    TECHNICAL GUIDE SPLIT -SYSTEM AIR CONDITIONERS 12 SEER MODELS: H*RC018 THRU 060 (1.5 THRU 5 NOMINAL TONS, 1 PH) H*RC036S(25,4 6) THRU 060 (3 THRU 5 NOMINAL TONS, 3 PH) Due to continuous prod uct improvement, specific ations are subject to change without notice. Visit u s on the web at www .york.com for the most up-to-date techni cal information . A ...

  • York H*RC036S - page 2

    036-21137-004 Rev. C (0505) 2 Unitary Products Group Physical and Electrical Dat a - 1 Phase MODEL H2RC018S06 H2RC024S06 H2RC030S06 H2RC036S06 H2RC 042S06 H2RC048S06 H4RC060S06 Unit Supply V oltage 208/230 – 1 – 60 Normal V oltage Range 187 to 252 Minimum Circuit Ampacity 1 10.1 14.1 16.5 19.7 26.2 28.5 37.5 Max. Overcurrent Device Amps 2 15 25 ...

  • York H*RC036S - page 3

    036-21137-004 Rev. C (0505) Unitary Products Group 3 Additional R-22 Charge / Orifice Size for V arious Matched Systems - 1 Phase Outdoor Unit H2RC018S06 H2RC024S06 H2RC030S06 H 2RC036S06 H2RC042S06 H2R C048S06 H4RC060S06 Unit Orifice (s ) 1 53 59 63 73 78 87 – Factory R-22 Charge, lbs-oz. 4 - 9 4 - 7 5 - 8 5 - 3 6 - 13 7 - 7 8 - 15 Indoor Coil 5 ...

  • York H*RC036S - page 4

    036-21137-004 Rev. C (0505) 4 Unitary Products Group PROCEDURES: 1. Unit factory charge list ed on the uni t n ameplate includes ref rig erant for th e cond enser , the smallest evaporator and fo r 15 f eet of interconnecting line tubing. 2. V erify the orif ice size and additional charge required for s pecific evaporator coil in t he system using ...

  • York H*RC036S - page 5

    036-21137-004 Rev. C (0505) Unitary Products Group 5 PROCEDURES: 1. Unit factory charge list ed on the uni t nameplate includes ref rig erant for th e condenser , the smallest evaporator and for 15 f eet of interconnecting l ine tubing. 2. V erify the orifice size and additi onal char ge required for sp ecific evaporator coil in the system using th ...

  • York H*RC036S - page 6

    036-21137-004 Rev. C (0505) 6 Unitary Products Group - = Not applicable. COOLING CAP ACITY - With Air Handler Coils UNIT MODEL AIR HANDLER COIL 1 MODEL COOLING MODEL ELECTRIC 2 HEA T KW W RA TED CFM NET MBH SEER W/O TXV SEER WITH TXV 3 EER TOT AL SENS. 1 PH 12 SEER AC WITH N1AH / G2FD H2RC018S06 N1AHB0806 2,5,8,10 17 G2FD024(S, H)17 600 19.6 13.2 1 ...

  • York H*RC036S - page 7

    036-21137-004 Rev. C (0505) Unitary Products Group 7 COOLING CAP ACITY - Up flow , Downflow & Horizont al Furnaces and Coils UNIT MODEL FURNACE** COIL MODEL COOLING CFM RANGE (Min.-max.) WR A T E D C F M NET MBH SEER W/O TXV SEER + TXV 1 EER TOT AL SENS. H2RC018S06 525 675 14,17 G1F A024S14,17 600 19.2 13.0 12.00* 12.00 1 1.35 14 G1HA024H14 600 ...

  • York H*RC036S - page 8

    036-21137-004 Rev. C (0505) 8 Unitary Products Group H2RC036S06 1050 1350 14 G1F A036S14 1200 33.6 23 .4 1 1.50* 1 1.50 10.60 17,21 G1F A036S17,21 1200 33.0 23.0 1 1.25 * 1 1.25 10.45 17 G1F A048S17 1200 35.0 24 .4 12.00* 12.00 10.90 21 G1F A048S21 1200 34.0 25 .2 12.00* 12.00 10.70 14 G1HA036H14 1 150 33.5 23 .8 12.00* – 10.75 14 G1HA036H14 1 15 ...

  • York H*RC036S - page 9

    036-21137-004 Rev. C (0505) Unitary Products Group 9 *Requires 2FD Blower T ime Delay unless a st andard furnace is equipped with one. ** Refer to Quick Selection Chart for specific furnace mat ch-up. H2RC048S06 1375 1775 17 G1F A048S17 1575 45.5 34.1 12.00* 12 .00 1 1.00 21 G1F A048S21 1575 46.5 34.9 12.00* 12 .00 1 1.00 21,24 G1F A060S21,24 1575 ...

