    OWNER'S OPERATING MANUAL XG Series Mini-Tower or Rackmount UPS Plus® Uninterruptible Power Supply Models XG1.5K-1T, XG2.2K-1T & XG3K-1T Shown in mini-tower po sition with base brackets installed . 2005 Falcon® Electri c Inc. All rights reser ved. All other brand names and trademarks are the property of their respe ctive owners. The infor ...

  • Falcon XG1.5K-1T - page 2

    2 TABLE OF CONTENTS SAFETY INFORMATION……………………… ….. 3 1.0 INTRODUCTION…………………………… ……….4 2.0 CIRCUIT DESCRIPTIONS……………… …. 5 Input Filter Current and Power Factor Regulator DC/AC Inverter Charger DC/DC Converter Battery Bypass Switch Output Filter 3.0 INSTALLATION……………… …… ...

  • Falcon XG1.5K-1T - page 3

    3 IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS RETAIN THIS USER MANUAL This manual contains important instructions wh ich must be followed during the installation, operation and maintenance of this UPS and its batteries. Please read all instructions before operating this equipment and save this manual for future reference. All of the model ...

  • Falcon XG1.5K-1T - page 4

    4 Do not dispose of battery pack or batteries in a fire. The battery may explode. Do not open or mutilate the battery pack. Released electrolyte is harmful to skin and eyes. It may be toxic. CAUTION A battery can present a risk of electrical shock and high shor t circuit current. The following precautions should be observed when working on batterie ...

  • Falcon XG1.5K-1T - page 5

    5 BLOCK DIAGRAM 2.0 CIRCUIT DESCRIPTIONS INPUT FILTER This internal UPS circuit provides surge protect ion, certified to m eet IEC 61000-4-5 and IEC 801-5. It also filters both electro-magnetic in terference (EM I) and radio frequency interference (RFI). It minimizes surges or RFI in terference present on the utility line. CURRENT AND POWER FACTOR ...

  • Falcon XG1.5K-1T - page 6

    6 BATTERY The XG Series UPS utilizes a flame retardant ba ttery pack comprised of four 12V 7 AH, valve- regulated, and sealed lead acid batteries. All XG battery packs are interchangeable. They are easy to install or change. To maintain battery d esign life, the user should operate the UPS in an ambient temperature of 68 o F to 77 o F (20 o C to 25 ...

  • Falcon XG1.5K-1T - page 7

    7 XG1.5K-1T XG2.2K-1T / XG3K-1T 1 box contains: 2 boxes contain: Box 1: UPS module with fitted battery pack UPS m odule without battery RS-232 cable RS-232 Cable Software CD Software CD Manual M anual 19” rack ears (+ screws) 19” rack ears (+ screws) Tower Mounting feet Tower M ounting feet Bo x 2: Battery Module Battery connection cable Keyhol ...

  • Falcon XG1.5K-1T - page 8

    8 NOTE! The rack-mounting ears WILL NOT support th e weight of the UPS by themselves. They are only to be used to secure the UPS to the front rails of the rack. Mounting rails or an equipment shelf ar e required to support the weight of each UPS or battery module. Use the following procedure to install the UPS in a rack: 1. Place the UPS on a flat, ...

  • Falcon XG1.5K-1T - page 9

    9 7. Install the slide assemblies, with brackets into the rack enclosure. The return flanges on the mounting brackets a nd outer parts fit to the inside of the rack-mounting rails. 8. Make sure the slide assemblies are in the same alignment position on all four rack- mounting rails. After checking ali gnment, TIGHTEN ALL SCREWS. 9. Insert the UPS, ...

  • Falcon XG1.5K-1T - page 10

    10 Mounting feet Mounting feet for a dditional Battery Modules XG1.5K-1T Free Standing XG2.2K-1T / XG3K-1T Free Stranding The default LCD display mounting is for horiz ontal (Rackmount) viewing. To orient the LCD display for vertical (Mini-Tower) viewing, remo ve the front plastic bezel by unscrewing the screws. The unit has two front panel covers. ...

