    April 2009 © 2009 Honeywe ll. All rights reserved. 800-04410, Revision A NetAXS™ Access Control Unit User ’ s Guide If this p anel is to be added to an existing loop, then all p anels need to be upgraded. Please see www .honeywellaccess.com. ...

  • Honeywell 800-04410 - page 2

    Copyright© 2009 Honeywell. All right s reserved. All product and brand names are the service ma rks, trademarks, registe red trademarks, or registered service marks of their respec tive owners. Printed in the United S tates of America. Honeywell reserves th e right to change an y inform ation in this document at any time without prior notice. Micr ...

  • Honeywell 800-04410 - page 3

    NetAXS™ Access Control Unit User’s Guide , Document 800-04410, Revision A iii C ONTENT S What’s New in Release 3.1.8 Dynamic Screens and Performance Enhancements ............. ................... ....................... .............. ix Multi-languag e Support .............. .................... ....................... .................... . ...

  • Honeywell 800-04410 - page 4

    iv www.honeywell.com 2.7 Configuring Other I/O & Grou ps Tab ........................ .................... ...................... ................... 52 2.7.1 Inputs Tab .................................... ............................... .................................... ....... 52 2.7.2 Outputs Tab ................... ..................... ...

  • Honeywell 800-04410 - page 5

    NetAXS™ Access Control Unit User’s Guide , Document 800-04410, Revision A v L IST OF F IGURES Figure 1-1: NetAXS™ Web Server Hub Connection ........................ .................................... .... 2 Figure 1-2: NetAXS™ Web Server Direct Connection ................................... .......................... 3 Figure 2-1: NetAXS? ...

  • Honeywell 800-04410 - page 6

    vi www.honeywell.com Figure 4-6: Status > Outputs > Doors/Aux/Other/DnStr Tab ..................... ............................. 85 Figure 4-7: Status > Outputs > Groups Tab ..................... .................................... .................... 86 Figure 4-8: Status > System ................................ ................ ...

  • Honeywell 800-04410 - page 7

    NetAXS™ Access Control Unit User’s Guide , Document 800-04410, Revision A vii L IST OF T ABLES Table 1-1: Reading the Select Panel ....................... .................................... ............................. .... 7 Table 2-1: Configuration > System > Hos t/Loop Communications Ta b Field Descriptions ..... 12 Table 2-2: Confi ...

  • Honeywell 800-04410 - page 8

    viii www.honeywell.com ...

  • Honeywell 800-04410 - page 9

    NetAXS™ Access Control Unit User ’s Guide , Document 800-04410, Revision A ix What’ s New in Release 3.1.8 Dynamic Screens and Performance Enhancement s Dynamic screens are screens that can refre sh data without re-submitting. In the Honeywell NetAXS™ panel, there is now a persistent connection between the web screens and the panel. This al ...

  • Honeywell 800-04410 - page 10

    x www .honeywell.com CSV Reports and Card Upgrade CSV Report s and Card Upgrade A requested feature was added to the NetAXS™ panel to support card holder updates and additions to the database via a CSV (comma separa ted variable) file. In order to su pport this, a CSV report is first created via a request from the web page. This report can be edi ...

  • Honeywell 800-04410 - page 11

    NetAXS™ Access Control Unit User ’s Guide , Document 800-04410, Revision A 1 1 Connecting to the W eb Server In this chapter ... 1.1 Overview A NetAXS™ access control site is configur ed with a host system and NetAXS™ access control units that ex ceed existing N-1000-III/IV , Pr o Series specifications and approvals, and that commun icate w ...

  • Honeywell 800-04410 - page 12

    2 www .hon eywell.com Connecting to the Web S erver Connecting to the Web Server 1.2 Connecting to the W eb Server This section describes how to connect a computer to the NetAXS™ web se rver via Ethernet and Internet Explorer . Notes: • The NetAXS™ panel that you are connecting to th e computer is the Gateway panel. DIP switc h 6 on a Gateway ...

  • Honeywell 800-04410 - page 13

    Connecting to the We b Server Connecting to the Web Server NetAXS™ Access Control Unit User ’s Guide , Document 800-04410, Revision A 3 Figur e 1-2: NetAXS™ W eb Server Dir ect Connection 2. Configure the computer ’ s n etwork connection: a. Select Start > Setti ngs > Control Panel . b. Click Network and Dial-up Connect ions . T ermin ...

  • Honeywell 800-04410 - page 14

    4 www .hon eywell.com Connecting to the Web S erver Connecting to the Web Server c. Identify your local Ethernet connectio n (commonly labe led Local Area Connection ), and right click the icon to display the Lo cal Area Connection Properties screen. d. Highlight the Internet Pr otocol (TCP/IP) connection. e. Click Properties to display your system ...