  • York H*RC036S - page 10

    036-21137-004 Rev. C (0505) 10 Unitary Products Group COOLING CAP ACITY - With V ariable Spe ed Furnaces UNIT MODEL V ARIABLE SPEED FURNACE MODEL COIL MODEL 1 W COOLING RA TED CFM NET MBH SEER W/O TXV SEER + TXV 2 EER TOT AL SENS. 1 PH 12 SEER AC - V ARIABLE SPEED 3 H2RC018S06 P1DUA12V/PV8A12****UH G1F A024 S14 14 600 19.6 13.4 – 13.00 12.55 P1DU ...

  • York H*RC036S - page 11

    036-21137-004 Rev. C (0505) Unitary Products Group 11 H2RC048S06 P1DUC20V/PV8C20****UH G1F A048S21 21 1 610 46.5 34.9 – 12.10 1 1.15 P1DUC20V/PV8C20****UH G2FD048(S,H)21 21 1610 46.5 34.9 – 12.25 1 1.05 P1XDD20V G2FD048(S,H)24 24 1610 47.0 35.4 – 12.40 1 1.00 P1XUC16V G1F A048S21 21 1480 46.0 34.4 – 12.10 10.90 P1XUC16V G2FD048(S,H)21 21 14 ...

  • York H*RC036S - page 12

    036-21137-004 Rev. C (0505) 12 Unitary Products Group All dimensions are in inches. T hey are subject to change without notice. Certified dimensi ons will be provided upon request. ACCESSORIES* Refer to Price Manual for specific model numbers. Hard St art Kit - Provides increased starting torque for areas with low voltage. Compressor Blanket - Desi ...

  • York H*RC036S - page 13

    036-21137-004 Rev. C (0505) Unitary Products Group 13 TYPICAL INST ALLA TION TYPICAL FIELD WIRING - 1 Phase Application TYPICAL FIELD WIRING - 3 Phase Application MINIMUM 18” SERVICE ACCESS CLEARANCE ON ONE SIDE 60” OVERHEAD CLEARANCE 10” CLEARANCE COIL AREA WEA THERPROOF DISCONNECT SWITCH THERMOST A T TO FURNACE OR AIR HANDLER TERMINAL BLOCK ...

  • York H*RC036S - page 14

    036-21137-004 Rev. C (0505) 14 Unitary Products Group Multipliers for determining th e performance with other indoor sec tions. NOTE: For dry bulb temperatures dif ferent than those listed (bet ween 73-87 F), sensible capacit y incr eases by 1060 BTUH per 1000 CFM per degree abo ve the listed temperature and decre ases by 1060 BTUH per 1000 CFM per ...

  • York H*RC036S - page 15

    036-21137-004 Rev. C (0505) Unitary Products Group 15 Multipliers for determining th e performance with other indoor sec tions. NOTE: For dry bulb temperatures dif ferent than those liste d (between 73-87 F), sensible cap acity incr eases by 1060 BTUH per 1000 CFM per degr ee above the listed temperature and decreases by 1060 BTUH per 1 000 CFM per ...

  • York H*RC036S - page 16

    036-21137-004 Rev. C (0505) 16 Unitary Products Group Multipliers for determining th e performance with other indoor sec tions. NOTE: For dry bulb temperatures dif ferent than those listed (bet ween 73-87 F), sensible capacit y incr eases by 1060 BTUH per 1000 CFM per degree abo ve the listed temperature and decre ases by 1060 BTUH per 1000 CFM per ...

  • York H*RC036S - page 17

    036-21137-004 Rev. C (0505) Unitary Products Group 17 Multipliers for determining th e performance with other indoor sec tions. NOTE: For dry bulb temperatures dif ferent than those liste d (between 73-87 F), sensible cap acity incr eases by 1060 BTUH per 1000 CFM per degr ee above the listed temperature and decreases by 1060 BTUH per 1 000 CFM per ...

  • York H*RC036S - page 18

    036-21137-004 Rev. C (0505) 18 Unitary Products Group Multipliers for determining th e performance with other indoor sec tions. NOTE: For dry bulb temperatures dif ferent than those listed (bet ween 73-87 F), sensible capacit y incr eases by 1060 BTUH per 1000 CFM per degree abo ve the listed temperature and decre ases by 1060 BTUH per 1000 CFM per ...

  • York H*RC036S - page 19

    036-21137-004 Rev. C (0505) Unitary Products Group 19 Multipliers for determining th e performance with other indoor sec tions. NOTE: For dry bulb temperatures dif ferent than those liste d (between 73-87 F), sensible cap acity incr eases by 1060 BTUH per 1000 CFM per degr ee above the listed temperature and decreases by 1060 BTUH per 1 000 CFM per ...

  • York H*RC036S - page 20

    036-21137-004 Rev. C (0505) 20 Unitary Products Group Multipliers for determining th e performance with other indoor sec tions. NOTE: For dry bulb temperatures dif ferent than those listed (bet ween 73-87 F), sensible capacit y incr eases by 1060 BTUH per 1000 CFM per degree abo ve the listed temperature and decre ases by 1060 BTUH per 1000 CFM per ...

