    # 48283B006 Page 1 Save these instructions for future reference INST ALLA TION AND MAINTENANCE INSTRUCTIONS 2SCU13 Series S plit System Air Conditioner Sharp metal edges can cause injury . When installing the unit, use care to avoid sharp edges. W ARNING Installation and servicing of air conditioning equipment can be hazardous due to internal refri ...

  • Lennox International Inc. 2SCU13 - page 2

    Page 2 # 48283B006 INST ALLA TION Location of Unit Outdoor unit s operate under a wide range of weather conditions; therefore, multiple factors must be considered when positioning the unit. The unit must be positioned to give adequate clearances for sufficient airflow and servic- ing. Refer to Figure 1 for installation clearances. General Read this ...

  • Lennox International Inc. 2SCU13 - page 3

    # 48283B006 Page 3 Figure 2 Slab Mounting 2° or 2" per 5' slope tolerance aw ay from b uilding str ucture. Discharge Air Mounting Slab Ground Le vel Building Structure Figure 3 Wind Barrier Construction Pre vailing Winter Winds 24" Wind Barrier Inlet Air Inlet Air Inlet Air Electrical Wiring All field wiring must be done in accordan ...

  • Lennox International Inc. 2SCU13 - page 4

    Page 4 # 48283B006 T able 2 Refrigerant Line Set Diameters (in.) For inst allations exceeding 5 0', cont act T echnical Services at (419) 483-4840. e n i L n o i t c u S H U T B e z i S d n a h t g n e L t e S e n i L . t f 2 1 . t f 5 2 . t f 0 5 . t f 5 7 . t f 0 0 1 0 0 0 , 8 14 / 34 / 34 / 34 / 34 / 3 0 0 0 , 4 2 4 / 3 4 / 3 4 / 3 4 / 3 8 ...

  • Lennox International Inc. 2SCU13 - page 5

    # 48283B006 Page 5 Figure 6 T o hang line set from joist or rafter , use either metal strapping material or anchored heavy n ylon wire ties. Strapping Material (around vapor line only) 8 ’ 8 ’ T ape or Wire Tie Strap the v apor line to the joist or rafter at 8 intervals then str ap the liquid line to the vapor line . ’ Floor Joist or Roof Raf ...

  • Lennox International Inc. 2SCU13 - page 6

    Page 6 # 48283B006 Figure 8 Refrigerant Line Set s: Inst alling V ertical Runs (new construction shown) Outside W all W ood Block Between Studs IMPOR T ANT: Refrigerant lines must not contact wall. V apor Line Liquid Line Wire Tie Inside W all Strap Slee ve Wire Tie Wire Tie Strap W ood Block Slee ve V apor Line Wrapped with Armaflex Liquid Line Ca ...

  • Lennox International Inc. 2SCU13 - page 7

    # 48283B006 Page 7 T o install an expansion valve (see Figure 9): 1. Separate the distributor assembly and remove the piston orifice and used teflon seal. Insert nozzle end of Figure 9 Metering Device Inst allation the expansion valve along with a new teflon seal into the distributor and tighten to 20 – 30 ft. lbs. Use backup wrench on all wrench ...

  • Lennox International Inc. 2SCU13 - page 8

    Page 8 # 48283B006 T o Close Liquid or Suction Line Service V alve: 1. Remove the stem cap with an adjustable wrench. 2. Use a service wrench with a hex-head extension to turn the stem clockwise to seat the valve. T ighten firmly . 3. Replace the stem cap. T ighten finger tight, then tighten an additional 1/6 turn. Suction Line (Ball T ype) Service ...

  • Lennox International Inc. 2SCU13 - page 9

    # 48283B006 Page 9 5. Evacuate the line set and indoor unit to a minimum of 500 microns or lower . During the early stages of evacuation, it is desirable to close the manifold gauge valve at least once to determine if there is a rapid rise in pressure. A rapid rise in pressure indicates a relatively large leak. If this occurs, the leak testing proc ...

