    CKF 50 Hz Condensing Unit s • Refer to Service Manual RS6100004 for installation, operation, and troubleshooting information. • All safety information must be followed as provided in the Service Manual. • Refer to the appropriate Parts Catalog for part number information. • Models listed on page 3. RT6111009r4 January 2012 This manual is to ...

  • Goodman Mfg Condensing Units - page 2

    PRODUCT IDENTIFICA TION 2 The model number is used for positive identification of component parts used in manufacturing. Please use this number when requesting service or parts information. WARNING WARNING HIGH VOLTAGE! Disconnect ALL power before servicing or installing this unit. Multiple power sources may be present. Failure to do so may cause p ...

  • Goodman Mfg Condensing Units - page 3

    PRODUCT IDENTIFICA TION 3 The model number is used for positive identification of component parts used in manufacturing. Please use this number when requesting service or parts information. CKF24-2M CKF24-2N CKF36-2M CKF36-2N CKF36-5M CKF36-5N CKF48-5M CKF48-5N CKF60-5M CKF60-5N CKF70-5M CKF70-5N * Indicates minor revision & is not used for ord ...

  • Goodman Mfg Condensing Units - page 4

    PRODUCT DESIGN 4 CKF 50 Hz models are available in 2 through 6 ton sizes. They are designed for 220/240 to 380 volt single phase appli- cations. The condenser air is pulled through the condenser coil by a direct drive propeller fan. This condenser air is then dis- charged out of the top of the cabinet. These units are designed for free air discharg ...

  • Goodman Mfg Condensing Units - page 5

    PRODUCT DESIGN 5 H W D Dimensions M o d el D i m en si o n s - W x D x H C KF 24- 2* 26 " [ 6 60] x 26" [ 66 0] x 29¾ [ 7 56] C KF 36- 2* 26 " [ 6 60] x 26" [ 66 0] x 29¾ [ 7 56] C KF 36- 5* 26 " [ 6 60] x 26" [ 66 0] x 29¾ [ 7 56] C KF 48- 5* 29 " [ 7 37] x 29" [ 73 7] x 29¾ [ 7 56] C KF 60- 5* 29 " ...

  • Goodman Mfg Condensing Units - page 6

    CONDENSING UNIT SPECIFICA TIONS 6 NOTE: This data is provided as a guide, it is important to electrically connect the unit and properly size fuses/circuit breakers and wires in accordance with all national and/or local electrical codes. Use copper wire only. CKF2 4 - 2 * CK F 3 6 - 2 * CKF3 6 -5 * CKF4 8 -5 * CKF 6 0 - 5* CKF7 0 - 5 * C ooli ng C a ...

  • Goodman Mfg Condensing Units - page 7

    7 COOLING PERFORMANCE DA T A CKF24-2* M O DE L: CKF24- 2* / A 2 4 - 00 - 2 RA C OOL IN G OP E R A T ION O utdoor Am bient Te m per ature 65°F 75°F 85°F 95°F 105°F 115 ° F 118°F 125°F E nte r i ng Indoor W et B ulb Tem pe r ature ID B Air f low 59 63 67 71 59 63 67 71 5 9 6 3 6 7 71 5 9 63 67 71 59 63 67 7 1 5 9 63 67 71 59 53 67 7 1 59 63 6 ...

  • Goodman Mfg Condensing Units - page 8

    8 COOLING PERFORMANCE DA T A CKF24-2* M O DE L: CKF24- 2* / A 2 4 - 00 - 2 RA C OOL IN G OP E R A T ION O utdoor Am bient Te m per ature 65 75 85 95 105 115 118°F 125°F E nte r i ng Indoor W et B ulb Tem pe r ature I D B * A i r f l o w 5 96 36 77 15 96 36 7 7 1 5 9 6 3 6 7 7 1 5 9 6 3 6 7 7 1 5 96 36 7 7 1 5 96 3 6 7 7 1 5 9 5 3 6 7 7 1 5 9 6 3 ...

  • Goodman Mfg Condensing Units - page 9

    9 COOLING PERFORMANCE DA T A CKF36-2* M O DEL: CK F36- 2* / A 36- 00- 2 C OOL IN G OP E R ATIO N O utdoor Am bi e nt Tem per a t ur e 65° F 75°F 85° F 95° F 105° F 115° F 1 18° F 125°F E nte r ing I ndoor W et B ulb Te m pe r a t ure ID B A ir flow 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 53 67 71 59 63 67 ...

  • Goodman Mfg Condensing Units - page 10

    10 COOLING PERFORMANCE DA T A CKF36-2* M O DEL: CK F36- 2* / A 36- 00- 2 C OOL IN G OP E R ATIO N O utdoor Am bi e nt Tem per a t ur e 65 75 85 95 105 115 11 8°F 125 °F E nte r ing I ndoor W et B ulb Te m pe r a t ure I D B * A i r f l o w 5 96 36 77 15 96 36 77 15 9 6 3 6 7 7 1 5 9 6 3 6 7 7 1 5 96 36 77 15 96 3 6 7 7 1 5 9 5 3 6 7 7 1 5 9 6 3 6 ...