  • York H*RC036S - page 21

    036-21137-004 Rev. C (0505) Unitary Products Group 21 Multipliers for determining th e performance with other indoor sec tions. NOTE: For dry bulb temperatures dif ferent than those liste d (between 73-87 F), sensible cap acity incr eases by 1060 BTUH per 1000 CFM per degr ee above the listed temperature and decreases by 1060 BTUH per 1 000 CFM per ...

  • York H*RC036S - page 22

    036-21137-004 Rev. C (0505) 22 Unitary Products Group Multipliers for determining th e performance with other indoor sec tions. NOTE: For dry bulb temperatures dif ferent than those listed (bet ween 73-87 F), sensible capacit y incr eases by 1060 BTUH per 1000 CFM per degree abo ve the listed temperature and decre ases by 1060 BTUH per 1000 CFM per ...

  • York H*RC036S - page 23

    036-21137-004 Rev. C (0505) Unitary Products Group 23 Multipliers for determining th e performance with other indoor sec tions. NOTE: For dry bulb temperatures dif ferent than those liste d (between 73-87 F), sensible cap acity incr eases by 1060 BTUH per 1000 CFM per degr ee above the listed temperature and decreases by 1060 BTUH per 1 000 CFM per ...

  • York H*RC036S - page 24

    Subject to change without notice. Printe d in U.S.A. 036-21137-004 Rev. C (0505) Copyright © by Y ork International Corp. 2005. All rights reserved. Supersedes: 036-21137-004 Rev. B (0105) Unitary 5005 Norman Product s Y ork O K Group Drive 73069 MA TCHING INDOOR COMPONENTS G1UA 1/2 CASED UPFLOW G1HD HORIZONT AL DUCT G2FD* MUL TI-POSITION (UPFLOW ...

Fabricant York Catégorie Air Conditioner

Les documents que nous recevons du fabricant de l'appareilYork H*RC036S peuvent être divisés en plusieurs groupes. Ceux-ci sont, entre autres:
- dessins techniques York
- manuels d’utilisations H*RC036S
- fiches produit York
- dépliants
- ou étiquettes-énergie York H*RC036S
Tous sont importants, mais les informations les plus importantes du point de vue de l'utilisation de l'appareil se trouvent dans le manuel d’utilisation York H*RC036S.

Un groupe de documents appelé manuels d’utilisation est également divisé en types plus spécifiques, tels que: Manuels d’installation York H*RC036S, manuels d’entretien, brefs manuels ou manuels de l’utilisateur York H*RC036S. Selon vos besoins, vous devriez chercher le document dont vous avez besoin. Sur notre site, vous pouvez voir le manuel le plus populaire d’utilisation du produit York H*RC036S.

Manuels d’utilsiation similaires

Manuel d’utilisation complet de l’appareil York H*RC036S, quelle devrait-elle être?
Le manuel d’utilisation, également appelé le mode d’emploi, ou tout simplement le manuel, est un document technique destiné à aider à utiliser York H*RC036S par les utilisateurs. Des manuels sont généralement écrits par un rédacteur technique, mais dans un langage accessible à tous les utilisateurs York H*RC036S.

Le manuel d’utilisation complet York, devrait inclure plusieurs éléments de base. Certains d'entre eux sont moins importants, tels que: la couverture / page de titre ou pages d'auteur. Cependant, la partie restante, devrait nous fournir des informations importantes du point de vue de l'utilisateur.

1. Introduction et des conseils sur la façon d'utiliser le manuel York H*RC036S - Au début de chaque manuel, nous devrions trouver des indices sur la façon d'utiliser le document. Il doit contenir des informations sur l'emplacement de la table des matières York H*RC036S, FAQ ou des problèmes les plus fréquents - les points qui sont les plus souvent recherchés par les utilisateurs de chaque manuel
2. Table des matières - index de tous les conseils pour lYork H*RC036S qui peuvent être trouvés dans le document courant
3. Conseils sur la façon d'utiliser les fonctions de base de l’appareil York H*RC036S - qui devraient nous aider dans les premières étapes lors de l'utilisation York H*RC036S
4. Troubleshooting - séquence systématique des activités qui nous aideront à diagnostiquer et ensuite résoudre les principaux problèmes de York H*RC036S
5. FAQ - questions fréquemment posées
6. Détails du contact Informations sur l'endroit où chercher le contact avec le fabricant / service York H*RC036S dans un pays donné, si le problème ne peut être résolu par nous-mêmes.

Avez-vous une question à propos de York H*RC036S?

Utiliser le formulaire ci-dessous

Si vous n’avez pas résolu votre problème avec York H*RC036S, avec l'aide du manuel que vous avez trouvé, posez une question en utilisant le formulaire ci-dessous. Si un utilisateur a eu un problème similaire avec York H*RC036S il est probable qu’il a envie de partager la façon de le résoudre.

Réécrire le texte de l'image

Commentaires (0)