    TECHNICAL GUIDE AFFINITY SPLIT -SYSTEM HEA T PUMPS 15 SEER – R-410A MODELS: YZE024THRU 060 (2 THRU 5 NOMINAL TONS) Due to continuous pr oduct improvement, spec ifications are subject to change without notice. Visit us on the web at www .york.com Additional rati ng information can be foun d at www .ari.org/aridirectory LISTED ISO 9001 Certified Qu ...

  • York YZE024 THRU 060 - page 2

    2 Johnson Controls Unitary Products 246750-YTG-L-0408 All dimensions are in inches. They are subject to change without notice. Certified dimensions wil l be provided upon request. * Adapter fitting required for 1-1/8” line set. Physical and Electrical Dat a MODEL YZE0241 1 YZE0361 1 YZE0481 1 YZE0601 1 Unit Supply V oltage 208-230V , 1 φ, 60Hz N ...

  • York YZE024 THRU 060 - page 3

    Johnson Controls Unitary Produ cts 3 246750-YTG-L-0408 PROCEDURES: 1. Unit factory charge listed on the unit nameplate includes refri gerant for the condenser , the smallest evaporator and 15 feet of intercon- necting line tubing. 2. V erify the TXV and additional charge requ ired for specific evaporator coil in th e system using the above table. 3 ...

  • York YZE024 THRU 060 - page 4

    4 Johnson Controls Unitary Products 246750-YTG-L-0408 COOLING CAP ACITY - Wi th Air Handler Coils UNIT MODEL AIR HANDLER COIL 1 MODEL COOLING MODEL W ST AGE RA TED CFM NET MBH SENSIBL E SEER EER YZE0241 1 A V24 17 – 1 535 18.6 13.6 15.00 13.00 2 800 24.0 18.6 12.50 A V36 17 – 1 535 18.6 13.6 15.00 13.00 2 800 24.0 18.6 12.50 MV12B 17 FC/MC30B 1 ...

  • York YZE024 THRU 060 - page 5

    Johnson Controls Unitary Produ cts 5 246750-YTG-L-0408 COOLING CAP ACITY - With V a riable Speed Furnaces UNIT MODEL V ARIABLE SPEED FURNACE MODEL COIL MODEL 1 W COOLING ST AGE RA TED CFM NET MBH SEER EER TOT AL SENSIBLE YZE0241 1 PV8*A12 FC/MC/PC/UC30A 14 1 430 17.3 1 1.5 14.00 12.60 2 750 23.0 18.2 12.00 PV9*A12 FC/MC/PC30A 14 1 625 18.5 14.4 14. ...

  • York YZE024 THRU 060 - page 6

    6 Johnson Controls Unitary Products 246750-YTG-L-0408 YZE0361 1 P(C,V)9*C16 FC/MC/PC/UC48C 21 1 640 24.2 16.2 15.50 12.70 2 1200 35.2 25.1 12.00 PV8*C16 FC/MC/PC/UC48C 21 1 780 25.0 18.9 15.00 12.85 2 1200 34.8 26.8 12.00 PV8*C20 FC/MC/PC/UC48C 21 1 800 25.2 19.1 15.25 12.90 2 1200 35.0 26.8 12.00 P(C,V)9*D20 FC/MC/PC/UC48D 24 1 770 25.0 18.8 15.50 ...

  • York YZE024 THRU 060 - page 7

    Johnson Controls Unitary Produ cts 7 246750-YTG-L-0408 HEA TIN G CAP ACITY - With Air Handler Coils UNIT MODEL AIR HANDLER MODEL COIL 1 MODEL HEA TING ST AGE RA TED CFM NET MBH HSPF COP @ 47 47 OD 17 OD YZE0241 1 A V24 - 1 650 19.0 - - 3.30 2 775 24.0 15.6 8.25 3.36 2 650 23.2 14.6 8.05 3.12 A V36 - 1 650 19.0 - - 3.30 2 775 24.0 15.6 8.25 3.36 2 6 ...

  • York YZE024 THRU 060 - page 8

    8 Johnson Controls Unitary Products 246750-YTG-L-0408 ** Refer to Q uick Selectio n Char t for specific furnace match-up. YZE0601 1 A V60 - 1 1200 37.6 - - 3.26 2 1900 55.0 32 .4 8.05 3.50 2 1200 50.0 29 .8 7.90 3.22 F2FV060 - 1 1200 37.6 - - 3.26 2 1900 54.0 32 .2 8.00 3.50 2 1200 50.0 29 .8 7.90 3.22 MV20D FC/MC60D 1 1200 37. 6 - - 3.26 2 1900 54 ...

  • York YZE024 THRU 060 - page 9

    Johnson Controls Unitary Produ cts 9 246750-YTG-L-0408 YZE0361 1 P(C,V)9*B12 FC/MC/PC3 5B 17 1 650 2 3.0 - - 3.54 2 1200 33.0 20.8 8.50 3.70 2 650 29.4 19.6 8.35 3.30 PV8*B16 FC/MC/PC35B 17 1 650 23.0 - - 3.54 2 1200 33.0 21.0 8.50 3.70 2 650 29.4 19.6 8.35 3.30 P(C,V)9*C16 FC/MC/PC35C 21 1 650 23.0 - - 3.54 2 1200 33.0 21.0 8.50 3.70 2 650 29.4 19 ...

  • York YZE024 THRU 060 - page 10

    10 Johnson Controls Unitary Products 246750-YTG-L-0408 YZE0481 1 PV8*C20 FC/PC/UC60C 21 1 860 31.2 - - 3.56 2 1610 48.0 27.8 8.35 3.96 2 860 44.5 26.2 8.30 3.66 P(C,V)9*C20 FC /PC/UC60C 21 1 870 31.2 - - 3.56 2 1590 48.0 27.8 8.40 3.96 2 870 44.5 26.2 8.30 3.66 P(C,V)9*D20 FC/MC/PC/UC60D 24 1 855 31.2 - - 3.56 2 1620 48.0 27.8 8.40 3.96 2 855 44.5 ...

  • York YZE024 THRU 060 - page 11

    Johnson Controls Unitary Produ cts 11 246750-YTG-L-0408 ACCESSORIES* TXV Kits - 1 TVM9 series thermal expansion val ves precisely meter refrigerant for optimu m performance. Bonnet Sensor (2SB137 00124) - The bonnet sensor is u sed to sense plenum temperatur e, and is optional with a gas or oi l back-up heat source. Compatible only with 13 SEER and ...

  • York YZE024 THRU 060 - page 12

    12 Johnson Controls Unitary Products 246750-YTG-L-0408 Multipliers for determining th e performance with other indoor sec tions . NOTE: For dry bulb temperatures dif f erent than those listed (bet ween 73-87 F), sensible capacity increa se s by 1060 BTUH per 100 0 CFM per degree above the listed temperatu re and decre ases by 1060 BTUH per 1000 CFM ...

  • York YZE024 THRU 060 - page 13

    Johnson Controls Unitary Produ cts 13 246750-YTG-L-0408 Multipliers for determining the performance with ot her indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (bet ween 73-87 F), sensible capacity increases by 1060 BTUH per 100 0 CFM per degree above the listed temperature and decre ases by 1060 BTUH per 10 00 CFM per ...

  • York YZE024 THRU 060 - page 14

    14 Johnson Controls Unitary Products 246750-YTG-L-0408 Multipliers for determining th e performance with other indoor sec tions . NOTE: For dry bulb temperatures dif f erent than those listed (bet ween 73-87 F), sensible capacity increa se s by 1060 BTUH per 100 0 CFM per degree above the listed temperatu re and decre ases by 1060 BTUH per 1000 CFM ...

  • York YZE024 THRU 060 - page 15

    Johnson Controls Unitary Produ cts 15 246750-YTG-L-0408 Multipliers for determining the performance with ot her indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (bet ween 73-87 F), sensible capacity increases by 1060 BTUH per 100 0 CFM per degree above the listed temperature and decre ases by 1060 BTUH per 10 00 CFM per ...

  • York YZE024 THRU 060 - page 16

    16 Johnson Controls Unitary Products 246750-YTG-L-0408 Multipliers for determining th e performance with other indoor sec tions . NOTE: For dry bulb temperatures dif f erent than those listed (bet ween 73-87 F), sensible capacity increa se s by 1060 BTUH per 100 0 CFM per degree above the listed temperatu re and decre ases by 1060 BTUH per 1000 CFM ...

  • York YZE024 THRU 060 - page 17

    Johnson Controls Unitary Produ cts 17 246750-YTG-L-0408 Multipliers for determining the performance with ot her indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (bet ween 73-87 F), sensible capacity increases by 1060 BTUH per 100 0 CFM per degree above the listed temperature and decre ases by 1060 BTUH per 10 00 CFM per ...

