    INST ALLA TION MANUAL - 50 Hz CAUTION: READ ALL SAFETY GUIDES BEFORE YOU BEGIN TO INST ALL YOUR UNIT . SA VE THIS MANUAL SINGLE P ACKAGE HEA T PUMP HIGH EFFICIENCY BP090 and 120 (7-1/2 and 10 TON) 66307-YIM-B-0606 CONTENTS GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 SAFETY CONSIDERATIONS . . . . . . . . . . ...

  • York BP 090 - page 2

    66307-YIM-B-0606 2 Unitary Products Group T ABLE OF CONTENTS GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . 5 INSPECTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 REFERENCE . . . . . . . . . . . . . . . . . . . . . . . . . ...

  • York BP 090 - page 3

    66307-YIM-B-0606 Unitary Products Group 3 LIST OF FIGURES Fig. # Pg. # 1 UNIT SHIPPING BRA CKET . . . . . . . . . . . . . . . . . . . . . 8 2 CONDENSER COIL COVERING . . . . . . . . . . . . . . . . . 8 3 COMPRESSOR SECTION . . . . . . . . . . . . . . . . . . . . . . 8 4 PREDATOR® COMPONENT LO CATION . . . . . . . . . . 9 5 UNIT 4 POINT LOAD . . . ...

  • York BP 090 - page 4

    66307-YIM-B-0606 4 Unitary Products Group LIST OF T ABLES Tbl. # Pg. # 1 UNIT TEMPERATURE LIMIT ATIONS . . . . . . . . . . . . . 9 2 UNIT VOLTAGE LIMITATIO NS . . . . . . . . . . . . . . . . . . 9 3 UNIT WEIGHTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 4 4 POINT LOAD WEI GHT . . . . . . . . . . . . . . . . . . . . . . 10 5 6 POI ...

  • York BP 090 - page 5

    66307-YIM-B-0606 Unitary Products Group 5 GENERAL YORK ® Predator ® Heat Pump units are single package, reverse cycle air conditioners designed fo r outdoor installa- tion on a rooftop or slab and for non-residential use. These units can be equipped with factory or field installed electric heaters for heatin g applications. These units are comple ...

  • York BP 090 - page 6

    66307-YIM-B-0606 6 Unitary Products Group REFERENCE Additional information is available i n the following re ference forms: • T echnical Guide - 259336 • General Installation - 66307 • Pre-start & Post-s t art Check List • Economizer Accessory - Downflow Factory Installed Downflow Field Installed Horizontal Field Installed • Motorized ...

  • York BP 090 - page 7

    66307-YIM-B-0606 Unitary Products Group 7 NOMENCLA TURE B P 090 C00 A 7 A AA 3 0 1 2 4 A Product Category B = HP, Single Pkg., R-22 A = Std. Motor Airflow B = Std. Motor/Econo./Barometric Relief (Downflow Only) C = Std. Motor/Econo./Power Exhaust (Downflow Only) D = Std. Motor/Motorized Damp er (Downflow Only) E = Std. Motor/Horizontal Economizer ( ...

  • York BP 090 - page 8

    66307-YIM-B-0606 8 Unitary Products Group INST ALLA TION INST ALLA TION SAFETY INFORMA TION Read these instructions before conti nuing this appliance installation. This is an o utdoor combination heating and cool- ing unit. The installer must assu re that these instructions are made available to the consu mer and with instructions to retain them fo ...

  • York BP 090 - page 9

    66307-YIM-B-0606 Unitary Products Group 9 LOCA TION Use the following guide lines to select a suitable locatio n for these units: 1. Unit is designed for outdoor installation only . 2. Condenser coils must have an unlimi ted supply of air . Where a choice of location is possible, position the unit on either north or east side of bu ilding. 3. Suita ...

  • York BP 090 - page 10

    66307-YIM-B-0606 10 Unitary Products Group RIGGING AND HANDLING Exercise care when movi ng the unit. Do not remove any packaging until the unit is near the place of installation. Rig the unit by attaching chain or cable slings to the lifting holes provided in the base rails. S preader bars, whose length exceeds the largest dimension across the unit ...

  • York BP 090 - page 11

    66307-YIM-B-0606 Unitary Products Group 11 CLEARANCES All units require particular cl earances for proper operation and service. Refer to T able 6 for clearances required for con- struction, servicing, a nd proper unit operation . NOTE: A one-inch clearance must b e provided between any combustible material an d the supply ductwork for a dist an ce ...

  • York BP 090 - page 12

    66307-YIM-B-0606 12 Unitary Products Group . FIGURE 9 - BOTTOM DUCT OPENINGS (FROM A BOVE) ...