  • Goodman Mfg Condensing Units - page 11

    11 COOLING PERFORMANCE DA T A CKF36-5* M O DEL: C KF36-5* / A R36-00- 2 C OOL I N G OP E R AT ION O utdoo r Am bie nt Te m pe r ature 65° F 75° F 85° F 95° F 105°F 1 15°F 118° F 125°F E nte r ing I ndoor Wet B ulb Te m pe r ature ID B Air fl ow 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 5 3 67 71 59 63 67 71 ...

  • Goodman Mfg Condensing Units - page 12

    12 COOLING PERFORMANCE DA T A CKF36-5* M O DEL: C KF36-5* / A R36-00- 2 C OOL I N G OP E R AT ION O utdoo r Am bie nt Te m pe r ature 65 75 85 95 1 05 115 118°F 125°F E nte r ing I ndoor Wet B ulb Te m pe r ature I D B * A i r f l o w 5 96 36 77 15 96 36 7 7 1 5 9 6 3 6 7 7 1 5 9 6 3 6 7 7 1 5 9 6 36 7 7 1 5 96 3 6 7 7 1 5 9 5 3 6 7 7 1 5 9 6 3 6 ...

  • Goodman Mfg Condensing Units - page 13

    13 COOLING PERFORMANCE DA T A CKF48-5* MO DEL : C K F48-5* / A 48-00- 2 C OOL IN G OP E R AT ION O utdoor Am bient Te m pe rature 65° F 75° F 85°F 95° F 105°F 115°F 118°F 125°F E n te ring Indoo r We t B ulb Te m pe r atur e ID B Air flo w 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 53 67 71 59 63 67 71 M Bh 4 ...

  • Goodman Mfg Condensing Units - page 14

    14 COOLING PERFORMANCE DA T A CKF48-5* MO DEL : C K F48-5* / A 48-00- 2 C OOL IN G OP E R AT ION O utdoor Am bient Te m pe rature 65 75 85 95 105 115 118°F 125°F E n te ring Indoo r We t B ulb Te m pe r atur e I D B * A i r f l o w 5 96 36 77 15 96 36 7 7 1 5 9 6 3 6 77 15 9 6 3 6 7 7 1 5 96 36 7 7 1 5 96 3 6 7 7 1 5 9 5 3 6 7 7 1 5 9 6 3 6 7 7 1 ...

  • Goodman Mfg Condensing Units - page 15

    15 COOLING PERFORMANCE DA T A CKF60-5* MO D EL: C KF6 0- 5* / A 60-00- 2 C OOL IN G OP E R AT ION O ut door Am bient Te m pe r ature 65° F 75°F 85° F 95°F 105°F 115° F 118° F 125°F E nte r ing Indoor W et B ulb Te m pe r a t ur e ID B Air f lo w 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 53 67 71 59 63 67 71 ...

  • Goodman Mfg Condensing Units - page 16

    16 COOLING PERFORMANCE DA T A CKF60-5* MO D EL: C KF6 0- 5* / A 60-00- 2 C OOL IN G OP E R AT ION O ut door Am bient Te m pe r ature 65 75 85 95 105 115 118°F 125° F E nte r ing Indoor W et B ulb Te m pe r a t ur e I D B * A i r f l o w 5 96 36 77 15 96 3 6 77 15 9 6 3 6 77 15 9 6 3 6 7 7 1 5 96 36 7 7 1 5 96 3 6 7 7 1 5 9 5 3 6 7 7 1 5 9 6 3 6 7 ...

  • Goodman Mfg Condensing Units - page 17

    17 COOLING PERFORMANCE DA T A CKF70-5* MO D EL : C K F70 -5* / A60-00-2 C OOL IN G OP E R A T ION O utdoor Am bient Te m pe r at ure 65°F 75°F 85°F 95°F 105°F 115°F 118°F 125°F E nte r i ng Indoor W e t B ulb Tem pe rature ID B Air f low 59 6 3 67 71 59 63 67 71 59 63 67 71 5 9 63 67 71 5 9 63 67 71 59 63 67 71 59 53 67 71 59 63 67 7 1 M Bh ...

  • Goodman Mfg Condensing Units - page 18

    18 COOLING PERFORMANCE DA T A CKF70-5* MO D EL : C K F70 -5* / A60-00-2 C OOL IN G OP E R A T ION O utdoor Am bient Te m pe r at ure 65 75 85 95 105 1 15 11 8°F 12 5°F E nte r i ng Indoor W e t B ulb Tem pe rature I D B * A i r f l o w 5 9 6 3 6 7 7 1 5 9 6 3 6 7 7 1 5 9 6 3 6 7 7 1 5 9 6 36 7 7 1 5 9 6 3 6 7 7 1 5 9 6 3 6 7 7 15 95 36 77 15 96 3 ...

  • Goodman Mfg Condensing Units - page 19

    19 PERFORMANCE DA T A PERFORMANCE TEST All data based upon listed indoor dry bulb temperature. .00 inches external static pressure on coil of outdoor section. Indoo r air cubic feet per minute (CFM) as listed in the Performance Data Sheets: If conditions vary from this, results will change as follows: 1. As indoor dry bulb temperatures increase, a ...

  • Goodman Mfg Condensing Units - page 20

    WIRING DIAGRAMS 20 HIGH VOL T A GE! DISCONNECT ALL POWER BEFORE SERVICING OR INS T A LLING THIS UNIT . MUL TIPL E POW ER SOURCES M A Y BE P RESENT . F AI LURE TO DO SO MA Y CAUS E PROPERTY DAM AGE, PERSO NAL INJURY OR DEA TH. Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring. CKF[24-36]M/N/P ...

  • Goodman Mfg Condensing Units - page 21

    WIRING DIAGRAMS 21 HIGH VOL T A GE! DISCONNECT ALL POWER BEFORE SERVICING OR INS T A LLING THIS UNIT . MUL TIPL E POW ER SOURCES M A Y BE P RESENT . F AI LURE TO DO SO MA Y CAUS E PROPERTY DAM AGE, PERSO NAL INJURY OR DEA TH. Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring. CKF[48-70]M/N/P ...

Fabricant Goodman Mfg Catégorie Air Conditioner

Les documents que nous recevons du fabricant de l'appareilGoodman Mfg Condensing Units peuvent être divisés en plusieurs groupes. Ceux-ci sont, entre autres:
- dessins techniques Goodman Mfg
- manuels d’utilisations Condensing Units
- fiches produit Goodman Mfg
- dépliants
- ou étiquettes-énergie Goodman Mfg Condensing Units
Tous sont importants, mais les informations les plus importantes du point de vue de l'utilisation de l'appareil se trouvent dans le manuel d’utilisation Goodman Mfg Condensing Units.

Un groupe de documents appelé manuels d’utilisation est également divisé en types plus spécifiques, tels que: Manuels d’installation Goodman Mfg Condensing Units, manuels d’entretien, brefs manuels ou manuels de l’utilisateur Goodman Mfg Condensing Units. Selon vos besoins, vous devriez chercher le document dont vous avez besoin. Sur notre site, vous pouvez voir le manuel le plus populaire d’utilisation du produit Goodman Mfg Condensing Units.

Manuels d’utilsiation similaires

Manuel d’utilisation complet de l’appareil Goodman Mfg Condensing Units, quelle devrait-elle être?
Le manuel d’utilisation, également appelé le mode d’emploi, ou tout simplement le manuel, est un document technique destiné à aider à utiliser Goodman Mfg Condensing Units par les utilisateurs. Des manuels sont généralement écrits par un rédacteur technique, mais dans un langage accessible à tous les utilisateurs Goodman Mfg Condensing Units.

Le manuel d’utilisation complet Goodman Mfg, devrait inclure plusieurs éléments de base. Certains d'entre eux sont moins importants, tels que: la couverture / page de titre ou pages d'auteur. Cependant, la partie restante, devrait nous fournir des informations importantes du point de vue de l'utilisateur.

1. Introduction et des conseils sur la façon d'utiliser le manuel Goodman Mfg Condensing Units - Au début de chaque manuel, nous devrions trouver des indices sur la façon d'utiliser le document. Il doit contenir des informations sur l'emplacement de la table des matières Goodman Mfg Condensing Units, FAQ ou des problèmes les plus fréquents - les points qui sont les plus souvent recherchés par les utilisateurs de chaque manuel
2. Table des matières - index de tous les conseils pour lGoodman Mfg Condensing Units qui peuvent être trouvés dans le document courant
3. Conseils sur la façon d'utiliser les fonctions de base de l’appareil Goodman Mfg Condensing Units - qui devraient nous aider dans les premières étapes lors de l'utilisation Goodman Mfg Condensing Units
4. Troubleshooting - séquence systématique des activités qui nous aideront à diagnostiquer et ensuite résoudre les principaux problèmes de Goodman Mfg Condensing Units
5. FAQ - questions fréquemment posées
6. Détails du contact Informations sur l'endroit où chercher le contact avec le fabricant / service Goodman Mfg Condensing Units dans un pays donné, si le problème ne peut être résolu par nous-mêmes.

Avez-vous une question à propos de Goodman Mfg Condensing Units?

Utiliser le formulaire ci-dessous

Si vous n’avez pas résolu votre problème avec Goodman Mfg Condensing Units, avec l'aide du manuel que vous avez trouvé, posez une question en utilisant le formulaire ci-dessous. Si un utilisateur a eu un problème similaire avec Goodman Mfg Condensing Units il est probable qu’il a envie de partager la façon de le résoudre.

Réécrire le texte de l'image

Commentaires (0)