  • Falcon XG1.5K-1T - page 11

    11 BATTERY MODULE INSTALLATION Additional battery modules can be connected to the UPS to provide additional battery run time. There are two types of battery modules available for the XG Series; the first., part number XGB2S7, is like the one shipped standa rd with some XG models. This module does not have an internal battery charger. The batte ry m ...

  • Falcon XG1.5K-1T - page 12

    12 4. Connect the supplied battery modules cable to the rear of the extended battery module, then to the rear of the UPS. 5. Turn on the battery breaker on the r ear of the extended battery module. 6. If an extended battery module has been connected, refer to the Battery Run Time charts in this manual for the approximate runtime available. 4.0 DISP ...

  • Falcon XG1.5K-1T - page 13

    13 INDICATORS AND ICONS LOCA TED ON THE LCD DISPLAY Buzzer: The buzzer is al ways flashing when unit turned on. Green Mode Bulb: When green mode is enabled, and the UPS has switched to Green Mode due to a load of less than 3% being detected, the bulb symbol will fl ash. Fault: The UPS failed and must be repaired; this symbol will flash and the UPS ...

  • Falcon XG1.5K-1T - page 14

    14 CONTROLS The primary front panel user controls consist of one switch and three buttons: The switch located to the right of display is the INPUT CIRCUIT BREAKER. The three buttons located to the left of th e display, from top to bottom are titled “Function/TEST”, “Set/ALARM SILENCE”, and “STANDBY”. “FUNCTION/TEST” BUTTON This butt ...

  • Falcon XG1.5K-1T - page 15

    15 CAUTION When the UPS is in Normal On-line mode, pressing the BYPASS button once will put the UPS into BYPASS MODE. During this time, should th e utility power become unavailable, the UPS will shut down. Once the unit is in BYPASS MODE operation, pres sing this button again will force UPS back to On-line operation. 5.0 OPERATION OPERATING MODES T ...

  • Falcon XG1.5K-1T - page 16

    16 BYPASS MODE The UPS will automatically go to BYPASS mode in the event it is overloaded or suffers an internal failure. When in bypass, the UPS will transfer the conn ected loads directly to utility power. When in bypass mode, BATTERY MODE w ill not be available. However, the utility power continues to be passively filtered by th e UPS. The UPS w ...

  • Falcon XG1.5K-1T - page 17

    17 TURNING THE UPS OFF To turn off the UPS: While in Normal On-line mode , press the BYPASS button for one second. The UPS will go into BYPASS MODE. Next, turn off the INPUT BREAK ER. The unit will shut down immediately. NOTE! DURING SHUT DOWN, DO NOT PRESS ANY BUTTON SINCE UPS MIGHT BE RE- ENERGIZED AND DELIVER POWER TO ITS OUTPUT UNEXPECTEDLY. 6. ...

  • Falcon XG1.5K-1T - page 18

    18 Green Mode is a power saving feature that shoul d only be used in non-critical applications. When the Green Mode is enabled and the connect ed load decreases to less than 3% of the full rated UPS output capacity, the UPS will automatical ly change from ON-LINE M O DE to BYPASS MODE, 30 seconds after the drop in load has been detected. After the ...

  • Falcon XG1.5K-1T - page 19

    19 CAUTION : When the UPS output voltage is set to 100Vac, the maximum amount of load that can be connected to the UPS must be derated (r educed). See the Specifi cations at the end of this manual for the derati ng information on your model. Output Voltage Function BIT( s) Status Bit (BIT 7) 120Vac BIT 0 & BIT 1 BIT 0 En abled (dot), BIT 1 Enab ...

  • Falcon XG1.5K-1T - page 20

    20 Note: A special external SNMP/HTTP Agent devi ce is available that connects to the UPS’s RS-232 Port. This allows for one Dry Contact interface boa rd to be installed into the Advanced Communications Option Slot concurrently. CAUTION : When an internal SNMP/HTTP AGENT device is installed into the Advanced Communications Option Slot, the RS-232 ...

  • Falcon XG1.5K-1T - page 21

    21 Standard Dry Contact Interface Card (Novell style) Please refer to the following schematic for interface details: PIN & JUMPER ASSIGNMENT FOR THE FALCON UA88374 RELAY OPTION BOARD (no on-bypass signal) PIN & JUMPER ASSIGNMENT FOR THE FALCON UA88376 RELAY OPTION BOARD (with on-bypass signal) JP1 JP2 JP3 J1 J2 J3 DB- 9 PIN DES CRIPTION 1 L ...