  • York BP 090 - page 13

    66307-YIM-B-0606 Unitary Products Group 13 DUCTWORK Ductwork should be d esigned and sized ac cording to the methods in Manual D of the Air Cond itioning Contractors of America (ACCA) or as reco mmende d by any other recog- nized authority such as ASHRAE or SMACNA. A closed return duct system should be used. Thi s will not preclude use of economize ...

  • York BP 090 - page 14

    66307-YIM-B-0606 14 Unitary Products Group Note orientation. Panel i s “insulation” side up. FIGURE 1 1 - PREDA TOR ® ROOF CURB DIMENSIONS 5 0 - 1 / 2 ( 1 2 8 5 ) 3 0 ( 7 6 0 ) 2 0 ( 5 1 0 ) 8 0 - 5 / 8 ( 2 0 5 0 ) 6 ( 1 5 0 ) 2 T Y P . ( 5 0 ) I N S U L A T E D D E C K U N D E R C O M P R E S S O R S E C T I O N I N S U L A T E D D E C K U N ...

  • York BP 090 - page 15

    66307-YIM-B-0606 Unitary Products Group 15 CONDENSA TE DRA IN The side condensate drain is reversible and maybe re -ori- ented to the rear of the cab i net to facilitate condensate pip- ing. A condensate drain connection is available through the base pan for piping inside the roof curb. Trap the connection per Figure 16. The tra p and drain lines s ...

  • York BP 090 - page 16

    66307-YIM-B-0606 16 Unitary Products Group comply with electrical codes should not be required. If an y of the wire su ppl ie d wi th th e un it must be repla ce d, r eplac em en t wire must be of the type show n on the wiring diagram and the same minimum gauge as the replaced wire. A disconnect must be utilized for these units. When in stalling a ...

  • York BP 090 - page 17

    66307-YIM-B-0606 Unitary Products Group 17 FIGURE 18 - FIELD WIRING 24 VOL T THERMOST A T O C C W 1 W 2 Y 1 G Y 2 X R S D C R E M O T E M I N P O S W 1 W 2 Y 1 G Y 2 C U N I T C O N T R O L B O A R D T - S T A T R H R C The thermostat must provide a “G” signal when there is a call for “W1.”The unit control board will energi ze the indoor b ...

  • York BP 090 - page 18

    66307-YIM-B-0606 18 Unitary Products Group T ABLE 8: ELECTRICAL DATA - 7-1/2 TON HP Vo l t a g e Compressors OD Fan Motors Supply Air BLower Motor FLA Pwr Exh Motor Electric Heater Model No. Actual Kw Heater Amps Minimum Circuit Ampacity (Amp s) MCA with Power Exhaust (Amps) Max Fuse Size * (Amps) Max Fuse Size w/Pwr . Exh.* (Amps) RLA ea LRA ea FL ...

  • York BP 090 - page 19

    66307-YIM-B-0606 Unitary Products Group 19 FACTORY INST ALLED OPTIONS/ FIELD INST ALLED ACCESSORIES ELECTRIC HEA T ACCESSORY Electric heaters are available as field installed accessories. Refer to electric heat instructi ons for installation. These heat- ers mount in the heat compartm ent with the heating elements extending into the supply air cham ...

  • York BP 090 - page 20

    66307-YIM-B-0606 20 Unitary Products Group MOTORIZED OUTDOOR DAMPER The Motorized Outdoor Damper can be a factory installed option or a field installed accessory . If facto ry installed, refer to the instructio ns included with the outdoor air hood to com- plete the assembly . Field installed Motorized Outdoor Damper accessories include comp lete i ...

  • York BP 090 - page 21

    66307-YIM-B-0606 Unitary Products Group 21 • For a dual enthalpy o peration, carefully tu rn the set point adjusting screw fully clockwise past the "D" setting. POWER EXHAUST DAMPER SET POINT (WITH OR WITH- OUT POWER EXHAUST) • With no power exha ust opti on, adjust the Exhaust Air Adjustment Screw fully clockwise. This will all ow 2n ...

  • York BP 090 - page 22

    66307-YIM-B-0606 22 Unitary Products Group PHASING Predator ® units are properly phased at the factory . Check for proper compressor rotation. If the blower or compressors rotate in the wrong direction at start-up, the electrical connec- tion to the unit is misphased. Change the phasing of the field line connection at the field supplied d isconnec ...