  • Lennox International Inc. 2SCU13 - page 10

    Page 10 # 48283B006 If the system is void of refrigerant, clean the system using the procedure described below . 1. Use dry nitrogen to pressurize the system and check for leaks. Repair leaks, if possible. 2. Evacuate the system to remove as much of the moisture as possible. 3. Use dry nitrogen to break the vacuum. 4. Evacuate the system again. 5. ...

  • Lennox International Inc. 2SCU13 - page 11

    # 48283B006 Page 11 Charge Using Weigh-In Method (Fixed Orifice/TXV Systems) If the system is void of refrigerant, or if the outdoor ambient temperature is cool, first locate and repair any leaks then use the weigh-in method to charge the unit. 1. Recover the refrigerant from the unit. 2. Conduct a leak check, then evacuate as previously outlined. ...

  • Lennox International Inc. 2SCU13 - page 12

    Page 12 # 48283B006 Pressures higher than those listed indicate that the system is overcharged. Pressures lower than those listed indicate that the system is undercharged. V erify adjusted charge using the approach method. 4. Use the same digital thermometer to check liquid line temperature. 5. Subtract the outdoor ambient temperature from the liqu ...

  • Lennox International Inc. 2SCU13 - page 13

    # 48283B006 Page 13 Normal Operating Pressures T able 9 l i o C r o o d t u O r i A g n i r e t n E e r u t a r e p m e T l e d o M 8 1 - 4 2 - 0 3 - 6 3 - 2 4 - 8 4 - 0 6 - L S L S L S L S L S L S L S ) V X T ( e v l a V n o i s n a p x E F ° 5 61 4 10 87 4 19 71 4 16 75 4 14 73 4 18 75 4 10 81 5 16 7 F ° 5 76 6 11 83 7 10 87 6 17 70 7 16 77 6 1 ...

  • Lennox International Inc. 2SCU13 - page 14

    Page 14 # 48283B006 OPERA TION Outdoor unit and indoor blower cycle on demand from the room thermostat. When the thermost at blower switch is moved to the ON position, the indoor blower operates continuously . Maintenance and service must be performed by a quali- fied installer or service agency . At the beginning of each cooling season, the system ...

  • Lennox International Inc. 2SCU13 - page 15

    # 48283B006 Page 15 5. Check for correct voltage at unit (with unit operating). 6. Check amp-draw on blower motor . Unit nameplate _________ Actual _________ St art-Up and Performance Checklist Job Name _______________________________ Job No. ________________ Date ______________ Job Location _____________________________ City ___________________ S ...

  • Lennox International Inc. 2SCU13 - page 16

    Page 16 # 48283B006 Figure 12 H C F 1 DESCRIPTION KEY COMPONENT A4 CONTROL - TIMED OFF B1 COMPRESSOR B4 MO TOR - OUTDOOR F AN C12 CAP ACIT OR - DU AL HR1 HEA TER - COMPRESSOR K1-1 CONT ACT OR - COMPRESSOR S4 SWITCH - HIGH PRESSURE S24 SWITCH - LOSS OF CHARGE FOR USE WITH COPPER CONDUCT ORS ONL Y . REFER TO UNIT RA TING PLA TE FOR MINIMUM CIRCUIT AM ...

  • Lennox International Inc. 2SCU13 - page 17

    # 48283B006 Page 17 Figure 13 Three Phase Wiring Diagram P/N 48436-001 B4 OUTDOOR FA N C1 OUTDOOR F AN CAP ACIT OR A4 TIMED OFF CONTROL (IF USED) PURPLE BLACK ORANGE BLACK BLACK RED T3 T2 T1 BLACK L3 L2 L1 COMPRESSOR B1 CRANKCASE HEA TER (IF USED) HR1 2 31 T O 24 V AC POWER SOURCE 10 V A MINIMUM NEC CLASS 2 C Y1 L1 L2 L3 208-230/60/3 GROUND 2 S4 HI ...