  • Falcon XG1.5K-1T - page 22

    22 8.0 MAINTENANCE The XG Series UPS requires very little maintena nce. The batteries are sealed, valve-regulated, maintenance-free and enclosed in the fire retardant pack. The batteries should be kept charged to prevent their premature failure. The UPS will continuously charge the batteries when connected to the utility supply. UPS AND BATTERY CAR ...

  • Falcon XG1.5K-1T - page 23

    23 Internal Battery Pack Replacement 1. Loosen and remove the screws on the left hand front panel. Remove the panel from the unit. 2. Lay the panel aside for reassembly. 3. Loosen and remove the screws of battery stoppers. Lay them aside for reassembly. 4. Grasp the battery pack, and pull it out of the front of th e unit. Marking the top of the pac ...

  • Falcon XG1.5K-1T - page 24

    24 Extended Battery Modules Replacement 1. Unplug the connected battery cab le from UPS and battery module. 2. Loosen and remove the screws from front panels. Remove both front panels from the module as shown above. 3. Lay the panels and screws aside for reassembly. 4. Loosen and remove the screws of battery stoppers. Lay them aside for reassembly. ...

  • Falcon XG1.5K-1T - page 25

    25 NEVER dispose of used batteries or the UPS in th e trash or landfill as it is against federal and state laws. The UPS and Batteries must be recycled. For UPS and battery recycling information, please contact our service departme nt for the name and address of the nearest battery recycling facility. Do not open or mutilate the battery or batteri ...

  • Falcon XG1.5K-1T - page 26

    26 9.0 TROUBLESHOOTING The XG Series UPS has an audibl e alarm feature to alert the u ser of potential problems. Please use following information to determine and resolve alarms and conditions. The XG Series UPS notifies the user of abnorma l conditions via audible alarms. The alarms are as follows: Alarm and Possible Cause Solution Three short bee ...

  • Falcon XG1.5K-1T - page 27

    27 UPS will not provide power to the load • Power only present on one output receptacle • No output from any output receptacle • Output fails as soon as load is connected • Check the output fuse • Check the connected cable • Ensure the load does not exceed the maximum rating of the UPS UPS operates from battery despite utility power pre ...

  • Falcon XG1.5K-1T - page 28

    28 SPECIFICATIONS Model Number XG1.5K-1T Model Rating 1500VA/1050W DIMENSIONS Unit W x D x H in. (mm) 16.8 x 21.5 x 3.5 (2U) (426 x 546 x 88) Shipping W x D x H in. (mm) 22 x 25.75 x 8.5 (560 x 654 x 215) WEIGHT Unit lbs (kg) 51 (23.2) Shipping lbs (kg) 58(26.4) INPUT Voltage Range 120 VAC nominal; variable based on output load 80 – 138 VAC full ...

  • Falcon XG1.5K-1T - page 29

    29 Model Number XG2.2K-1T XG3K-1T Model Rating 2200VA/ 1540W 3000VA/2100W DIMENSIONS Unit W x D x H in. (mm) 16.8 x 21.5 x 3.5 (2U) (426 x 546 x88) 16.8 x 21.5 x 3.5 (2U) (426 x 546 x 88) Shipping W x D x H in. (mm) 22 x 25.75 x 8.5 (560 x 654 x 215) 22 x 25.75 x 8.5 (560 x 654 x 215) WEIGHT Unit lb s (kg) 63.9 (29) 66.2 (30) Shipping lbs (kg) 87.1 ...

  • Falcon XG1.5K-1T - page 30

    30 Qty x V x Rating Pack 4 x 12 V x 7.2 AH ENVIRONMENTAL Operating Temperature +32 o F to +104 o F (0 o C to +40 o C) Storage Temperature +5 o F to +122 o F (-15 o C to +50 o C) Relative Humidity 0% to 95%, non-condensing Operating Elevation Up to 10,000 ft (3000m) at 104 o F without de-rating Audible Noise <45 dbA, at 1 meter from rear AGENCY S ...