  • York BP 090 - page 23

    66307-YIM-B-0606 Unitary Products Group 23 FIGURE 22 - BELT ADJUSTMENT A A A B SPAN LENGTH DEFL. FORCE C* * NEVER LOOSEN Procedure for adjusting belt tension: 1. Loosen six nuts (top and bottom) A. 2. Adjust by turning (B). 3. Never loosen nuts (C). 4. Use belt tension checker to apply a perp endicular force to one belt at the midpoint of the sp a ...

  • York BP 090 - page 24

    66307-YIM-B-0606 24 Unitary Products Group T ABLE 13: BLOWER PERFOR MA NCE 7-1/2 TON ST AN DARD MOTOR - SIDE DUCT (IMPERIAL) ESP (iwg) T urns Open 012345 CFM W atts BHP CFM W atts BHP CFM Watts BHP CFM W atts BHP C FM W atts BHP CFM Watt s BHP 0.2 - - - - - - - - - - - - 3698 1382 1.48 3527 1249 1.34 0.4 - - - - - - - - - 3591 142 4 1.53 3288 1242 ...

  • York BP 090 - page 25

    66307-YIM-B-0606 Unitary Products Group 25 T ABLE 16: BLOWER PERFORMANCE 7-1/2 TON OPTIONAL MOTOR - SIDE DUCT (METRIC) ESP (Pa) T urns Open 012345 m 3 /s In (kW) Out (kW) m 3 /s In (kW) Out (kW) m 3 /s In (kW) Out (kW) m 3 /s In (kW) Out (kW) m 3 /s In (kW) Out (kW) m 3 /s In (kW) Out (kW) 100 -- --- --- --- - 1 . 9 1 1 . 8 3 1 . 4 6 1 . 7 5 1 . 5 ...

  • York BP 090 - page 26

    66307-YIM-B-0606 26 Unitary Products Group T ABLE 19: BLOWER PERFOR MA NCE 10 TON OP TIONAL MOTOR - SIDE DUCT (IMPERIAL) ESP (iwg) T urns Open 012345 CFM W atts BHP CFM W atts BHP CFM Watts BHP CFM W atts BHP C FM W atts BHP CFM Watt s BHP 0.4 -- - -- - - - - -- - -- - 4 9 6 0 2 4 9 5 2 . 6 8 0.6 - - - - - - - - - - - - 5091 2745 2.94 4646 2314 2.4 ...

  • York BP 090 - page 27

    66307-YIM-B-0606 Unitary Products Group 27 T ABLE 21: BLOWER PERFORMANCE 7-1/2 T O N STANDARD MOTOR - DOWNSHOT (IMPERIAL) ESP (iwg) T u rns Open 012345 CFM W atts BHP CFM W atts BHP CFM Watts BHP CFM Watts BHP CFM Watts BHP CFM Watts B HP 0.2 - - - 3838 1772 1. 90 3530 1491 1. 60 3487 1385 1.49 3260 1234 1.32 3091 1 1 19 1.2 0 0.4 3299 1485 1.592 3 ...

  • York BP 090 - page 28

    66307-YIM-B-0606 28 Unitary Products Group T ABLE 24: BL OW ER PE RFOR MANCE 7-1/2 TO N OPTIONAL MOTOR - DOWNSHOT (METRIC) ESP (Pa) T u rns Open 012345 m 3 /s In (kW) Out (kW) m 3 /s In (kW) Out (kW) m 3 /s In (kW) Out (kW) m 3 /s In (kW) Out (kW) m 3 /s In (kW) Out (kW) m 3 /s In (kW) Out (kW) 50 - - - - - - - - - - - - 1.83 1.75 1.40 1.70 1.52 1. ...

  • York BP 090 - page 29

    66307-YIM-B-0606 Unitary Products Group 29 T ABLE 27: BLOWER PERFORM ANCE 10 T ON OP TIONAL MOTOR - DOWNSHOT (IMPER IAL) ESP (iwg) T u rns Open 012345 CFM Watts BHP CFM Watts BHP CFM Watts BHP CFM Watts BHP CFM Watts BHP CFM Watts BHP 0.2 -- - -- - -- - - - - 4966 2666 2.86 4605 2290 2.46 0.4 -- - -- - -- - 4919 2473 2.65 4721 2515 2.70 4344 2145 2 ...

  • York BP 090 - page 30

    66307-YIM-B-0606 30 Unitary Products Group AIR BALANCE S tart the supply air blower motor . Adjust the resistances in both the supply and the return air duct systems to balance the ai r distribution throughout the cond it ioned space. The job specifications may requ ire that this balancing be done by some one other than the equipment installer . CH ...

