    TECHNICAL GUIDE SPLIT -SYSTEM A IR CONDITIONERS 13 SEER – R-22 MODELS: H*RD018 THRU 060 (1.5 THRU 5 NOMINAL TONS, 1 PHASE) H*RD036 THRU 060 (2.5 THRU 5 NOMINAL TONS, 3 PHASE) Due to continuous produc t impr ovement, specifications are subject to change without notice. V isit us on th e web at www .york.com A dditional rating informa tion can be f ...

  • York H*RD018 THRU 060 - page 2

    254892-YTG-C-0606 2 Unitary Products Group All dimensions are in inches. They a re subject to change without notice. Ce rtif ied dimensio ns will be provide d upon request. PHYSICAL AND ELECTRICAL DA T A - 1 PHASE MODEL H2RD018S06 H2RD024S06 H2RD030S06 H 2RD036S06 H2RD042S06 H2RD048S06 H 2RD060S06 Unit Supply V olt age 208-230V , 1 φ, 60Hz Normal ...

  • York H*RD018 THRU 060 - page 3

    254892-YTG-C-0606 Unitary Products Group 3 Additional R-22 Charge / Orifice Size for V arious Ma tched Systems - 1 Phase Outdoor Unit H2RD018S06 H2RD024S06 H2RD030S06 H2RD036S06 H2RD042S06 H2RD048S06 H2RD060S06 Required TXV 1 TVM2A1 1 TVM2(A,B)1 1 TVM2A1 1 TVM2A1 1 TVM2C1 1 TVM2C1 1 TVM2C1 Factory R-22 Charge, lbs-oz 4 - 9 6 - 3 5 - 13 6 - 0 8 - 13 ...

  • York H*RD018 THRU 060 - page 4

    254892-YTG-C-0606 4 Unitary Products Group H C 1 8 A 3 X 0 2 B + 1 ––––– H C 3 0 A 3 X – 2 A + 0 0 –––– HC36B3X – – 0 0 – – – H C 4 2 C 3 X ––––0 0 – H C 6 0 C 3 X –––––0 0 H D 2 4 A 3 X 0 2 A + 0 ––––– HD36B3X – – 0 0 – – – H D 4 8 C 3 X ––––0 0 – H D 6 0 D 3 X ––? ...

  • York H*RD018 THRU 060 - page 5

    254892-YTG-C-0606 Unitary Products Group 5 PROCEDURES: 1. U nit factory charge listed on the unit nameplate includes refr igerant for the condenser , the smallest evaporator and for 15 feet of inter- connecting line tubing. 2. Verify the TXV and additional charge required for specific evaporator coil in the system using the above table. 3. Addition ...

  • York H*RD018 THRU 060 - page 6

    254892-YTG-C-0606 6 Unitary Products Group All dimensions are in inches. They a re subject to change without notice. Ce rtif ied dimensio ns will be provide d upon request. PHYSICAL AND ELECTRICAL DA T A - 3 PHASE MODEL H1RD 030S25 H1RD 036S25 H1RD 042S25 H1RD 048S25 H1RD 060S25 H1RD 030S46 H1RD 036S46 H1RD 042S46 H1RD 048S46 H1RD 060S46 Unit Suppl ...

  • York H*RD018 THRU 060 - page 7

    254892-YTG-C-0606 Unitary Products Group 7 Additional R-22 Charge / Orifice Size for V arious Ma tched Systems - 3 Phase Outdoor Unit H1RD030S(25,46) H1RD036S(25,46) H1RD042S(25,46) H1RD048S(25, 46) H1RD060S(25,46) Required TXV 1 TVM2A1 1 TVM2A1 1 TVM2C1 1 TVM2C1 1 TVM2C1 Factory R-22 Charge, lbs-oz 5 - 13 6 - 0 8 - 13 8 - 6 10 - 2 Indoor Coil 1 Ad ...

