    SER VICE MANUAL CONTENTS 1. TECHNICAL CHANGES ····································2 2. P ART NAMES AND FUNCTIONS ······················2 3. INDOOR/OUTDOOR CORRESPONDENCE T ABLE ···························3 4. INDOOR UNITS COMBINA TION ··············· ...

  • Mitsubishi Electronics MXZ-32SV - page 2

    P ART NAMES AND FUNCTIONS 2 OUTDOOR UNIT Air inlet Air outlet (back and side) Model indication MXZ-32SV - MXZ-32SV - E2 E1 2 TECHNICAL CHANGES 1 MXZ-32RV - ➔ MXZ-32SV - 1. The combination pattern of the indoor unit has increased. 2. Crankcase heater has disused. 3. Refrigerant circuit has changed. • Disuse of 2-way valve. • Disuse of capillar ...

  • Mitsubishi Electronics MXZ-32SV - page 3

    3 3 INDOOR / OUTDOOR CORRESPONDENCE T ABLE ❈ There is no combination other than this table. MXZ-32SV - E1 , MXZ-32SV - E2 OUTDOOR UNIT Combination of the connectable indoor units 07+07 07+09 07+12 07+18 09+09 09+12 09+18 12+12 12+18 18+18 07+07+07 07+07+09 07+07+12 07+07+18 07+09+09 07+09+12 07+09+18 07+12+12 07+12+18 07+18+18 09+09+09 09+09+12 0 ...

  • Mitsubishi Electronics MXZ-32SV - page 4

    4 07 09 12 18 07+07 07+09 07+12 07+18 09+09 09+12 09+18 12+12 12+18 18+18 07+07+07 07+07+09 07+07+12 07+07+18 07+09+09 07+09+12 07+09+18 07+12+12 07+12+18 07+18+18 90 90 90 90 90 90 90 90 90 90 90 90 90 90 90 90 90 90 90 90 90 90 90 90 3.47 4.17 6.67 10.65 7.13 7.50 10.56 14.31 8.80 12.64 17.31 18.33 18.33 18.33 10.19 1 1.25 13.80 13.80 12.96 13.80 ...

  • Mitsubishi Electronics MXZ-32SV - page 5

    5 Indoor units combination Unit A Unit B Unit C Unit D Cooling capacity (kW) T otal Outdoor unit power consumption (kW) Current (A) Power factor (%) 220V 240V 90 90 90 90 90 90 90 90 90 90 90 90 90 90 90 90 90 90 90 90 90 90 90 90 90 13.80 13.80 13.80 13.80 13.80 13.80 13.80 13.80 13.80 13.80 13.80 13.80 13.80 13.80 13.80 13.80 13.80 13.80 13.80 13 ...

  • Mitsubishi Electronics MXZ-32SV - page 6

    6 NOTE : Electrical data is for outdoor unit only . 07 09 12 18 07+07 07+09 07+12 07+18 09+09 09+12 09+18 12+12 12+18 18+18 07+07+07 07+07+09 07+07+12 07+07+18 07+09+09 07+09+12 07+09+18 07+12+12 07+12+18 07+18+18 90 90 90 90 90 90 90 90 90 90 90 90 90 90 90 90 90 90 90 90 90 90 90 90 5.23 6.1 1 8.84 10.65 8.94 9.49 1 1.81 12.41 10.88 12.13 12.87 1 ...

  • Mitsubishi Electronics MXZ-32SV - page 7

    7 Indoor units combination Unit A Unit B Unit C Unit D Heating capacity (kW) T otal Outdoor unit power consumption (kW) Current (A) Power factor (%) 220V 240V 90 90 90 90 90 90 90 90 90 90 90 90 90 90 90 90 90 90 90 90 90 90 90 90 90 12.87 12.87 12.87 12.87 12.87 12.87 12.87 12.87 12.87 12.87 12.87 12.87 12.87 12.87 12.87 12.87 12.87 12.87 12.87 12 ...

