    SITE MONITORING SiteGate-232 U SER ’ S M ANUAL ...

  • Liebert 232 - page 2

    Rev. (08-JULY-98) © 1996-98 Liebert Corporation 2 SiteGate-232 Technical Instructions Contents Introduction .................................................................................................. 3 Specifications .............................................................................................. 3 Network Communications ..... ...

  • Liebert 232 - page 3

    © 1996-98 Liebert Corporation 3 Rev. (08-JULY-98) Introduction The SiteGate-232 is part of the Liebert SiteScan gateway family and provides communications between a workstation and a control module network (CMnet) consisting of fewer than 50 modules. The SiteGate-232 provides two EIA-232 Console Ports for connecting a workstation and/or a modem. T ...

  • Liebert 232 - page 4

    Rev. (08-JULY-98) © 1996-98 Liebert Corporation 4 Battery: Seven-year lithium battery provides a minimum of 10,000 hours of data retention during power outages. Fault Detection: Hardware watchdog timer. Software Requirements: One LGM module driver as FB #15. Workstation software must be SiteScan for Windows v2.5b or later, Alert 1.1a or later, and ...

  • Liebert 232 - page 5

    © 1996-98 Liebert Corporation 5 Rev. (08-JULY-98) segment. A segment is defined as the network of modules between main nodes. Main nodes can be represented by a gateway module, or a repeater (part no. REPOPT). A repeater can be used to end one segment and begin another, all on the same CMnet. It is recommended that only a dedicated, 22AWG to 18AWG ...

  • Liebert 232 - page 6

    Rev. (08-JULY-98) © 1996-98 Liebert Corporation 6 Power Wiring CAUTION: The SiteGate-232 modules are Class 2 devices (less than 30 VAC). Take appropriate isolation measures when mounting a SiteGate-232 module in a control panel where Class 1 devices or wiring are present. NOTE: Whenever possible, terminate and verify power and communication to all ...

  • Liebert 232 - page 7

    © 1996-98 Liebert Corporation 7 Rev. (08-JULY-98) Addressing, Baud Rates, and Console Settings The SiteGate-232 module's address is factory-set as control module #1 and cannot be changed. NOTE: The CMnet Baud Rate jumper (see Figure 1 for location) is only used to configure the CMnet for 156k bps. If the CMnet Baud Rate jumper is set to 156k, ...

  • Liebert 232 - page 8

    Rev. (08-JULY-98) © 1996-98 Liebert Corporation 8 Procedure 1. Turn the SiteGate-232's power switch OFF. 2. Set the module's baud rates and console port settings using the 8-position dip switch (see Figure 1 for switch location). 3. Turn the SiteGate-232's power switch ON. Communication Wiring CMnet Wiring NOTE: Only one SiteGate-23 ...

  • Liebert 232 - page 9

    © 1996-98 Liebert Corporation 9 Rev. (08-JULY-98) The "SETGCM" Command The "SETGCM" command initializes the SiteGate-232 with system parameters including Maxnet, the workstation telephone number from the SiteScan connections page (set only for the port(s) which are connected when this command is issued), and the system's l ...

  • Liebert 232 - page 10

    Rev. (08-JULY-98) © 1996-98 Liebert Corporation 10 Cables Several cables, which vary depending upon the communication requirements, are available. The following is a description and wiring configuration of each cable (the arrows indicate direction of data flow). Cable Diagrams for Console Port #1 ATAD The ATAD cable connects a 9-pin EIA-232 port t ...

  • Liebert 232 - page 11

    © 1996-98 Liebert Corporation 11 Rev. (08-JULY-98) Sit e G a t e - 2 32 C ons ole Port # 2 Term ina l N umb e r TX RX GND RX TX GND 1 2 3 4 5 3 2 7 N o conne c ti o n requ i re d N o conne c ti o n r equi re d Wor k s t a t ion Po rt (DB-25S ) Pin N umber S i t e G a te -23 2 C ons ole P o rt # 2 T e r m inal N umb e r TX RX DTR CD GN D TX RX DTR ...

