Manuel d’utilisation Lenox Elite Series X16 Air Conditioner Units

28 pages 0.84 mb
Télécharger

Aller à la page of 28

Summary
  • Lenox Elite Series X16 Air Conditioner Units - page 1

    1 1/10 506637−01 *2P1110* *P506637-01* Page 1  2010 Lennox Industries Inc. Dallas, T exas, USA RET AIN THESE INSTRUCTIONS FOR FUTURE REFERENCE These instructions are intended as a general guide and do not supersede local codes in any way . Consult authorities having jurisdiction before inst allation. W ARNING Improper installation, adjustment, ...

  • Lenox Elite Series X16 Air Conditioner Units - page 2

    Page 2 506637−01 1 1/10 Unit Dimensions − Inches (mm) ELECTRICAL INLETS SIDE VIEW SUCTION LINE CONNECTION LIQUID LINE CONNECTION 4−1/2" (108) 4−3/4" (121) TOP VIEW D G K J E F UNIT SUPPORT FEET XC14−024 T O −060 BASE WITH ELONGA TED LEGS H A B C Model Number A B C D E F G H J K XC16−024−230 39 (991) 30−1/2 ( 775) 35 (889 ...

  • Lenox Elite Series X16 Air Conditioner Units - page 3

    Page 3 XC16 SERIES T ypical Unit Part s Arrangement LIQUID LINE FIL TER DRIER (SINGLE FLOW) FIELD CONNECTION FOR LIQUID LINE SET LIQUID LINE SERVICE VA LV E SUCTION LINE SER VICE V AL VE FIELD CONNECTION FOR SUCTION LINE HIGH PRESSURE SWITCH (MANUAL RESET) (S4) COMPRESSOR HARNESS GROUND LUG SINGLE POLE CONT ACT OR (K1) DUAL RUN CAP ACIT OR (C12) CO ...

  • Lenox Elite Series X16 Air Conditioner Units - page 4

    Page 4 506637−01 1 1/10 W ARNING Electric Shock Hazard. Can cause injury or death. Unit must be grounded in accordance with national and local codes. Line volt age is present at all component s when unit is not in operation on units with single-pole contactors. Disconnect all remote electric power supplies before opening access panel. Unit may ha ...

  • Lenox Elite Series X16 Air Conditioner Units - page 5

    Page 5 XC16 SERIES (V AL VE STEM SHOWN CLOSED) INSERT HEX WRENCH HERE SERVICE PORT CORE SER VICE PORT CAP ANGLE−TYPE SERVICE V AL VE (FRONT−SEA TED CLOSED) SER VICE PORT CORE TO OUTDOOR UNIT STEM CAP (V AL VE STEM SHOWN OPEN) INSER T HEX WRENCH HERE TO INDOOR UNIT ANGLE−TYPE SERVICE VALVE (BACK−SEATED OPENED) BALL (SHOWN CLOSED) SER VICE PO ...

  • Lenox Elite Series X16 Air Conditioner Units - page 6

    Page 6 506637−01 1 1/10 Recovering Refrigerant from Existing System MAIN FUSE BOX/BREAKER P ANEL Disconnect all power to the existing outdoor unit at the disconnect switch or main fuse box/breaker panel. DISCONNECT POWER CONNECT MANIFOLD GAUGE SET MANIFOLD GAUGES RECOVER Y MACHINE CLEAN RECOVERY CYLINDER OUTDOOR UNIT HIGH LOW Connect a gauge set, ...

  • Lenox Elite Series X16 Air Conditioner Units - page 7

    Page 7 XC16 SERIES CONTROL P ANEL ACCESS LOCA TION 6 (152) 36 (914) 12 (305) 30 (762) LINE SET CONNECTIONS 24 (610) 48 (1219) MINIMUM CLEARANCE BETWEEN TWO UNITS CLEARANCE ON ALL SIDES  INCHES (MILLIMETERS) ACCESS P ANEL MINIMUM CLEARANCE ABOVE UNIT NOTES:  Clearance to on e of t he oth er three sides must be 36 inches (914mm).  Clearance ...

  • Lenox Elite Series X16 Air Conditioner Units - page 8

    Page 8 506637−01 1 1/10 LEG DET AIL BASE 2" (50.8MM) SCH 40 FEMALE THREADED ADAPTER Concrete slab  use two plastic anchors (hole drill 1/4") W ood or plastic slab  no plastic anchor (hole drill 1/8") COIL BASE P AN CORNER POST ST ABILIZING BRACKET (18 GAUGE MET AL  2" WIDTH; HEIGHT AS REQUIRED)  Slab Side Mounting ...

  • Lenox Elite Series X16 Air Conditioner Units - page 9

    Page 9 XC16 SERIES ROOF MOUNTING Install the unit a minimum of 6 inches (152 mm) above the roof surface to avoid ice build−up around the unit. Locate the unit above a load bearing wall or area of the roof that can adequately support the unit. Consult local codes for rooftop applications. NOTICE Roof Damage! This syst em contains both refr igerant ...

  • Lenox Elite Series X16 Air Conditioner Units - page 10

    Page 10 506637−01 1 1/10 New or Replacement Line Set REFRIGERANT LINE SET This section provides information on installation or replacement of existing line set. If new or replacement line set is not being installed then proceed to Brazing Connections on p age 12. IMPORT ANT Lennox highly recommends changing line set when converting the existing s ...

  • Lenox Elite Series X16 Air Conditioner Units - page 11

    Page 1 1 XC16 SERIES ANCHORED HEA VY NYLON WIRE TIE OR AUT OMOTIVE MUFFLER-TYPE HANGER STRAP LIQUID LINE TO V APOR LINE W ALL STUD LIQUID LINE NON−CORROSIVE MET AL SLEEVE V APOR LINE − WRAPPED IN ARMAFLEX AUT OMOTIVE MUFFLER-TYPE HANGER REFRIGERANT LINE SET  TRANSITION FROM VERTICAL TO HORIZONT AL Line Set Isolation  The following illustr ...

  • Lenox Elite Series X16 Air Conditioner Units - page 12

    Page 12 506637−01 1 1/10 Brazing Connections Use the procedures outline in figures 7 and 8 for brazing line set connections to service valves. W ARNING Polyol Ester (POE) oils used with HF C−410A refr igerant absorb moistur e very qui ckly . It is very important that the refrigerant sy stem be kept closed as much as possibl e. DO NOT remove lin ...

  • Lenox Elite Series X16 Air Conditioner Units - page 13

    Page 13 XC16 SERIES A TT ACH THE MANIFOLD GAUGE SET FOR BRAZING LIQUID AND SUCTION / V APOR LINE SER VICE V AL VES OUTDOOR UNIT LIQUID LINE V APOR LINE LIQUID LINE SERVICE VA LV E SUCTION / V APOR LINE SER VICE VA LV E A TTACH GAUGES INDOOR UNIT SUCTION / V APOR SER VICE PORT MUST BE OPEN TO ALLOW EXIT POINT FOR NITROGEN A Connect gauge set low pre ...

  • Lenox Elite Series X16 Air Conditioner Units - page 14

    Page 14 506637−01 1 1/10 WHEN BRAZING LINE SET TO SER VICE V AL VES, POINT FLAME A WA Y FROM SERVICE V AL VE. LIQUID LINE SERVICE V AL V E LIQUID LINE BRAZE LINE SET W rap both service valves with water saturated cloths as illustrated here and as mentioned in step 4, before brazing to line set . Water saturated cloths must remain water saturated ...

  • Lenox Elite Series X16 Air Conditioner Units - page 15

    Page 15 XC16 SERIES Flushing Line Set and Indoor Coil SENSING LINE TEFLON ® RING FIXED ORIFICE BRASS NUT LIQUID LINE ASSEMBL Y (INCLUDES STRAINER) LIQUID LINE ORIFICE HOUSING DISTRIBUT OR TUBES DISTRIBUT OR ASSEMBL Y REMOVE AND DISCARD WHITE TEFLON ® SEAL (IF PRESENT) A On fully cased coils, remove the coil access and plumbing panels. B Remove an ...

  • Lenox Elite Series X16 Air Conditioner Units - page 16

    Page 16 506637−01 1 1/10 Installing Indoor Metering Device This outdoor unit is designed for use in systems that use exp ansion valve metering devices at the indoor coil. See the Lennox XC16 Engineering Handbook for approved exp ansion valve kit matc h−ups. The expansion valve unit can be installed internal or external to the indoor coil. In ap ...

  • Lenox Elite Series X16 Air Conditioner Units - page 17

    Page 17 XC16 SERIES IMPORT ANT The Environmental Protection Agency (EP A) prohibits the intentional venting of HFC refrigerants during maintenance, service, repair and disposal of appliance. Approved methods of recovery , recycling or reclaiming must be followed. IMPORT ANT If this unit is bei ng matched wi t h an approved line set or indoor unit c ...

  • Lenox Elite Series X16 Air Conditioner Units - page 18

    Page 18 506637−01 1 1/10 Evacuating Line Set and Indoor Coil A Open both manifold valv es and start the vacuum pum p. B Evacuate the line set and indoor unit to an absolute pressure of 23,000 microns (29.01 inches of mercury). NOTE  During the early stages of evacuation, it is desirable to close the manifold gauge valve at least once. A rapid ...

  • Lenox Elite Series X16 Air Conditioner Units - page 19

    Page 19 XC16 SERIES IMPORT ANT Use a thermocouple or thermistor electronic vacuum gauge that is calibrated in microns. Use an instrument capable of accurately measuring down to 50 microns. W ARNING Danger of Equipment Damage. A void deep vacuum operation. Do not use compressor s to evacuat e a system. Extremely low vacuums can cause internal arcing ...

  • Lenox Elite Series X16 Air Conditioner Units - page 20

    Page 20 506637−01 1 1/10 ƒ ⁄ Figure 13. T ypical Unit Wiring Diagram ...

  • Lenox Elite Series X16 Air Conditioner Units - page 21

    Page 21 XC16 SERIES HIGH PRESSURE SWITCH (S4) LOW PRESSURE SWITCH (S87) CRANKCASE THERMOST A T (S40) CRANKCASE HEA TER (HR1) COMPRES - SOR (B1) DUAL RUN CAP ACI- T OR (C12) F AN MOTOR (B4) CONT ACTOR K1 GROUND LUG Figure 14. T ypical Factory Wiring Diagram Servicing Units Delivered V oid of Charge If the out door unit is void of refrigerant, clean ...

  • Lenox Elite Series X16 Air Conditioner Units - page 22

    Page 22 506637−01 1 1/10 6. Set the thermostat for a cooling demand. T urn on power to the indoor indoor unit and close the outdoor unit disconnect switch to start the unit. 7. Recheck voltage while the unit is running. Power must be within range shown on the nameplate. 8. Check system for sufficient refrigerant by using the procedures listed und ...

  • Lenox Elite Series X16 Air Conditioner Units - page 23

    Page 23 XC16 SERIES CHECKING AIR FLOW A T INDOOR COIL Check airflow using the Delta−T ( D T) process using the illustration in figure 17. 1. Determine the desired D T Measure entering air temper- ature using dry bulb ( A ) and wet bulb ( B ). D T is the intersect- ing value of A and B in the t able (see triangle). 2. Find temperature drop acro ...

  • Lenox Elite Series X16 Air Conditioner Units - page 24

    Page 24 506637−01 1 1/10 DO NOT CHARGE UNIT (Results of charging at low temperatures not reliable) ST ART : Measure outdoor ambient temperature USE WEIGH-IN METHOD Weigh-in or remove refrigerant based upon line length APPº (Approach) V alues(F:+/−1.0° [C: +/−0.6°]) 1. Connect gauge set as illustrated in figure 15. 2. Confirm proper airflow ...

  • Lenox Elite Series X16 Air Conditioner Units - page 25

    Page 25 XC16 SERIES T a b l e 3. HFC−410A T emperature (°F) − Pressure (Psig) °F Psig °F Psig °F Psig °F Psig °F Psig °F Psig °F Psig °F Psig 32 100.8 48 137.1 63 178.5 79 231.6 94 290.8 11 0 365.0 125 445.9 141 545.6 33 102.9 49 139.6 64 181.6 80 235.3 95 295.1 111 370.0 126 451.8 142 552.3 34 105.0 50 142.2 65 184.3 81 239.0 96 299.4 ...

  • Lenox Elite Series X16 Air Conditioner Units - page 26

    Page 26 506637−01 1 1/10 UNIT COMPONENTS IMPORT ANT Some scroll compressor have internal vacuum protector that will unload scrolls when suction pressure goes below 20 psig. A hissing sound will be heard when the compressor is running unloaded. Protector will reset when low pressure in system is raised above 40 psig. DO NOT REPLACE COMPRESSOR. The ...

  • Lenox Elite Series X16 Air Conditioner Units - page 27

    Page 27 XC16 SERIES  Digit al volt/amp meter  Electronic temperature thermometer  On-off toggle switch Procedure NOTE − Block outdoor coil to maint ain a minimum of 375 p sig during testing). 1. Turn main power OFF to outdoor unit. 2. Adjust room thermostat set point 5ºF above the room temperature. 3. Remove control access panel. Inst a ...