  • Mitsubishi Electronics MXZ-32SV - page 8

    8 5 SPECIFICA TION Outdoor model Indoor units number Indoor units total capacity (Connectable) indoor units total capacity (Simultaneous operation) Piping total length Connecting pipe length Height difference (Indoor ~ Outdoor) Height difference (Indoor ~ Indoor) Function Capacity Dehumidification Outdoor air flow Power outlet Running current Power ...

  • Mitsubishi Electronics MXZ-32SV - page 9

    9 NOISE CRITERIA CUR VES 6 90 80 70 60 50 40 30 20 10 63 125 250 500 1000 2000 4000 8000 APPROXIMA TE TERESHOLD OF HEARING FOR CONTINUOUS NOISE NC-60 NC-50 NC-40 NC-30 NC-20 NC-70 OCT A VE BAND SOUND PRESSURE LEVEL, 0dB = 0.0002 MICRO BAR BAND CENTER FREQUENCIES, Hz T est conditions. Cooling :DB35 : WB24 : Heating :DB 7 : WB 6 : COOL(220V) NO ...

  • Mitsubishi Electronics MXZ-32SV - page 10

    10 OUTLINES AND DIMENSIONS 7 MXZ-32SV - MXZ-32SV - E2 E1 Unit: mm OUTDOOR UNIT 23 10 35 320 900 88 460 50 900 350.0 480.8 531.3 317 23 33 Handle for moving Air in Indoor and outdoor connect wiring 23 ✕ 45 hole Air in D unit connection C unit connection B unit connection A unit connection 6.35 (flared) 1/4 Liquid pipe 12.7 (flared) 1/2 (A , B unit ...

  • Mitsubishi Electronics MXZ-32SV - page 11

    11 WIRING DIAGRAM 8 POWER SUPPLY ~/N 220-240V 50Hz INDOOR UNIT (A) CIRCUIT BRAKER TB2 TB3 BLU RED TB4 X64 GRN/YLW GRN CN720 CN601 0 4 X64 LD62 CN913 CN791 CN901 64 2 CN902 CN851 CN852 MF61 21S4 12 21 21 12 12 34 1234 5 6 1 2 345 67 1234 5 6 C65 LD63 LD64 LDB LDB LD61 LDE L61 F911 SSR61 X63 X62 X61 1 6 L N 3 N INDOOR UNIT (B) BLU ORN CN602 12 3 3 3 ...

  • Mitsubishi Electronics MXZ-32SV - page 12

    12 REFRIGERANT SYSTEM DIAGRAM 9 Unit:mm ● Refrigerant pipe diameter is different according to indoor unit to be connected. When using extension pipes,refer to the tables below . ● When diameter of refrigerant pipe is different from that of outdoor unit union, use optional Dif ferent-diameter pipe. For further information on Different-diameter p ...

  • Mitsubishi Electronics MXZ-32SV - page 13

    13 10 The standard data contained in these specifications apply only to the operation of the air conditioner under normal conditions, since operating conditions vary according to the areas where these units are installed. The following information has been pro- vided to clarify the operating characteristics of the air conditioner under the conditio ...

  • Mitsubishi Electronics MXZ-32SV - page 14

    14 10-3-.2.Capacity and input correction by inverter output frequency (OUTDOOR UNIT :MXZ-32SV) The dotted line on graphs connects the frequency range in normal operation shown by the full line and the frequency in test run shown by the point. 0 50 100 150 0.5 1.0 1.5 <COOL>Capacity Frequency Hz 0 50 100 150 0.5 1.0 1.5 2.0 Frequency <COOL& ...

  • Mitsubishi Electronics MXZ-32SV - page 15

    0 5 10 15 20 25 4 5 6 7 8 9 10 Ambient temperature( : ) 45Hz Outdoor unit current (A) Ambient temperature( : )/ Ambient humidity(%) Ambient temperature( : )/ Ambient humidity(%) Outdoor low pressure (MPa•Gauge) (kgf/ F •Gauge) Outdoor unit current (A) 15 20 25 30 35 0.2 0.3 0.4 0.5 0.6 0.7 0.8 ( ; ) (%) 33Hz 15 20 25 30 35 3 4 5 6 7 8 9 ( ; ) ( ...