  • York H*RD018 THRU 060 - page 8

    254892-YTG-C-0606 8 Unitary Products Group PROCEDURES: 1. U nit factory charge listed on the unit nameplate include s refr iger ant for the condenser , the smallest evaporator and for 15 feet of inter- connecting line tubing. 2. Verify the TXV and additional charge required for specific evaporator coil in the system using the above table. 3. Additi ...

  • York H*RD018 THRU 060 - page 9

    254892-YTG-C-0606 Unitary Products Group 9 COOLING CAP ACITY - With Air Handler Coils UNIT MODEL AIR HANDLER COIL MODEL 1 COOLING MODEL ELECTRIC HEA T KW 2 W RA TED CFM NET MBH SEER EER TOT AL SENS. 1 & 3 PH 13 SEER AC WITH MA H2RD018S06 MA08B 2,5,8 17 FC/MC18B 600 17.5 1 1.7 13.00 1 1.00 MA08B 2,5,8 17 G*FD024H17 600 17.5 1 1.7 13.00 1 1.00 H2 ...

  • York H*RD018 THRU 060 - page 10

    254892-YTG-C-0606 10 Unitary Products Group — = Not applicable. 1 PH 13 SEER AC WITH A V / SV - V ARIABLE SPEED H2RD018S06 A V24 2,5,8,10,15 17 – 600 18.0 1 1.7 14.00 1 1.50 H2RD024S06 A V24 2,5,8,10,15 17 – 800 23.2 16.5 14.00 1 1.50 H2RD030S06 A V36 5,8,10,15,18 21 – 1000 30.0 21.2 14.00 1 1.50 H2RD036S06 A V36 5,8,10,15,18 21 – 1200 35 ...

  • York H*RD018 THRU 060 - page 11

    254892-YTG-C-0606 Unitary Products Group 11 COOLING CAP ACITY - Up flow , Downflow & Horizont al Furnaces and Coils UNIT MODEL F URNACE** COIL MODEL COOLING CFM RANGE (MIN.-MAX.) W RA TED CFM NET MBH SEER 1 EER TOT AL SENS. H2RD018S06 450 750 14,17 FC/MC/PC/UC18 600 17.5 1 1.7 13.00 1 1.00 14,17 FC/MC/PC/UC24 600 17.7 1 1.9 13.00 1 1.00 14 G*F ...

  • York H*RD018 THRU 060 - page 12

    254892-YTG-C-0606 12 Unitary Products Group H2RD042S06 1200 1600 17,21 FC/MC/PC/UC42 1400 40.5 29.6 13.00 1 1.00 21,24 FC/MC/PC/UC48 1400 41.0 30.2 13.00 1 1.00 17 G*F A042S17 1400 40.5 29.6 13.00 1 1.00 21 G*F A048S21 1400 41.0 29.6 13.00 1 1.00 21 G*FD042H21 1400 40.5 29.6 13.00 1 1.00 17 G*FD046H17 1400 40.5 29.6 13.00 1 1.00 21,24 G*FD048H21,24 ...

  • York H*RD018 THRU 060 - page 13

    254892-YTG-C-0606 Unitary Products Group 13 COOLING CAP ACITY - With V ariable Speed Furnaces UNIT MODEL V ARIABLE SPEED FURNACE MODEL COIL MODEL 1 W COOLING RA TED CFM NET MBH SEER EER T OTAL SENS. 1 PH 13 SEER AC WITH V ARIABLE SPEED FURNACES 2 H2RD018S06 PV8*A12 FC/MC/PC18A 14 600 17.8 1 1.9 14 .00 1 1.50 PV9*A12 FC/MC/PC18A 14 600 17.8 1 1.8 14 ...

  • York H*RD018 THRU 060 - page 14

    254892-YTG-C-0606 14 Unitary Products Group H2RD036S06 PV8*A12 FC/MC/PC36A 14 1200 35.0 25.4 13.00 1 1.00 PV8*B16 FC/MC/PC36B 17 1200 35.2 25.6 13.75 1 1.00 PV8*C16 FC/MC/PC36C 21 1200 35.2 25.6 14.00 1 1.50 PV8*C20 FC/MC/PC36C 21 1200 35.2 25.6 14.00 1 1.50 PV9*A12 FC/MC/PC36A 14 1200 34.8 25.4 13.00 1 1.00 P(C,V)9*B12 FC/MC/PC36B 17 1200 35.0 25. ...

  • York H*RD018 THRU 060 - page 15

    254892-YTG-C-0606 Unitary Products Group 15 H2RD048S06 PV8*C16 FC/MC/PC48C 21 1500 46.5 34.2 13.00 1 1.00 PV8*C20 FC/MC/PC48C 21 1600 47.0 35.2 13.00 1 1.00 P(C,V)9*C16 FC/MC/PC48C 21 1600 47.0 35.2 13.00 1 1.00 P(C,V)9*C20 FC/MC/PC48C 21 1600 47.0 35.2 13.00 1 1.00 P(C,V)9*D20 FC/MC/PC48D 24 1600 47.0 35.2 13.25 1 1.00 PV8*C16 HC48 21 1500 46.5 33 ...

  • York H*RD018 THRU 060 - page 16

    254892-YTG-C-0606 16 Unitary Products Group ACCESSORIES Refer to Price Manual for specific model numbers. HARD ST ART KIT - Provides increased starting torque for areas with low voltage. COMPRESSOR BLANKET - Designed to furth er reduce the normal compressor operating sound. Refer to price pages for specific match-ups. OFF CYCLE TIMER DELA Y - Provi ...

  • York H*RD018 THRU 060 - page 17

    254892-YTG-C-0606 Unitary Products Group 17 Multipliers for determining the performance with other indoor sections . NOTE: For dry bulb temperatures dif ferent than t hose liste d (between 73-87 F), sensible cap acity incr eases by 1060 BTUH per 1000 CFM per degree above the listed temperature and decreases by 1060 BTUH per 1 000 CFM per degree bel ...

  • York H*RD018 THRU 060 - page 18

    254892-YTG-C-0606 18 Unitary Products Group Multipliers for determining the p erfo rman ce with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those liste d (bet ween 73-87 F), sensible capacit y incr eases by 1060 BTUH per 1000 CFM per deg ree above the listed temperatur e and decre ases by 1060 BTUH per 1000 CFM per degree ...

  • York H*RD018 THRU 060 - page 19

    254892-YTG-C-0606 Unitary Products Group 19 Multipliers for determining the performance with other indoor sections . NOTE: For dry bulb temperatures dif ferent than t hose liste d (between 73-87 F), sensible cap acity incr eases by 1060 BTUH per 1000 CFM per degree above the listed temperature and decreases by 1060 BTUH per 1 000 CFM per degree bel ...

  • York H*RD018 THRU 060 - page 20

    254892-YTG-C-0606 20 Unitary Products Group Multipliers for determining the p erfo rman ce with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those liste d (bet ween 73-87 F), sensible capacit y incr eases by 1060 BTUH per 1000 CFM per deg ree above the listed temperatur e and decre ases by 1060 BTUH per 1000 CFM per degree ...

  • York H*RD018 THRU 060 - page 21

    254892-YTG-C-0606 Unitary Products Group 21 Multipliers for determining the performance with other indoor sections . NOTE: For dry bulb temperatures dif ferent than t hose liste d (between 73-87 F), sensible cap acity incr eases by 1060 BTUH per 1000 CFM per degree above the listed temperature and decreases by 1060 BTUH per 1 000 CFM per degree bel ...

  • York H*RD018 THRU 060 - page 22

    254892-YTG-C-0606 22 Unitary Products Group Multipliers for determining the p erfo rman ce with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those liste d (bet ween 73-87 F), sensible capacit y incr eases by 1060 BTUH per 1000 CFM per deg ree above the listed temperatur e and decre ases by 1060 BTUH per 1000 CFM per degree ...

  • York H*RD018 THRU 060 - page 23

    254892-YTG-C-0606 Unitary Products Group 23 Multipliers for determining the performance with other indoor sections . NOTE: For dry bulb temperatures dif ferent than t hose liste d (between 73-87 F), sensible cap acity incr eases by 1060 BTUH per 1000 CFM per degree above the listed temperature and decreases by 1060 BTUH per 1 000 CFM per degree bel ...

  • York H*RD018 THRU 060 - page 24

    Subject to change without notice. Printe d in U .S.A. 254892-YTG-C-0606 Copyright © by York International Corp. 2006. All right s reserved. Supersedes: 254892 / 036-21339-002 Rev. B (020 6) Unitary 5005 Norman Product s Y ork O K Group Drive 73069 NOTES ...

Fabricant York Catégorie Air Conditioner

Les documents que nous recevons du fabricant de l'appareilYork H*RD018 THRU 060 peuvent être divisés en plusieurs groupes. Ceux-ci sont, entre autres:
- dessins techniques York
- manuels d’utilisations H*RD018 THRU 060
- fiches produit York
- dépliants
- ou étiquettes-énergie York H*RD018 THRU 060
Tous sont importants, mais les informations les plus importantes du point de vue de l'utilisation de l'appareil se trouvent dans le manuel d’utilisation York H*RD018 THRU 060.

Un groupe de documents appelé manuels d’utilisation est également divisé en types plus spécifiques, tels que: Manuels d’installation York H*RD018 THRU 060, manuels d’entretien, brefs manuels ou manuels de l’utilisateur York H*RD018 THRU 060. Selon vos besoins, vous devriez chercher le document dont vous avez besoin. Sur notre site, vous pouvez voir le manuel le plus populaire d’utilisation du produit York H*RD018 THRU 060.

Manuels d’utilsiation similaires

Manuel d’utilisation complet de l’appareil York H*RD018 THRU 060, quelle devrait-elle être?
Le manuel d’utilisation, également appelé le mode d’emploi, ou tout simplement le manuel, est un document technique destiné à aider à utiliser York H*RD018 THRU 060 par les utilisateurs. Des manuels sont généralement écrits par un rédacteur technique, mais dans un langage accessible à tous les utilisateurs York H*RD018 THRU 060.

Le manuel d’utilisation complet York, devrait inclure plusieurs éléments de base. Certains d'entre eux sont moins importants, tels que: la couverture / page de titre ou pages d'auteur. Cependant, la partie restante, devrait nous fournir des informations importantes du point de vue de l'utilisateur.

1. Introduction et des conseils sur la façon d'utiliser le manuel York H*RD018 THRU 060 - Au début de chaque manuel, nous devrions trouver des indices sur la façon d'utiliser le document. Il doit contenir des informations sur l'emplacement de la table des matières York H*RD018 THRU 060, FAQ ou des problèmes les plus fréquents - les points qui sont les plus souvent recherchés par les utilisateurs de chaque manuel
2. Table des matières - index de tous les conseils pour lYork H*RD018 THRU 060 qui peuvent être trouvés dans le document courant
3. Conseils sur la façon d'utiliser les fonctions de base de l’appareil York H*RD018 THRU 060 - qui devraient nous aider dans les premières étapes lors de l'utilisation York H*RD018 THRU 060
4. Troubleshooting - séquence systématique des activités qui nous aideront à diagnostiquer et ensuite résoudre les principaux problèmes de York H*RD018 THRU 060
5. FAQ - questions fréquemment posées
6. Détails du contact Informations sur l'endroit où chercher le contact avec le fabricant / service York H*RD018 THRU 060 dans un pays donné, si le problème ne peut être résolu par nous-mêmes.

Avez-vous une question à propos de York H*RD018 THRU 060?

Utiliser le formulaire ci-dessous

Si vous n’avez pas résolu votre problème avec York H*RD018 THRU 060, avec l'aide du manuel que vous avez trouvé, posez une question en utilisant le formulaire ci-dessous. Si un utilisateur a eu un problème similaire avec York H*RD018 THRU 060 il est probable qu’il a envie de partager la façon de le résoudre.

Réécrire le texte de l'image

Commentaires (0)