  • Honeywell 800-04410 - page 15

    Connecting to the We b Server Connecting to the Web Server NetAXS™ Access Control Unit User ’s Guide , Document 800-04410, Revision A 5 j. Click OK to accept the entries. 3. Open your browser (Internet Explorer shown below), and ente r https://192.168.1.150 as the target address. ...

  • Honeywell 800-04410 - page 16

    6 www .hon eywell.com Connecting to the Web S erver Connecting to the Web Server 4. Press the Enter key to display the Honeywell NetAXS™ login screen. Note: If you are using Microsoft Internet E xplorer 7, and you receive a certificate error message, follow these steps to clear it: a. Enter the IP Address of the panel into the URL box. b. Click C ...

  • Honeywell 800-04410 - page 17

    Connecting to the We b Server Reading th e Select Panel NetAXS™ Access Control Unit User ’s Guide , Document 800-04410, Revision A 7 1.3 Reading the Select Panel The Select Panel is located at the right margin of the NetAXS™ web server main screen, shown in the preceding section. The presence of a number in on e of the Select Panel cells indi ...

  • Honeywell 800-04410 - page 18

    8 www .hon eywell.com Connecting to the Web S erver Reading the Select Panel Large white number on blue background, such as “2” in the example below: Panel 2 is selected, and it has no unacknowledged alarms. Small white number on a red background, su ch as “1” in the example below: Panel 1 is not selected, but it does have unacknowledged al ...

  • Honeywell 800-04410 - page 19

    NetAXS™ Access Control Unit User ’s Guide , Document 800-04410, Revision A 9 2 Configuring via the W eb Server In this chapter ... Overview 10 Configuring the System 1 1 Configuring the Doors 31 Configuring Other I/O & Groups T ab 52 Configuring Interlocks 59 Configuring T ime Management 24 Configuring Access Levels 45 Configuring Users 61 ...

  • Honeywell 800-04410 - page 20

    10 www .hon eywell.com Configuring via the We b Server Configuring the System 2.1 Overview This chapter explains the NetAXS™ configura tion functions as accessed via the NetAXS™ web server . These functions should be performed only by th e NetAXS™ system administrator or service personnel. Caution: The sequence of NetAXS™ configuration task ...

  • Honeywell 800-04410 - page 21

    Configuring via the Web Serv er Configuring the System NetAXS™ Access Control Unit User ’s Guide , Document 800-04410, Revision A 11 2.2 Configuring the System 2.2.1 Host/Loop Communications T ab In order to maintain your NetAXS™ system configurat ion or to monitor its status, you must conn ect to the NetAXS™ panel by using one of two modes ...

  • Honeywell 800-04410 - page 22

    12 www .hon eywell.com Configuring via the We b Server Configuring the System The Host/Loop Communications t ab enables you to: • Configure the following host settings: – Connection type (host or web server) – Communications type –B a u d r a t e – Port number – T ime sync • Configure the loop baud rate for co mmunicatio n among downs ...

  • Honeywell 800-04410 - page 23

    Configuring via the Web Serv er Configuring the System NetAXS™ Access Control Unit User ’s Guide , Document 800-04410, Revision A 13 Baud Rate Specifies the transmission rate (bits per second) between the host and the panel. Select the highest rate t hat your modem will support (19,200 bps is reco mmended). Port Number Specifies the port number ...

  • Honeywell 800-04410 - page 24

    14 www .hon eywell.com Configuring via the We b Server Configuring the System 2.2.2 General T ab Click Configurat ion > System in the NetAXS™ menu to display the System Configuration (General) screen: Figure 2-3: Configuration > System > General T ab The General T ab enables you to: • Set the general configuration settings. • Reset t ...

  • Honeywell 800-04410 - page 25

    Configuring via the Web Serv er Configuring the System NetAXS™ Access Control Unit User ’s Guide , Document 800-04410, Revision A 15 Boot T ime Displays the time that power was applied to the Ne tAXS™ panel. Reset Reboots the panel. A reset does not change the current configuration in the database. Anti-Passback Enabled – Enables anti-passb ...

  • Honeywell 800-04410 - page 26

    16 www .hon eywell.com Configuring via the We b Server Configuring the System Duress Detect Enabled – Enables the user to trigge r an alarm or output device in times of duress, such as when the operator is forced to grant access against his will to an unauthorized person. This feature is available only when the reader is configured with a “Card ...

  • Honeywell 800-04410 - page 27

    Configuring via the Web Serv er Configuring the System NetAXS™ Access Control Unit User ’s Guide , Document 800-04410, Revision A 17 2.2.3 File Management T ab Firmware is software that is embedded in the NetAXS™ board. The firmware provides this web interface and all access cont rol functionality . Periodically , the firmware is updated. Thi ...