  • York BP 090 - page 31

    66307-YIM-B-0606 Unitary Products Group 31 SUPPL Y AIR DRIVE ADJUSTMENT At unit start-up, the measured CFM may be higher or lower than the required CFM. T o achieve the required CFM, th e speed of the drive may have adjusted b y changing the datum diameter (DD) of the va riable pitch mo tor sheave as described below: Required CFM Measured CFM Use t ...

  • York BP 090 - page 32

    66307-YIM-B-0606 32 Unitary Products Group T ABLE 30: ADDITIONAL STATIC RESIST ANCE - IMPERIAL CFM Cooling Only * Ec onomizer † ‡ Electric Heat KW † 9 1 82 43 65 4 2300 0.08 0.02 0.07 0.08 0.09 0.10 0.13 2500 0.09 0.02 0.08 0.09 0.10 0.1 1 0.14 2700 0.1 1 0.03 0.09 0.10 0.12 0.13 0.16 2900 0.12 0.03 0.10 0.1 1 0.13 0.14 0.18 3100 0.14 0.03 0. ...

  • York BP 090 - page 33

    66307-YIM-B-0606 Unitary Products Group 33 OPERA TION SEQUENCE OF OPERA TIONS OVERVIEW For the Predator ® series of units, the thermostat makes a cir- cuit between "R" and "Y1" for the first stage of cooling. The call is passed to the Unit Control Board (UCB) , which then determines wh ether the req uested operation is avai lab ...

  • York BP 090 - page 34

    66307-YIM-B-0606 34 Unitary Products Group "Y1" energizes the economize r . The dampers will modulate to maint ain a const ant supply air temperatur e as monitored by the discharge air sensor . If the outdoor air enthalpy is above the set point, "Y1" energizes compre ssor #1. When the thermostat calls for "second-stage" ...

  • York BP 090 - page 35

    66307-YIM-B-0606 Unitary Products Group 35 and the thermostat is calling fo r coolin g, the U CB will operate in the low ambient mode. Low ambient mode operates the co mpressors in this manner: 10 minutes on, 5 minutes off. The indoor blo wer is operated throughout the cycle. The 5-minute off period is necessary to defrost the indoor coil. Low ambi ...

  • York BP 090 - page 36

    66307-YIM-B-0606 36 Unitary Products Group at the position of the defrost thermostats . This action is repeated unti l, at the completion of a run time cycle , one of the defrost thermo stat s is found to be clo sed and the DC enters defrost mode. When the DC enters the defros t mode, it’s on-board defrost relay is powered. This energiz es bo th ...

  • York BP 090 - page 37

    66307-YIM-B-0606 Unitary Products Group 37 • If blower ro tation is in the wrong direction. Refer to Phasing Section in general info rmation section. • Check bl ower drive belt tension. 6. Check the unit supply air (CFM). 7. Measure evaporator fan moto r's amp draw . 8. Set the room thermostat fan switch to off. 9. T urn uni t electrical p ...

  • York BP 090 - page 38

    66307-YIM-B-0606 38 Unitary Products Group T ABLE 35: SUPERHEA T CHARGING SUCTION PRESSURE PSIG (Service Port) SUCTION TUBE TEMPERA TURE 0 * 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 61.5 35 37 39 41 43 45 47 49 51 53 55 57 59 61 63 65 67 69 64.2 37 39 41 43 45 47 49 51 53 55 57 59 61 63 65 67 69 71 67.1 39 41 43 45 47 49 51 53 55 57 59 61 63 ...

  • York BP 090 - page 39

    66307-YIM-B-0606 Unitary Products Group 39 TROUBLESHOOTING PREDA TOR ® FLASH CODES Various flash codes are utilized by the unit co ntrol board (UCB) to aid in troubleshooting. Flash codes are distinguished by the short on a nd off cycle used (approximately 200ms on and 200ms off). To show normal operation, the control bo ard flashes a 1 secon d on ...

  • York BP 090 - page 40

    66307-YIM-B-0606 40 Unitary Products Group FIGURE 24 : UNIT CONTRO L BOARD T ABLE 38: UNIT CON TROL BOARD FLASH CODES FLASH CODE DESCRIPTION GREEN LED 16 RED LED 8 RED LED 4 RED LED 2 RED LED 1 On S teady This is a Control Failure - - - - - 1 Flash Not Applicable - - - - - 2 Flashes Control wait ing ASCD * Flashing Off Off On Off 3 Flashes HPS1 Com ...