  • Lenox Elite Series X16 Air Conditioner Units - page 28

    Page 28 506637−01 1 1/10 Accessories For update−to−date information, see any of the following publications:  Lennox XC16 Engineering Handbook  Lennox Product Catalog  Lennox Price Book Checklists T wo−Stage Modulation Compressors Field Operational Checklist Unit Readings Y1 − First-St age Expected results during Y2 demand (T oggl ...

Fabricant Lenox Catégorie Air Conditioner

Les documents que nous recevons du fabricant de l'appareilLenox Elite Series X16 Air Conditioner Units peuvent être divisés en plusieurs groupes. Ceux-ci sont, entre autres:
- dessins techniques Lenox
- manuels d’utilisations Elite Series X16 Air Conditioner Units
- fiches produit Lenox
- dépliants
- ou étiquettes-énergie Lenox Elite Series X16 Air Conditioner Units
Tous sont importants, mais les informations les plus importantes du point de vue de l'utilisation de l'appareil se trouvent dans le manuel d’utilisation Lenox Elite Series X16 Air Conditioner Units.

Un groupe de documents appelé manuels d’utilisation est également divisé en types plus spécifiques, tels que: Manuels d’installation Lenox Elite Series X16 Air Conditioner Units, manuels d’entretien, brefs manuels ou manuels de l’utilisateur Lenox Elite Series X16 Air Conditioner Units. Selon vos besoins, vous devriez chercher le document dont vous avez besoin. Sur notre site, vous pouvez voir le manuel le plus populaire d’utilisation du produit Lenox Elite Series X16 Air Conditioner Units.

Manuel d’utilisation complet de l’appareil Lenox Elite Series X16 Air Conditioner Units, quelle devrait-elle être?
Le manuel d’utilisation, également appelé le mode d’emploi, ou tout simplement le manuel, est un document technique destiné à aider à utiliser Lenox Elite Series X16 Air Conditioner Units par les utilisateurs. Des manuels sont généralement écrits par un rédacteur technique, mais dans un langage accessible à tous les utilisateurs Lenox Elite Series X16 Air Conditioner Units.

Le manuel d’utilisation complet Lenox, devrait inclure plusieurs éléments de base. Certains d'entre eux sont moins importants, tels que: la couverture / page de titre ou pages d'auteur. Cependant, la partie restante, devrait nous fournir des informations importantes du point de vue de l'utilisateur.

1. Introduction et des conseils sur la façon d'utiliser le manuel Lenox Elite Series X16 Air Conditioner Units - Au début de chaque manuel, nous devrions trouver des indices sur la façon d'utiliser le document. Il doit contenir des informations sur l'emplacement de la table des matières Lenox Elite Series X16 Air Conditioner Units, FAQ ou des problèmes les plus fréquents - les points qui sont les plus souvent recherchés par les utilisateurs de chaque manuel
2. Table des matières - index de tous les conseils pour lLenox Elite Series X16 Air Conditioner Units qui peuvent être trouvés dans le document courant
3. Conseils sur la façon d'utiliser les fonctions de base de l’appareil Lenox Elite Series X16 Air Conditioner Units - qui devraient nous aider dans les premières étapes lors de l'utilisation Lenox Elite Series X16 Air Conditioner Units
4. Troubleshooting - séquence systématique des activités qui nous aideront à diagnostiquer et ensuite résoudre les principaux problèmes de Lenox Elite Series X16 Air Conditioner Units
5. FAQ - questions fréquemment posées
6. Détails du contact Informations sur l'endroit où chercher le contact avec le fabricant / service Lenox Elite Series X16 Air Conditioner Units dans un pays donné, si le problème ne peut être résolu par nous-mêmes.

Avez-vous une question à propos de Lenox Elite Series X16 Air Conditioner Units?

Utiliser le formulaire ci-dessous

Si vous n’avez pas résolu votre problème avec Lenox Elite Series X16 Air Conditioner Units, avec l'aide du manuel que vous avez trouvé, posez une question en utilisant le formulaire ci-dessous. Si un utilisateur a eu un problème similaire avec Lenox Elite Series X16 Air Conditioner Units il est probable qu’il a envie de partager la façon de le résoudre.

Réécrire le texte de l'image

Commentaires (0)