  • Liebert 232 - page 12

    Rev. (08-JULY-98) © 1996-98 Liebert Corporation 12 Common Problems Modem connected to the SiteGate-232 will not answer. Make sure the TR light on the modem is ON; if it is OFF check the modem cables. Verify connection and baud rate with the SiteGate-232. Modem connect to SiteGate-232 will not dial out. Make sure the modem installed on this port is ...

  • Liebert 232 - page 13

    © 1996-98 Liebert Corporation 13 Rev. (08-JULY-98) Figure 11: SiteGate-232 LED Identification RUN LED ERROR LED CONDITION 2 flashes per sec. Off All normal 2 flashes per sec. 2 flashes per sec. 5 minute auto-restart delay after system error. 2 flashes per sec. On Exec halted after frequent system errors. 5 flashes per sec. On Exec startup aborted, ...

  • Liebert 232 - page 14

    Rev. (08-JULY-98) © 1996-98 Liebert Corporation 14 LED Power-up Sequence During power-up, the module goes through an initialization and self test sequence. Proper module power-up can be verified by observing the LEDs as follows: 1. The Run and Error LEDs turn on and begin blinking. 2. The Error LED will then turn off. 3. The Run LED will continue ...

  • Liebert 232 - page 15

    © 1996-98 Liebert Corporation 15 Rev. (08-JULY-98) LGM Module Driver Parameter Page Function Block Type: LGM (LGM Module Driver) Name SiteGate-232 Line 1 LG 2 CM 1 FB 15 Flags — ID ID14 Tele NB All Options Y Type 67 Ver 1 Power Up Delay 0 (sec) Demand Controller Address 0 ,0 Update Time 0:00 (mm:ss) BACnet Device Parameters: Use default device o ...

  • Liebert 232 - page 16

    Rev. (08-JULY-98) © 1996-98 Liebert Corporation 16 If not connected, and with no alarms pending delivery, reset modem every 5:00 (mm:ss). Note: the minimum value for this is 5:00. If connected, but no activity has been detected for 20:00 (mm:ss), hang up and reset modem. After dialing, wait 2:00 (mm:ss) for connection before hanging up. After unsu ...

  • Liebert 232 - page 17

    © 1996-98 Liebert Corporation 17 Rev. (08-JULY-98) Output character pacing? If set to YES, this parameter reduces CMnet transmission speed by 50%. This may be necessary when operating at 38.4k baud with older modules on the same CMnet. Delay before sending all replies (20 msec minimum) = 20 msec : The time in milliseconds to wait before replying t ...

  • Liebert 232 - page 18

    Rev. (08-JULY-98) © 1996-98 Liebert Corporation 18 Modem Control Parameters Modem Reset : This is a user definable parameter that sends a reset string to the modem. Dial Prefix : This parameter sets the dial prefix used for dialing out alarms. Phone Number : This parameter sets the number to be dialed out for alarms. Use This Number? NO : If " ...

  • Liebert 232 - page 19

    © 1996-98 Liebert Corporation 19 Rev. (08-JULY-98) Status Page Function Block Type: LGM (LGM Module Driver) Name SiteGate-232 Line 1 LG 1 CM 1 FB 15 Flags --- ID CM01_15 Tele DC26 All Options Y Type 83 Ver 1 Status-Code 10 Current Demand Level 0 Module Status: Auto-Restart Delay General GFB shutdown Module Halted One or more GFBs stopped ---- Alar ...

  • Liebert 232 - page 20

    Rev. (08-JULY-98) © 1996-98 Liebert Corporation 20 LGM Module Driver Status This is the overall module status. Function Block Type: This the Module Driver's three-character filename. Name: This is the name referring to the space or equipment used. Line: The telephone line number used by the Function Block. LG: Gateway module number used by th ...