  • Mitsubishi Electronics MXZ-32SV - page 16

    16 2. 09-class unit in single operation NOTE: The unit of pressure has been changed to MPa on the international system of units(SI unit system). The converted score against the traditional unit system can be gotten according to the formula below . 1(MPa • G) =10.2(kgf/ f f • G) (1) COOL operation 1 Both indoor and outdoor units are under the sa ...

  • Mitsubishi Electronics MXZ-32SV - page 17

    17 3. 12-class unit in single operation NOTE: The unit of pressure has been changed to MPa on the international system of units(SI unit system). The converted score against the traditional unit system can be gotten according to the formula below . 1(MPa • G) =10.2(kgf/ f f • G) (1) COOL operation 1 Both indoor and outdoor units are under the sa ...

  • Mitsubishi Electronics MXZ-32SV - page 18

    18 4. 18-class unit in single operation NOTE: The unit of pressure has been changed to MPa on the international system of units(SI unit system). The converted score against the traditional unit system can be gotten according to the formula below . 1(MPa • G) =10.2(kgf/ f f • G) (1) COOL operation ① ➁ Both indoor and outdoor units are under ...

  • Mitsubishi Electronics MXZ-32SV - page 19

    19 MICROPROCESSOR CONTROL 11 Compressor power factor Indoor unit microprocessor SSR61 Drive circuit T ransistor module Indoor Unit A Indoor Unit D Indoor Unit C Indoor Unit B Gas pipe temperature thermistor RT66, 67, 68, 69 Accumulator Comp. H.P .S 63H2 Discharge temperature thermistor RT61 Indoor Unit A Evaporation temperature thermistor RT63 Outd ...

  • Mitsubishi Electronics MXZ-32SV - page 20

    20 Linear expansion valve (LEV) is controlled by "Thermostat ON" commands given from each unit. • The standard opening is on the straight line, which connects an each standard point in the section where divided into seven according to the operation frequency of compressor as shown in the figure below . (LEV opening is controlled in prop ...

  • Mitsubishi Electronics MXZ-32SV - page 21

    21 (1) LEV opening correction by suction super heat (COOL, DRY) (Suction super heat) = (Minimum gas pipe temperature) - (Evaporation temperature) When COOL and DRY , correct the LEV openings corrected from the table below (2) Separate correction (COOL,DRY) (When number of operation unit is 2 units or more) (a) Correction by the separate super heat ...

  • Mitsubishi Electronics MXZ-32SV - page 22

    22 1 1-2.Operational frequency range (3) LEV opening correction by discharge temperature When LEV correction output is 0 pulse by the suction super heat at cool or dry operation, or dry operating, correct LEV is cor- rected according to the following table. The target discharge temperature is determined according to frequency zone and number of ope ...

  • Mitsubishi Electronics MXZ-32SV - page 23

    23 1 1-3.Heat defrosting control (1) Conditions to enter defrosting mode 1 . When temperature of defrosting thermistor is -3 ; or less. 2 .When specified non-defrosting time, is counted in the control p.c.board is satisfied. (T otal time of compressor operating) Going to defrosting mode at both condition of 1 and 2 . (2) Defrosting operation 1 . Co ...

  • Mitsubishi Electronics MXZ-32SV - page 24

    24 <Control status> The control performs when the following status are satisfied everything; • When there is 1 unit or more not operating indoor unit on heat operation. (Excluding thermo OFF) • When discharge temperature becomes 107 ; or more. • When it passed 60 minutes or more since the operation has started or the last refrigerant re ...

  • Mitsubishi Electronics MXZ-32SV - page 25

    25 12 TROUBLESHOOTING 3. T roubleshooting procedure 1) First, check if the OPERA TION INDICA TOR lamp on the indoor unit is flashing on and off to indicate an abnormality . T o make sure, check how many times the abnormality indication is flashing on and off before starting service work. 2) If the electronic control P .C. board is supposed to be de ...

  • Mitsubishi Electronics MXZ-32SV - page 26

    26 Outdoor power system abnor- mality When the compressor operation has been interrupted by overcurrent protection continuously three times within 1 minute after start-up, the compressor stops operation. • Inverter output • Compressor Display Detecting method Detecting method Check points Symptom Outdoor unit does not operate. Note . LED indica ...