  • Honeywell 800-04410 - page 28

    18 www .hon eywell.com Configuring via the We b Server Configuring the System Step s to reset the firmware ver sion: 1. In the Active Image column, clic k to select the firmware version to which you want to revert. The prompt “Switching to an alternate fi rmware set requires a panel reboot” appears. 2. Click OK to reboot the panel. Step s to re ...

  • Honeywell 800-04410 - page 29

    Configuring via the Web Serv er Configuring the System NetAXS™ Access Control Unit User ’s Guide , Document 800-04410, Revision A 19 Step s to do wnload a c ard database report (.CSV file) from the host system to the panel: 1. Click Brows e to lo cate the . CSV file. 2. Click Downlo ad to download the file. If the file is in the correct report ...

  • Honeywell 800-04410 - page 30

    20 www .hon eywell.com Configuring via the We b Server Configuring the System 2.2.4 Network T ab Y our NetAXS™ panel is physically configured in one of a number of possible network configurations. See the “System Configur ation” section in the NetAXS™ NX4L1 Installation Guide, NetAXS™ NX4S1 Installation Guide, and NetAXS™ NX4S2 Installa ...

  • Honeywell 800-04410 - page 31

    Configuring via the Web Serv er Configuring the System NetAXS™ Access Control Unit User ’s Guide , Document 800-04410, Revision A 21 2.2.5 Site Codes T ab Site codes identify an enterprise’ s site. Y ou ca n create a maximum of eight site codes to serve as secondary IDs (in addition to the card nu mber) on the card for additional validation. ...

  • Honeywell 800-04410 - page 32

    22 www .hon eywell.com Configuring via the We b Server Configuring the System 2. Click Modify to display the Name an d Site Code fields. 3. Modify the na me or site code number as you desire, and click Modi fy again. Step s to delete a site code : 1. In the Num column, click the number of the site you want to delete. 2. Click Delete to di splay a p ...

  • Honeywell 800-04410 - page 33

    Configuring via the Web Serv er Configuring the System NetAXS™ Access Control Unit User ’s Guide , Document 800-04410, Revision A 23 2.2.6 Downstream Devices T ab The NetAXS™ downstream devices provide the NetA XS™ panel with additiona l inputs and outputs. The NetAXS™ panel supports two down stream board types: • NX4IN—Provides 32 su ...

  • Honeywell 800-04410 - page 34

    24 www .hon eywell.com Configuring via the We b Server Configuring the System 2.3 Configuring T ime Management This set of time-relate d functions includ es: • Setting the current time by which the panel will function. • Creating the time zones by which the panel will control the operation of the inputs, outputs, groups, readers, access levels, ...

  • Honeywell 800-04410 - page 35

    Configuring via the Web Serv er Configuring the System NetAXS™ Access Control Unit User ’s Guide , Document 800-04410, Revision A 25 Ste ps : Use the descriptions in the following table to configure the time settings: T able 2-3: Configuration > T ime Management T ab Field Descriptions Setting Description Current loop time Displays by defaul ...

  • Honeywell 800-04410 - page 36

    26 www .hon eywell.com Configuring via the We b Server Configuring the System 2.3.2 T im e Zones T ab The NetAXS™ panel controls access by using time zo nes, or time schedules. Inputs, outputs, groups, readers, access levels, a nd cards through access levels are all conf igured with time zones by which they will be energized or de-ener gized, ena ...

  • Honeywell 800-04410 - page 37

    Configuring via the Web Serv er Configuring the System NetAXS™ Access Control Unit User ’s Guide , Document 800-04410, Revision A 27 4. If the time zone will be linked to another time zone, select the “linked to” time zone’ s number from the drop down list. Caution: W e recommend that you read the explan ation of time zone linking below ( ...

  • Honeywell 800-04410 - page 38

    28 www .hon eywell.com Configuring via the We b Server Configuring the System Note: T ime Zone 1 is reserved as a default with a time range of 24 hours, seven days a week . So, we need to add three time zone s to the panel. Then, with the Link T ime Zone feature, you can link them so that they all work together: 1. Add T ime Zon e 2 and select Mond ...

  • Honeywell 800-04410 - page 39

    Configuring via the Web Serv er Configuring the System NetAXS™ Access Control Unit User ’s Guide , Document 800-04410, Revision A 29 2.3.3 Holidays T ab Holidays are days when no work is scheduled at the facility . The se holidays are used in time zone configuration (see “ Ti m e Z o n e s T a b “ on page 26). Click the Holidays tab: Figure ...

  • Honeywell 800-04410 - page 40

    30 www .hon eywell.com Configuring via the We b Server Configuring the System While Annual is selected, the Y ear box is grayed out. The NX4 can suppor t three different Holiday T ypes (T ype 1, T ype 2, and T ype 3), but a user can on ly select one type per day . Also of no te, a single calendar day cannot be set for m ore than one type of Holiday ...