  • York BP 090 - page 41

    66307-YIM-B-0606 Unitary Products Group 41 COOLING TROUBL ESHO OTIN G GUI DE On calls for cooling, if the compressors are operati ng but the supply air blower motor do es not energize after a sho rt delay (the room thermostat fan switch is in the “AUTO” position): 1. T urn the thermostat fan switch to the ON position. If the supply air blower m ...

  • York BP 090 - page 42

    66307-YIM-B-0606 42 Unitary Products Group locked out the compressor for repeat trips. The UCB should be flashing an alarm code . If not, press and release the ALARMS button on the UCB. The UCB will flash the last five alarms on th e LED. If the compre ssor is locked out, cancel any call for cooling. Thi s will reset any compressor lock outs. NOTE: ...

  • York BP 090 - page 43

    66307-YIM-B-0606 Unitary Products Group 43 low-pressure switch, or freeze stat. Check for 24 volts at the HPS2, LPS2, and FS2 terminals of th e UCB. If a switch has opened, there shou ld be a voltage potential between the UCB termin als, e.g. if LPS2 has opened, there will be 24 volts of potential between the LPS2 te r- minals. 9. If 24 volts is pr ...

  • York BP 090 - page 44

    Subject to change without notice. Print ed in U.S.A. 66307-YIM-B-0606 Copyright © 2006 by Unitary Products Gro up. All rights reserved. Supersedes: 66307-YI M-A- 0704/035-17277-004-A -0704 Unitary 5005 Norman Product s Y ork OK Group Drive 73069 present, trace the wiring from Y1 “OUT” for in correct wir- ing. If 24 volts is not present at the ...

Fabricant York Catégorie Heat Pump

Les documents que nous recevons du fabricant de l'appareilYork BP 090 peuvent être divisés en plusieurs groupes. Ceux-ci sont, entre autres:
- dessins techniques York
- manuels d’utilisations BP 090
- fiches produit York
- dépliants
- ou étiquettes-énergie York BP 090
Tous sont importants, mais les informations les plus importantes du point de vue de l'utilisation de l'appareil se trouvent dans le manuel d’utilisation York BP 090.

Un groupe de documents appelé manuels d’utilisation est également divisé en types plus spécifiques, tels que: Manuels d’installation York BP 090, manuels d’entretien, brefs manuels ou manuels de l’utilisateur York BP 090. Selon vos besoins, vous devriez chercher le document dont vous avez besoin. Sur notre site, vous pouvez voir le manuel le plus populaire d’utilisation du produit York BP 090.

Manuels d’utilsiation similaires

Manuel d’utilisation complet de l’appareil York BP 090, quelle devrait-elle être?
Le manuel d’utilisation, également appelé le mode d’emploi, ou tout simplement le manuel, est un document technique destiné à aider à utiliser York BP 090 par les utilisateurs. Des manuels sont généralement écrits par un rédacteur technique, mais dans un langage accessible à tous les utilisateurs York BP 090.

Le manuel d’utilisation complet York, devrait inclure plusieurs éléments de base. Certains d'entre eux sont moins importants, tels que: la couverture / page de titre ou pages d'auteur. Cependant, la partie restante, devrait nous fournir des informations importantes du point de vue de l'utilisateur.

1. Introduction et des conseils sur la façon d'utiliser le manuel York BP 090 - Au début de chaque manuel, nous devrions trouver des indices sur la façon d'utiliser le document. Il doit contenir des informations sur l'emplacement de la table des matières York BP 090, FAQ ou des problèmes les plus fréquents - les points qui sont les plus souvent recherchés par les utilisateurs de chaque manuel
2. Table des matières - index de tous les conseils pour lYork BP 090 qui peuvent être trouvés dans le document courant
3. Conseils sur la façon d'utiliser les fonctions de base de l’appareil York BP 090 - qui devraient nous aider dans les premières étapes lors de l'utilisation York BP 090
4. Troubleshooting - séquence systématique des activités qui nous aideront à diagnostiquer et ensuite résoudre les principaux problèmes de York BP 090
5. FAQ - questions fréquemment posées
6. Détails du contact Informations sur l'endroit où chercher le contact avec le fabricant / service York BP 090 dans un pays donné, si le problème ne peut être résolu par nous-mêmes.

Avez-vous une question à propos de York BP 090?

Utiliser le formulaire ci-dessous

Si vous n’avez pas résolu votre problème avec York BP 090, avec l'aide du manuel que vous avez trouvé, posez une question en utilisant le formulaire ci-dessous. Si un utilisateur a eu un problème similaire avec York BP 090 il est probable qu’il a envie de partager la façon de le résoudre.

Réécrire le texte de l'image

Commentaires (0)