  • Mitsubishi Electronics MXZ-32SV - page 27

    27 Frequency drop by current protection When the outdoor unit input current exceeds 22.5 A, the compressor operates at reduced frequency . These symptoms do not mean any abnormality of the product, but check the following points. • Air filter clogging. • Amount of gas. • Short cycle of indoor/outdoor air flow . Display Detecting method Detect ...

  • Mitsubishi Electronics MXZ-32SV - page 28

    28 Part name Check method and criterion Measure the resistance using a tester . (Part temperature -10°C ~ 40°C) Defrost thermistor Evaporation / Gas pipe temperature thermistor Normal abnormal 5k Ω ~ 55k Ω Opened or short-circuited Measure the resistance using a tester , after warming up the thermistor by holding by hand. (Part temperature : ...

  • Mitsubishi Electronics MXZ-32SV - page 29

    29 B B Check of serial signal T urn on power supply No Ye s Ye s No No Ye s No Ye s Start Check the connecting of main circuit parts and connector (CN501: I.P .M P . C. board, CN 801: Electronic control P . C. board, CN554: relay P . C. board) Is there voltage of 220V AC - 240V AC in the power supply terminal block? Is there voltage of 310V DC - 34 ...

  • Mitsubishi Electronics MXZ-32SV - page 30

    30 C C Check of R. V . coil No Ye s No Ye s No Ye s No Ye s No Ye s Start 1. Disconnect the lead wire leading to the compressor . 2. Turn on power supply to the indoor and outdoor unit, three minutes later EMERGENCY OPERA TION (HEA T operation) starts. Is there voltage of 220V AC - 240V AC between pin1 and pin 2 at connector CN913? T urn off power ...

  • Mitsubishi Electronics MXZ-32SV - page 31

    31 D D Check of LEV No Ye s No Ye s Start T urn on power supply to the outdoor unit after checking LEV coil is mounted to the LEV body securely . Is "click - click" sound heard? Or , do you feel vibration of the LEV coil with a hand? Disconnect the connector (CN791: unit A, CN792: unit B, CN793: unit C, CN794: unit D), and measure the res ...

  • Mitsubishi Electronics MXZ-32SV - page 32

    32 F F Check of thermistor Normal Ye s No Abnormal Reconnect the connector (CN661, CN662 and CN663) and disconnect the lead wire leading to the compressor . T urn on power supply to the indoor and outdoor unit. Three minutes later EMERGENCY OPERA TION starts. Thermistor Defrost thermistor Discharge temperature thermistor Evaporation temperature the ...

  • Mitsubishi Electronics MXZ-32SV - page 33

    H H Check of HPS Infinity 0 " Ye s No Ye s Start 1. Disconnect the connector CN722 in the electronic control P . C. board. 2. Check the resistance of HPS after 1 minutes have passed since the outdoor unit power supply was turnd off. Check the resistance between each terminal? Return CN722 to former . T urn on power supply to the indoor and out ...

  • Mitsubishi Electronics MXZ-32SV - page 34

    34 TEST POINT DIAGRAM AND VOL T AGE MXZ-32SV - , MXZ-32SV - Electronic control P .C.board E2 E1 Gas pipe temperature thermistor Evaporation temperature thermistor Defrost temperature thermistor Resistance (k Ω ) Resistance (k Ω ) T emperature( ; ) T emperature( ; ) { Fin temperature thermistor 1.0~4.0V DC Evaporation temperature thermistor 2.5~ ...

  • Mitsubishi Electronics MXZ-32SV - page 35

    35 Noise filter P .C.board MXZ-32SV - E1 { 220V -240V AC OUTPUT { 220V -240V AC INPUT { OUTDOOR F AN 220V -240V AC { REVERSING V AL VE 220V -240V AC MXZ-32SV - E2 { OUTDOOR F AN 230V AC { REVERSING V AL VE 230V AC { 230V AC OUTPUT { 230V AC INPUT FUSE 3.15A V ARISTOR OB254-2.qxp 03.1.16 4:37 PM Page 35 ...

  • Mitsubishi Electronics MXZ-32SV - page 36

    36 I.P .M P .C.board MXZ-32SV - MXZ-32SV - E2 E1 Relay P .C.board MXZ-32SV - MXZ-32SV - E2 E1 { { { { Short 12V DC High pressure switch 12V DC { 12V DC { 12V DC { 320V DC OB254-2.qxp 03.1.16 4:37 PM Page 36 ...

  • Mitsubishi Electronics MXZ-32SV - page 37

    37 OPERA TING PROCEDURE PHOTOS 1.Removing the compressor (1)Remove the screws fo the service panel, and remove it. Release refrigerant gas. (2)Remove the screws of the top panel, and remove it. (3)Remove the screws of the front panel, and remove it. (4)Disconnect the compressor lead wire. (T AB64,T AB65,T AB66) (5)Disconnect the ourdoor electronic ...

  • Mitsubishi Electronics MXZ-32SV - page 38

    38 OPERA TING PROCEDURE PHOTOS 3.Removing the 4-way valve (1)Remove the screws of the top panel, and remove it. (See Photo 1.) (2)Remove the service panel, rear panel, and connect cover panel.Release refrigerant gas. (3)Remove the electrical parts. (See Photo 2.) (4)Detach the brazed joint of 4-way valve and pipe. (See Photo 4.) 4.Removing the line ...

  • Mitsubishi Electronics MXZ-32SV - page 39

    39 OPERA TING PROCEDURE PHOTOS 5.Removing the reactor (1)Remove the five screws of the top panel, and remove it. (See Photo 1.) (2)Disconnect the reactor lead wire. (3)Remove the two screws of the reactor , and take it out. Reactor Photo 6 OB254-2.qxp 03.1.16 4:39 PM Page 39 ...

  • Mitsubishi Electronics MXZ-32SV - page 40

    40 14 Part numbers that are circled are not shown in the illustration. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 M21 17A 501 T2W E40 301 T2W E40 452 M21 17A 447 M21 17A 443 M21 17E 337 T2W E40 357 T2W E40 356 T2W E70 451 T2W E79 424 T2W G01 424 T2W E58 376 T2W E65 375 M21 42A 340 T2W E70 307 M21 42A 308 M21 17A 362 T2W G01 362 T2W E70 3 ...

  • Mitsubishi Electronics MXZ-32SV - page 41

    14-2. OUTDOOR UNIT STRUCTURAL P ARTS MXZ-32SV - MXZ-32SV - E2 E1 41 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 M21 AS2 232 M21 17A 245 T92 500 800 T2W E70 654 T2W E95 654 T2W E95 655 T2W E70 653 T2W E95 653 T2W E95 655 T2W E70 652 T2W E95 652 T2W E95 655 T2W E70 651 T2W E95 651 T2W E95 655 T2W E79 290 M21 42E 644 T2W E40 247 T2W E70 248 ...

  • Mitsubishi Electronics MXZ-32SV - page 42

    42 1 No. Parts Name Symbol in Wiring Diagram Parts No. Q'ty / unit Remarks E1 MXZ-32SV T2W E59 704 DRAIN SOCKET ASSEMBL Y 1 DRAIN SOCKET O 1 DRAIN CAP O 2 E2 1 14-3. ACCESSOR Y P ARTS 1 MXZ-32SV - MXZ-32SV - E2 E1 OB254-2.qxp 03.1.16 4:39 PM Page 42 ...

  • Mitsubishi Electronics MXZ-32SV - page 43

    43 15-1. Different-diameter pipe Unit : mm (inch) For different- diameter pipes MXZ-32SV MAC-454JP MAC-455JP MAC-456JP Model name 51H-454 51H-455 516456 Model code Connected pipes diameter (mm) Length A 69 65 66.5 Length B { 9.52 (3/8) { 12.7 (1/2) { 12.7 (1/2) { 12.7 (1/2) { 9.52 (3/8) { 15.88 (5/8) Length C { 9.52 — { 12.7 (3/8) (1/2) { 12.7 ? ...

  • Mitsubishi Electronics MXZ-32SV - page 44

    New publication, effective Jan. 2003 Specifications subject to change without notice. C C Copyright 2000 MITSUBISHI ELECTRIC ENGINEERING CO.,L TD Distributed in Jan. 2003. No.OB254 REVISED EDITION-A 7 Reprinted in Feb. 2002 No.OB254 12 Reprinted in Dec. 2001 No.OB254 5 Reprinted in Dec. 2001 No.OB254 50 Reprinted in Feb. 2001 No.OB254 10 Distribute ...

Fabricant Mitsubishi Electronics Catégorie Air Conditioner

Les documents que nous recevons du fabricant de l'appareilMitsubishi Electronics MXZ-32SV peuvent être divisés en plusieurs groupes. Ceux-ci sont, entre autres:
- dessins techniques Mitsubishi Electronics
- manuels d’utilisations MXZ-32SV
- fiches produit Mitsubishi Electronics
- dépliants
- ou étiquettes-énergie Mitsubishi Electronics MXZ-32SV
Tous sont importants, mais les informations les plus importantes du point de vue de l'utilisation de l'appareil se trouvent dans le manuel d’utilisation Mitsubishi Electronics MXZ-32SV.

Un groupe de documents appelé manuels d’utilisation est également divisé en types plus spécifiques, tels que: Manuels d’installation Mitsubishi Electronics MXZ-32SV, manuels d’entretien, brefs manuels ou manuels de l’utilisateur Mitsubishi Electronics MXZ-32SV. Selon vos besoins, vous devriez chercher le document dont vous avez besoin. Sur notre site, vous pouvez voir le manuel le plus populaire d’utilisation du produit Mitsubishi Electronics MXZ-32SV.

Manuel d’utilisation complet de l’appareil Mitsubishi Electronics MXZ-32SV, quelle devrait-elle être?
Le manuel d’utilisation, également appelé le mode d’emploi, ou tout simplement le manuel, est un document technique destiné à aider à utiliser Mitsubishi Electronics MXZ-32SV par les utilisateurs. Des manuels sont généralement écrits par un rédacteur technique, mais dans un langage accessible à tous les utilisateurs Mitsubishi Electronics MXZ-32SV.

Le manuel d’utilisation complet Mitsubishi Electronics, devrait inclure plusieurs éléments de base. Certains d'entre eux sont moins importants, tels que: la couverture / page de titre ou pages d'auteur. Cependant, la partie restante, devrait nous fournir des informations importantes du point de vue de l'utilisateur.

1. Introduction et des conseils sur la façon d'utiliser le manuel Mitsubishi Electronics MXZ-32SV - Au début de chaque manuel, nous devrions trouver des indices sur la façon d'utiliser le document. Il doit contenir des informations sur l'emplacement de la table des matières Mitsubishi Electronics MXZ-32SV, FAQ ou des problèmes les plus fréquents - les points qui sont les plus souvent recherchés par les utilisateurs de chaque manuel
2. Table des matières - index de tous les conseils pour lMitsubishi Electronics MXZ-32SV qui peuvent être trouvés dans le document courant
3. Conseils sur la façon d'utiliser les fonctions de base de l’appareil Mitsubishi Electronics MXZ-32SV - qui devraient nous aider dans les premières étapes lors de l'utilisation Mitsubishi Electronics MXZ-32SV
4. Troubleshooting - séquence systématique des activités qui nous aideront à diagnostiquer et ensuite résoudre les principaux problèmes de Mitsubishi Electronics MXZ-32SV
5. FAQ - questions fréquemment posées
6. Détails du contact Informations sur l'endroit où chercher le contact avec le fabricant / service Mitsubishi Electronics MXZ-32SV dans un pays donné, si le problème ne peut être résolu par nous-mêmes.

Avez-vous une question à propos de Mitsubishi Electronics MXZ-32SV?

Utiliser le formulaire ci-dessous

Si vous n’avez pas résolu votre problème avec Mitsubishi Electronics MXZ-32SV, avec l'aide du manuel que vous avez trouvé, posez une question en utilisant le formulaire ci-dessous. Si un utilisateur a eu un problème similaire avec Mitsubishi Electronics MXZ-32SV il est probable qu’il a envie de partager la façon de le résoudre.

Réécrire le texte de l'image

Commentaires (0)