  • Honeywell 800-04410 - page 41

    Configuring via the Web Serv er Configuring the System NetAXS™ Access Control Unit User ’s Guide , Document 800-04410, Revision A 31 2.4 Configuring the Doors Each NetAXS™ panel supports four doors. For each door , you must configure the read ers, inputs, and outputs. At Configuration > Doors in the task menu at the left mar gin of the Net ...

  • Honeywell 800-04410 - page 42

    32 www .hon eywell.com Configuring via the We b Server Configuring the System • Define the time zone during which the reader will be in lockdown mode (see Time Zones T ab , page 26 for details about setting time zones). When the reader is in lockdown m ode, entry is prevented but egress is still allowed. • Define the reader ’ s access mode (t ...

  • Honeywell 800-04410 - page 43

    Configuring via the Web Serv er Configuring the System NetAXS™ Access Control Unit User ’s Guide , Document 800-04410, Revision A 33 Ste ps : 1. Use the descriptions in the table below to configure the General reader settings. T able 2-4: Configuration > Doors > Rea der T ab Descriptions Setting Description Access Mode Specifies the valid ...

  • Honeywell 800-04410 - page 44

    34 www .hon eywell.com Configuring via the We b Server Configuring the System 2. Click Card Fo rmats at the side of the tab. A card form at tells the panel how the card number will be read. The panel supplies the format to the card reader s. Then, the card readers can correctly read the card. Anti-Passback Configures the anti-passback feature, wh i ...

  • Honeywell 800-04410 - page 45

    Configuring via the Web Serv er Configuring the System NetAXS™ Access Control Unit User ’s Guide , Document 800-04410, Revision A 35 Figure 2-12: Configuration > Doors > Reade r > Car d Formats T ab 3. Click to highlight each desired card format liste d in the A vailable box, and click the green right arrow button to move the format(s) ...

  • Honeywell 800-04410 - page 46

    36 www .hon eywell.com Configuring via the We b Server Configuring the System Concatenated Site Code Combines the Site Code and Card ID as one unique num ber . T otal Num Bits Lists the total number of bits on the card. Even Parity Lists where on the card th at even parity is being observed. Star t B i t – first bit in the card wh ere even parity ...

  • Honeywell 800-04410 - page 47

    Configuring via the Web Serv er Configuring the System NetAXS™ Access Control Unit User ’s Guide , Document 800-04410, Revision A 37 6. If you want to change an existing card format’ s data layout, do uble-click the format’ s name on the list of existing formats to di splay the Card Format Data Layout scre en. Use the descriptions in the ta ...

  • Honeywell 800-04410 - page 48

    38 www .hon eywell.com Configuring via the We b Server Configuring the System 2.4.2 Output s T ab An output, or ou tput relay , is a switch on the panel that either energizes or de-ener gizes or pulses an output device, such as a door lock or an LED. For example, a successf ul card read at a reader (input device) causes the output relay switch on t ...

  • Honeywell 800-04410 - page 49

    Configuring via the Web Serv er Configuring the System NetAXS™ Access Control Unit User ’s Guide , Document 800-04410, Revision A 39 the group configuration from this screen. T o edit the Group configuration, click Config uration > Other I/O & Group s in the side panel. Figure 2-14: Configuration > Doors > Outputs > Gr oup T ab ...

  • Honeywell 800-04410 - page 50

    40 www .hon eywell.com Configuring via the We b Server Configuring the System The LED Reader dialog box enables you to configure the Rea der LED: The Output s t ab enables you to: • Configure the following for each of th e door ’ s output locks and reader LEDs: –N a m e – Pulse time – T ime zones – Latching –I n t e r l o c k – T im ...

  • Honeywell 800-04410 - page 51

    Configuring via the Web Serv er Configuring the System NetAXS™ Access Control Unit User ’s Guide , Document 800-04410, Revision A 41 Ste ps : Use the descriptions in the following table to configure each individual lock or Reader LED: T able 2-6: Configuration > Doors > Output T ab Field Descriptions Setting Description Name Enter a uniqu ...

  • Honeywell 800-04410 - page 52

    42 www .hon eywell.com Configuring via the We b Server Configuring the System 2.4.3 Input s T ab Three inputs are associated with each of the four doors on a NetAXS™ p anel: • Stat us – Provides the following door status information: • Egress – Allows the door to open or cl ose normally without generating an alarm. • T amper – Reports ...

  • Honeywell 800-04410 - page 53

    Configuring via the Web Serv er Configuring the System NetAXS™ Access Control Unit User ’s Guide , Document 800-04410, Revision A 43 The Input s t ab enables you to: • Define the Status, Egress, and T amper inputs’ access modes. • Specify the Status, Egress, and T amper shunt time, or the period of time the d oor ’ s normal state will b ...

  • Honeywell 800-04410 - page 54

    44 www .hon eywell.com Configuring via the We b Server Configuring the System Ste ps : