D+ 19.2 65.51 23.1 38 40 40 * A12D+ 11.2 38.21 13.5 26 30 30 * A15D+ 14.4 49.13 17.3 31 35 35 *A21D+ 19.2 65.51 23.1 38 40 40 9.6 A036DM No Heat — — — 9 15 15 32.75 11.6 24 * A06D+ 5.6 19.10 6.7 18 20 20 25 25 * A20D+ 19.2 65.51 23.1 39 40 40 * A12D+ 11.2 3 ...

  • Rheem RJNA Series - page 30

    A036JK No Heat — — — 25/25 30/35 30/35 * A10J+ 7.2/9.6 24.56/32.75 34.7/40.0 69/75 70/70 80/80 * A06J+ 4.2/5.6 14.33/19.10 20.2/23.3 51/55 60/60 60/60 *A11J+ 7.2/9.6 24.56/32.75 34.7/40.0 69/75 70/70 80/80 * A20J+ 14.4/19.2 49.13/65.51 69.3/80.0 112/125 125/125 125/125 * A12J+ 8.4/11.2 28.66/38.21 40.4/46.7 76/84 80/80 90/90 * A15J+ 10.8/14.4 ...

  • Rheem RJNA Series - page 31

    UNIT D IMENS IONS P A CKA GE HEA T PUMPS [ ] Des igna tes Me tric C onv ers ions 31 UNIT DIMENSIONS—RJNA- SERIES ...

  • Rheem RJNA Series - page 32

    UNIT D IMENS IONS P A CKA GE HEA T PUMPS [ ] Des igna tes Me tric C onv ers ions BOT TOM VIEW 32 UNIT DIMENSIONS—RJNA- SERIES ...

  • Rheem RJNA Series - page 33

    SELECTION PR OCEDURE 1 . Determine cooling and heating requirements at design conditions. Example: T otal cooling capacity ............43,600 BTUH [1 2.78 kW] Sensible cooling capacity ......34,00 0 BTUH [9.96 kW] Condenser ent ering air ..........95°F [35°C] E vaporat or entering air ..........63°F [1 7°C] wb/76°F [2 4°C] db Indoor air flow ...

  • Rheem RJNA Series - page 34

    Accessory Description Model Application 3 to 5 T on [10.6 to 17.6 kW] Accessory Model No. 3 to 5 T on [10.6 to 17.6 kW] Roofcurb Adapters RJNA- RXRX-BBCDB21 RXRX-BBCDB22 RXRX-BBCDB23 Economizer with Single Enthalpy ➀ RJNA- RXRD-KECM3 Time Delay RJNA- RXMD-B01 Low Ambient Control to 0°F [-18°C] RJNA- RXPZ-C01 Fresh Air Damper Manual RJNA- RXRF-F ...

  • Rheem RJNA Series - page 35

    Roofcurb Adapters Old Models OLD CURB MODEL ROOFCURB ADAPTER NEW MODEL MEDIUM C ABINET (3 TON [1 1 kW]) 21 SE RI ES RXP A-CA2 1 (1) RXRA-DB21 (2) RXRX -BBCDB21 RJNA (-)SNC, (-)SND, (-)SNE (-)RGE, (-)RGF , (-)RGG (-)PNC, (-)PND EX TRA LARGE CABINET (3.5-5 TON [1 2-1 8 kW]) 23 SE RIE S RXP A-CA23 (1) RXRA-DB23 (2) RXRX -BBCDB23 (-)SNC, (-)SND, (-)SNE ...

  • Rheem RJNA Series - page 36

    ROOFCURBS (F ull Perimeter) ■ Rheem’s ne w roofcurb design can be utiliz ed on 3 through 5 t on [1 0.6- 1 7 .6 kW] models. ■ T wo a vailable heights (1 4" [356 mm] and 2 4" [6 1 0 mm]) for ALL models. ■ Quick assembl y corners for simple and f ast assembl y . ■ Opening pro vided in bottom pan to ma tch the “Thru the Curb” el ...

  • Rheem RJNA Series - page 37

    [ ] Designates Metric Conversions ■ Fea tu re s Honeywell Cont rols ■ A vailable fact or y installed or field accessory ■ Gear Driv en Direct Drive Actua tor ■ F ully Modulating (0- 1 00%) ■ Low L eakage D ampers ■ Horiz ontal or Downflow Applica tions ■ Slip-In Design for E asy Installa tions ■ Plug-In P olarized 1 2-pin Electrical ...

  • Rheem RJNA Series - page 38

    Illustration ST -A0903-01 INTEGRAL PO WER EXHA UST FOR EC ONOM IZER (FIELD I NST ALLED ONL Y) RXRX -BFF0 4C—3-5 T on [10.6- 1 7 .6 kW] Models 208-230 V , 1 PH, 60 Hz ■ For RXRD-KECM3 E conomiz er ■ Downflow or hori zontal applica tions ■ Requires s eparat e power supply w ith disconnect ■ Adjustable s witch on economiz er , factory preset ...

  • Rheem RJNA Series - page 39

    DUCT AD APTERS (3 TO 5 TON [1 0.6 TO 1 7 .6 kW] MODELS) Rectangular to Round T ransitions (Downflow) RXMC-CB03 – 1 8" [457 mm] Round A vailable in 1 8 inch round to fit all units. Dr ops into a nd secures to RXK G- Series Roofcurbs. For use with Concentric Diffusers. [ ] Designates Metric Conversions 39 ACCESSORIES ...

  • Rheem RJNA Series - page 40

    SID E DISCHARGE CONCENTR IC DI FFUSER RXRN -F A60 (3 to 5 T on [10.6 t o 1 7 .6 kW] Models) For Use With Duct A dapter (RXMC) Model No. A B C D E F G H I J K Duct Size RXRN-F A60 47 5 / 8 " [1210 mm] 23 5 / 8 " [600 mm] 11 3 / 8 " [289 mm] 21 1 / 2 " [546 mm] 45 1 / 2 " [1156 mm] 22 1 / 2 " [572 mm] 11 1 / 2 " [29 ...

  • Rheem RJNA Series - page 41

    FLUSH MOUNT CONCENTRIC D IFFUSER RXRN -F A70 (3 to 5 T on [10.6 t o 1 7 .6 kW] Models) For Use With Duct A dapter (RXMC) DIMENSION AL D A T A ENGI NEERIN G D A T A Model No. A B C D E F G H Duct Size RXRN-F A70 47 5 / 8 " [1210 mm] 23 5 / 8 " [600 mm] 13 1 / 2 " [343 mm] 21" [533 mm] 45" [1143 mm] 22 1 / 2 " [572 mm] 1 ...

  • Rheem RJNA Series - page 42

    THERMOST A TS — P A CKA GE HE A T PUMPS RECOMMENDED HEA T P UMP THERM OST A T S Units Without Economizer Honeywell T7300A1005 T8611R1166 T874R T841A1209 T874G1881 Q674F1360 Included Q674F1360 Included Q7300C1006 1 1 1 1 1 2 2 2 2 2 Manufacturer Model Sub-Base Cooling Stages Heating Stages T8141A Included 1 2 General Electric 3AA T86B8A2 Included ...

  • Rheem RJNA Series - page 43

    43 WIRING SCHEMA TICS—RJNA- SERIES ...

  • Rheem RJNA Series - page 44

    44 WIRING SCHEMA TICS—RJNA- SERIES ...

  • Rheem RJNA Series - page 45

    45 WIRING SCHEMA TICS—RJNA- SERIES ...

  • Rheem RJNA Series - page 46

    46 WIRING SCHEMA TICS—RJNA- SERIES ...

  • Rheem RJNA Series - page 47

    47 WIRING SCHEMA TICS—RJNA- SERIES ...

  • Rheem RJNA Series - page 48

    48 WIRING SCHEMA TICS—RJNA- SERIES ...

  • Rheem RJNA Series - page 49

    49 WIRING SCHEMA TICS—RJNA- SERIES ...

  • Rheem RJNA Series - page 50

    GENERAL TERMS OF LI MITED W ARR ANT Y Before proceeding with installation, refer to installation instructions packaged with each model, as well as complying with all Federal, State, Pro vincial, and Local codes, regulations, and practices. RHEEM AIR CONDITIONING DIVISION 5600 Old Greenwood Road, Fort Smith, Arkansas 72908 “In keeping with its pol ...

Fabricant Rheem Catégorie Electric Heater

Les documents que nous recevons du fabricant de l'appareilRheem RJNA Series peuvent être divisés en plusieurs groupes. Ceux-ci sont, entre autres:
- dessins techniques Rheem
- manuels d’utilisations RJNA Series
- fiches produit Rheem
- dépliants
- ou étiquettes-énergie Rheem RJNA Series
Tous sont importants, mais les informations les plus importantes du point de vue de l'utilisation de l'appareil se trouvent dans le manuel d’utilisation Rheem RJNA Series.

Un groupe de documents appelé manuels d’utilisation est également divisé en types plus spécifiques, tels que: Manuels d’installation Rheem RJNA Series, manuels d’entretien, brefs manuels ou manuels de l’utilisateur Rheem RJNA Series. Selon vos besoins, vous devriez chercher le document dont vous avez besoin. Sur notre site, vous pouvez voir le manuel le plus populaire d’utilisation du produit Rheem RJNA Series.

Manuels d’utilsiation similaires

Manuel d’utilisation complet de l’appareil Rheem RJNA Series, quelle devrait-elle être?
Le manuel d’utilisation, également appelé le mode d’emploi, ou tout simplement le manuel, est un document technique destiné à aider à utiliser Rheem RJNA Series par les utilisateurs. Des manuels sont généralement écrits par un rédacteur technique, mais dans un langage accessible à tous les utilisateurs Rheem RJNA Series.

Le manuel d’utilisation complet Rheem, devrait inclure plusieurs éléments de base. Certains d'entre eux sont moins importants, tels que: la couverture / page de titre ou pages d'auteur. Cependant, la partie restante, devrait nous fournir des informations importantes du point de vue de l'utilisateur.

1. Introduction et des conseils sur la façon d'utiliser le manuel Rheem RJNA Series - Au début de chaque manuel, nous devrions trouver des indices sur la façon d'utiliser le document. Il doit contenir des informations sur l'emplacement de la table des matières Rheem RJNA Series, FAQ ou des problèmes les plus fréquents - les points qui sont les plus souvent recherchés par les utilisateurs de chaque manuel
2. Table des matières - index de tous les conseils pour lRheem RJNA Series qui peuvent être trouvés dans le document courant
3. Conseils sur la façon d'utiliser les fonctions de base de l’appareil Rheem RJNA Series - qui devraient nous aider dans les premières étapes lors de l'utilisation Rheem RJNA Series
4. Troubleshooting - séquence systématique des activités qui nous aideront à diagnostiquer et ensuite résoudre les principaux problèmes de Rheem RJNA Series
5. FAQ - questions fréquemment posées
6. Détails du contact Informations sur l'endroit où chercher le contact avec le fabricant / service Rheem RJNA Series dans un pays donné, si le problème ne peut être résolu par nous-mêmes.

Avez-vous une question à propos de Rheem RJNA Series?

Utiliser le formulaire ci-dessous

Si vous n’avez pas résolu votre problème avec Rheem RJNA Series, avec l'aide du manuel que vous avez trouvé, posez une question en utilisant le formulaire ci-dessous. Si un utilisateur a eu un problème similaire avec Rheem RJNA Series il est probable qu’il a envie de partager la façon de le résoudre.

Réécrire le texte de l'image

Commentaires (0)