  • Liebert 232 - page 21

    © 1996-98 Liebert Corporation 21 Rev. (08-JULY-98) Module Halted : All GFB related tasks have stopped. This can only happen if there have been 3 or more frequent System Errors. System Errors are errors that are severe enough to cause the module to reset. The module can still partially communicate on the CMnet when in this Halted state, but color u ...

  • Liebert 232 - page 22

    Rev. (08-JULY-98) © 1996-98 Liebert Corporation 22 Module time and date: Shows the current module date and time. Time since last reset: The amount of time that has elapsed since the last module reset. CMnet Communication lost: If "YES", this module has detected that it is alone on this CMnet. CMnet address: The module’s current CMnet n ...

  • Liebert 232 - page 23

    SiteGate-232 - User's Manual A World Leader in Computer Support Systems Environmental Control • Power Protection • Site Monitoring/Control Service • Parts • Training Liebert Corporation designs, manufactures, and markets complete systems for improvement of computer uptime and performance. The result is improved business operations, inc ...

Fabricant Liebert Catégorie Network Card

Les documents que nous recevons du fabricant de l'appareilLiebert 232 peuvent être divisés en plusieurs groupes. Ceux-ci sont, entre autres:
- dessins techniques Liebert
- manuels d’utilisations 232
- fiches produit Liebert
- dépliants
- ou étiquettes-énergie Liebert 232
Tous sont importants, mais les informations les plus importantes du point de vue de l'utilisation de l'appareil se trouvent dans le manuel d’utilisation Liebert 232.

Un groupe de documents appelé manuels d’utilisation est également divisé en types plus spécifiques, tels que: Manuels d’installation Liebert 232, manuels d’entretien, brefs manuels ou manuels de l’utilisateur Liebert 232. Selon vos besoins, vous devriez chercher le document dont vous avez besoin. Sur notre site, vous pouvez voir le manuel le plus populaire d’utilisation du produit Liebert 232.

Manuels d’utilsiation similaires

Manuel d’utilisation complet de l’appareil Liebert 232, quelle devrait-elle être?
Le manuel d’utilisation, également appelé le mode d’emploi, ou tout simplement le manuel, est un document technique destiné à aider à utiliser Liebert 232 par les utilisateurs. Des manuels sont généralement écrits par un rédacteur technique, mais dans un langage accessible à tous les utilisateurs Liebert 232.

Le manuel d’utilisation complet Liebert, devrait inclure plusieurs éléments de base. Certains d'entre eux sont moins importants, tels que: la couverture / page de titre ou pages d'auteur. Cependant, la partie restante, devrait nous fournir des informations importantes du point de vue de l'utilisateur.

1. Introduction et des conseils sur la façon d'utiliser le manuel Liebert 232 - Au début de chaque manuel, nous devrions trouver des indices sur la façon d'utiliser le document. Il doit contenir des informations sur l'emplacement de la table des matières Liebert 232, FAQ ou des problèmes les plus fréquents - les points qui sont les plus souvent recherchés par les utilisateurs de chaque manuel
2. Table des matières - index de tous les conseils pour lLiebert 232 qui peuvent être trouvés dans le document courant
3. Conseils sur la façon d'utiliser les fonctions de base de l’appareil Liebert 232 - qui devraient nous aider dans les premières étapes lors de l'utilisation Liebert 232
4. Troubleshooting - séquence systématique des activités qui nous aideront à diagnostiquer et ensuite résoudre les principaux problèmes de Liebert 232
5. FAQ - questions fréquemment posées
6. Détails du contact Informations sur l'endroit où chercher le contact avec le fabricant / service Liebert 232 dans un pays donné, si le problème ne peut être résolu par nous-mêmes.

Avez-vous une question à propos de Liebert 232?

Utiliser le formulaire ci-dessous

Si vous n’avez pas résolu votre problème avec Liebert 232, avec l'aide du manuel que vous avez trouvé, posez une question en utilisant le formulaire ci-dessous. Si un utilisateur a eu un problème similaire avec Liebert 232 il est probable qu’il a envie de partager la façon de le résoudre.

Réécrire le texte de l'image

Commentaires (0)