  • York YZE024 THRU 060 - page 18

    18 Johnson Controls Unitary Products 246750-YTG-L-0408 Multipliers for determining th e performance with other indoor sec tions . NOTE: For dry bulb temperatures dif f erent than those listed (bet ween 73-87 F), sensible capacity increa se s by 1060 BTUH per 100 0 CFM per degree above the listed temperatu re and decre ases by 1060 BTUH per 1000 CFM ...

  • York YZE024 THRU 060 - page 19

    Johnson Controls Unitary Produ cts 19 246750-YTG-L-0408 Multipliers for determining the performance with ot her indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (bet ween 73-87 F), sensible capacity increases by 1060 BTUH per 100 0 CFM per degree above the listed temperature and decre ases by 1060 BTUH per 10 00 CFM per ...

  • York YZE024 THRU 060 - page 20

    20 Johnson Controls Unitary Products 246750-YTG-L-0408 Multipliers for determining the perfo rman ce with other indoor section. NOTE: KW RA TING IS FOR OUT DOOR AND INDOOR UNITS. LOW CFM HEA TING PERFORMA NCE DA T A - LOW CFM 1-ST AGE OPERA TION OUTDOOR UNIT MODEL NO. YZE0241 1 INDOOR COIL MODEL NO . FC/MC/PC36B + MV12B AIR TEMP . ENTERING OUTDOOR ...

  • York YZE024 THRU 060 - page 21

    Johnson Controls Unitary Produ cts 21 246750-YTG-L-0408 Multipliers for de termining the performa nce with other i ndoor section. NOTE: KW RA TING IS FOR OU TDOOR AND INDOOR UNITS. HIGH CFM HEA TIN G PERFOR MA NCE DA T A - HIGH CFM 2-ST AGE OPERA TION OUTDOOR UNIT MODEL NO. YZE0241 1 INDOOR COIL MODEL NO. FC/MC/PC36B + MV12B AIR TEMP . ENTERING OUT ...

  • York YZE024 THRU 060 - page 22

    22 Johnson Controls Unitary Products 246750-YTG-L-0408 Multipliers for determining th e performance with other indoor sec tions . NOTE: KW RA TING IS FOR OUT DOOR AND INDOOR UNITS. LOW CFM HEA TING PERFORMA NCE DA T A - LOW CFM 1-ST AGE OPERA TION OUTDOOR UNIT MODEL NO. YZE0361 1 INDOOR COIL MODEL NO . FC/MC/PC48C + MV16C AIR TEMP . ENTERING OUTDOO ...

  • York YZE024 THRU 060 - page 23

    Johnson Controls Unitary Produ cts 23 246750-YTG-L-0408 Multipliers for de termining the performa nce with other i ndoor sections. NOTE: KW RA TING IS FOR OU TDOOR AND INDOOR UNITS. HIGH CFM HEA TIN G PERFOR MA NCE DA T A - HIGH CFM 2-ST AGE OPERA TION OUTDOOR UNIT MODEL NO. YZE0361 1 INDOOR COIL MODEL NO. FC/MC/PC48C + MV16C AIR TEMP . ENTERING OU ...

  • York YZE024 THRU 060 - page 24

    24 Johnson Controls Unitary Products 246750-YTG-L-0408 Multipliers for determining the perfo rman ce with other indoor sections. NOTE: KW RA TING IS FOR OUT DOOR AND INDOOR UNITS. LOW CFM HEA TING PERFORMA NCE DA T A - LOW CFM 1-ST AGE OPERA TION OUTDOOR UNIT MODEL NO. YZE0481 1 INDOOR COIL MODEL NO . FC/MC/PC60D + MV20D AIR TEMP . ENTERING OUTDOOR ...

  • York YZE024 THRU 060 - page 25

    Johnson Controls Unitary Produ cts 25 246750-YTG-L-0408 Multipliers for de termining the performa nce with other i ndoor sections. NOTE: KW RA TING IS FOR OU TDOOR AND INDOOR UNITS. HIGH CFM HEA TIN G PERFOR MA NCE DA T A - HIGH CFM 2-ST AGE OPERA TION OUTDOOR UNIT MODEL NO. YZE0481 1 INDOOR COIL MODEL NO. FC/MC/PC60D + MV20D AIR TEMP . ENTERING OU ...

  • York YZE024 THRU 060 - page 26

    26 Johnson Controls Unitary Products 246750-YTG-L-0408 Multipliers for determining the perfo rman ce with other indoor sections. NOTE: KW RA TING IS FOR OUT DOOR AND INDOOR UNITS. LOW CFM HEA TING PERFORMA NCE DA T A - LOW CFM 1-ST AGE OPERA TION OUTDOOR UNIT MODEL NO. YZE0601 1 INDOOR COIL MODEL NO. MC61D + MV20D AIR TEMP . ENTERING OUTDOOR UNIT A ...