  • Lennox International Inc. 2SCU13 - page 18

    Page 18 # 48283B006 Limited Warranty August 1, 1997 This warranty gives you specific legal rights and you may have other rights which vary from state/province to st ate/province. W arrantor: Armstrong Air Conditioning Inc., 421 Monroe St., Bellevue, OH 4481 1 Armstrong Air Conditioning Inc. products are available under the following names: Air Ease ...

Fabricant Lennox International Inc. Catégorie Air Conditioner

Les documents que nous recevons du fabricant de l'appareilLennox International Inc. 2SCU13 peuvent être divisés en plusieurs groupes. Ceux-ci sont, entre autres:
- dessins techniques Lennox International Inc.
- manuels d’utilisations 2SCU13
- fiches produit Lennox International Inc.
- dépliants
- ou étiquettes-énergie Lennox International Inc. 2SCU13
Tous sont importants, mais les informations les plus importantes du point de vue de l'utilisation de l'appareil se trouvent dans le manuel d’utilisation Lennox International Inc. 2SCU13.

Un groupe de documents appelé manuels d’utilisation est également divisé en types plus spécifiques, tels que: Manuels d’installation Lennox International Inc. 2SCU13, manuels d’entretien, brefs manuels ou manuels de l’utilisateur Lennox International Inc. 2SCU13. Selon vos besoins, vous devriez chercher le document dont vous avez besoin. Sur notre site, vous pouvez voir le manuel le plus populaire d’utilisation du produit Lennox International Inc. 2SCU13.

Manuel d’utilisation complet de l’appareil Lennox International Inc. 2SCU13, quelle devrait-elle être?
Le manuel d’utilisation, également appelé le mode d’emploi, ou tout simplement le manuel, est un document technique destiné à aider à utiliser Lennox International Inc. 2SCU13 par les utilisateurs. Des manuels sont généralement écrits par un rédacteur technique, mais dans un langage accessible à tous les utilisateurs Lennox International Inc. 2SCU13.

Le manuel d’utilisation complet Lennox International Inc., devrait inclure plusieurs éléments de base. Certains d'entre eux sont moins importants, tels que: la couverture / page de titre ou pages d'auteur. Cependant, la partie restante, devrait nous fournir des informations importantes du point de vue de l'utilisateur.

1. Introduction et des conseils sur la façon d'utiliser le manuel Lennox International Inc. 2SCU13 - Au début de chaque manuel, nous devrions trouver des indices sur la façon d'utiliser le document. Il doit contenir des informations sur l'emplacement de la table des matières Lennox International Inc. 2SCU13, FAQ ou des problèmes les plus fréquents - les points qui sont les plus souvent recherchés par les utilisateurs de chaque manuel
2. Table des matières - index de tous les conseils pour lLennox International Inc. 2SCU13 qui peuvent être trouvés dans le document courant
3. Conseils sur la façon d'utiliser les fonctions de base de l’appareil Lennox International Inc. 2SCU13 - qui devraient nous aider dans les premières étapes lors de l'utilisation Lennox International Inc. 2SCU13
4. Troubleshooting - séquence systématique des activités qui nous aideront à diagnostiquer et ensuite résoudre les principaux problèmes de Lennox International Inc. 2SCU13
5. FAQ - questions fréquemment posées
6. Détails du contact Informations sur l'endroit où chercher le contact avec le fabricant / service Lennox International Inc. 2SCU13 dans un pays donné, si le problème ne peut être résolu par nous-mêmes.

Avez-vous une question à propos de Lennox International Inc. 2SCU13?

Utiliser le formulaire ci-dessous

Si vous n’avez pas résolu votre problème avec Lennox International Inc. 2SCU13, avec l'aide du manuel que vous avez trouvé, posez une question en utilisant le formulaire ci-dessous. Si un utilisateur a eu un problème similaire avec Lennox International Inc. 2SCU13 il est probable qu’il a envie de partager la façon de le résoudre.

Réécrire le texte de l'image

Commentaires (0)