  • Falcon XG1.5K-1T - page 31

    31 WARRANTY GENERAL PROVISIONS FALCON® ELECTRIC I NC., hereby warrants produc t shipped under this agre ement to be free from de fective workmanship f or a period of two years following date of shipment. This Limite d New Product Warrant y A greement only applies to covered repairs to the product o c curring within the United States and Ca nada. E ...

  • Falcon XG1.5K-1T - page 32

    32 period Falc on Electric may elect to offer a loa ner unit, providing the end-u ser agrees to pay for all shipping costs associated with transportation of the loaner unit bo th from and return to the Falcon Electric U.S. Service Center. c. All shipping costs for product submitted beyo nd 90 days of the original date of inv oice is the responsibil ...

Fabricant Falcon Catégorie Power Supply

Les documents que nous recevons du fabricant de l'appareilFalcon XG1.5K-1T peuvent être divisés en plusieurs groupes. Ceux-ci sont, entre autres:
- dessins techniques Falcon
- manuels d’utilisations XG1.5K-1T
- fiches produit Falcon
- dépliants
- ou étiquettes-énergie Falcon XG1.5K-1T
Tous sont importants, mais les informations les plus importantes du point de vue de l'utilisation de l'appareil se trouvent dans le manuel d’utilisation Falcon XG1.5K-1T.

Un groupe de documents appelé manuels d’utilisation est également divisé en types plus spécifiques, tels que: Manuels d’installation Falcon XG1.5K-1T, manuels d’entretien, brefs manuels ou manuels de l’utilisateur Falcon XG1.5K-1T. Selon vos besoins, vous devriez chercher le document dont vous avez besoin. Sur notre site, vous pouvez voir le manuel le plus populaire d’utilisation du produit Falcon XG1.5K-1T.

Manuels d’utilsiation similaires

Manuel d’utilisation complet de l’appareil Falcon XG1.5K-1T, quelle devrait-elle être?
Le manuel d’utilisation, également appelé le mode d’emploi, ou tout simplement le manuel, est un document technique destiné à aider à utiliser Falcon XG1.5K-1T par les utilisateurs. Des manuels sont généralement écrits par un rédacteur technique, mais dans un langage accessible à tous les utilisateurs Falcon XG1.5K-1T.

Le manuel d’utilisation complet Falcon, devrait inclure plusieurs éléments de base. Certains d'entre eux sont moins importants, tels que: la couverture / page de titre ou pages d'auteur. Cependant, la partie restante, devrait nous fournir des informations importantes du point de vue de l'utilisateur.

1. Introduction et des conseils sur la façon d'utiliser le manuel Falcon XG1.5K-1T - Au début de chaque manuel, nous devrions trouver des indices sur la façon d'utiliser le document. Il doit contenir des informations sur l'emplacement de la table des matières Falcon XG1.5K-1T, FAQ ou des problèmes les plus fréquents - les points qui sont les plus souvent recherchés par les utilisateurs de chaque manuel
2. Table des matières - index de tous les conseils pour lFalcon XG1.5K-1T qui peuvent être trouvés dans le document courant
3. Conseils sur la façon d'utiliser les fonctions de base de l’appareil Falcon XG1.5K-1T - qui devraient nous aider dans les premières étapes lors de l'utilisation Falcon XG1.5K-1T
4. Troubleshooting - séquence systématique des activités qui nous aideront à diagnostiquer et ensuite résoudre les principaux problèmes de Falcon XG1.5K-1T
5. FAQ - questions fréquemment posées
6. Détails du contact Informations sur l'endroit où chercher le contact avec le fabricant / service Falcon XG1.5K-1T dans un pays donné, si le problème ne peut être résolu par nous-mêmes.

Avez-vous une question à propos de Falcon XG1.5K-1T?

Utiliser le formulaire ci-dessous

Si vous n’avez pas résolu votre problème avec Falcon XG1.5K-1T, avec l'aide du manuel que vous avez trouvé, posez une question en utilisant le formulaire ci-dessous. Si un utilisateur a eu un problème similaire avec Falcon XG1.5K-1T il est probable qu’il a envie de partager la façon de le résoudre.

Réécrire le texte de l'image

Commentaires (0)