  • York YZE024 THRU 060 - page 27

    Johnson Controls Unitary Produ cts 27 246750-YTG-L-0408 Multipliers for de termining the performa nce with other i ndoor sections. NOTE: KW RA TING IS FOR OU TDOOR AND INDOOR UNITS. HIGH CFM HEA TIN G PERFOR MA NCE DA T A - HIGH CFM 2-ST AGE OPERA TION OUTDOOR UNIT MODEL NO. YZE0601 1 INDOOR COIL MODEL NO. MC61D + MV20D AIR TEMP . ENTERING OUTDOOR ...

  • York YZE024 THRU 060 - page 28

    Subject to change without notice. Printe d in U.S.A. 246750-YTG-L-0408 Copyright © 2008 by Johnson Controls, Inc. All rights reserved. Supersedes: 246750-YTG-K-0108 Johnson Controls Unit ary Products 5005 Y ork Drive Norman, OK 73069 NOTES ...

Fabricant York Catégorie Heat Pump

Les documents que nous recevons du fabricant de l'appareilYork YZE024 THRU 060 peuvent être divisés en plusieurs groupes. Ceux-ci sont, entre autres:
- dessins techniques York
- manuels d’utilisations YZE024 THRU 060
- fiches produit York
- dépliants
- ou étiquettes-énergie York YZE024 THRU 060
Tous sont importants, mais les informations les plus importantes du point de vue de l'utilisation de l'appareil se trouvent dans le manuel d’utilisation York YZE024 THRU 060.

Un groupe de documents appelé manuels d’utilisation est également divisé en types plus spécifiques, tels que: Manuels d’installation York YZE024 THRU 060, manuels d’entretien, brefs manuels ou manuels de l’utilisateur York YZE024 THRU 060. Selon vos besoins, vous devriez chercher le document dont vous avez besoin. Sur notre site, vous pouvez voir le manuel le plus populaire d’utilisation du produit York YZE024 THRU 060.

Manuels d’utilsiation similaires

Manuel d’utilisation complet de l’appareil York YZE024 THRU 060, quelle devrait-elle être?
Le manuel d’utilisation, également appelé le mode d’emploi, ou tout simplement le manuel, est un document technique destiné à aider à utiliser York YZE024 THRU 060 par les utilisateurs. Des manuels sont généralement écrits par un rédacteur technique, mais dans un langage accessible à tous les utilisateurs York YZE024 THRU 060.

Le manuel d’utilisation complet York, devrait inclure plusieurs éléments de base. Certains d'entre eux sont moins importants, tels que: la couverture / page de titre ou pages d'auteur. Cependant, la partie restante, devrait nous fournir des informations importantes du point de vue de l'utilisateur.

1. Introduction et des conseils sur la façon d'utiliser le manuel York YZE024 THRU 060 - Au début de chaque manuel, nous devrions trouver des indices sur la façon d'utiliser le document. Il doit contenir des informations sur l'emplacement de la table des matières York YZE024 THRU 060, FAQ ou des problèmes les plus fréquents - les points qui sont les plus souvent recherchés par les utilisateurs de chaque manuel
2. Table des matières - index de tous les conseils pour lYork YZE024 THRU 060 qui peuvent être trouvés dans le document courant
3. Conseils sur la façon d'utiliser les fonctions de base de l’appareil York YZE024 THRU 060 - qui devraient nous aider dans les premières étapes lors de l'utilisation York YZE024 THRU 060
4. Troubleshooting - séquence systématique des activités qui nous aideront à diagnostiquer et ensuite résoudre les principaux problèmes de York YZE024 THRU 060
5. FAQ - questions fréquemment posées
6. Détails du contact Informations sur l'endroit où chercher le contact avec le fabricant / service York YZE024 THRU 060 dans un pays donné, si le problème ne peut être résolu par nous-mêmes.

Avez-vous une question à propos de York YZE024 THRU 060?

Utiliser le formulaire ci-dessous

Si vous n’avez pas résolu votre problème avec York YZE024 THRU 060, avec l'aide du manuel que vous avez trouvé, posez une question en utilisant le formulaire ci-dessous. Si un utilisateur a eu un problème similaire avec York YZE024 THRU 060 il est probable qu’il a envie de partager la façon de le résoudre.

Réécrire le texte de l'image

Commentaires (0)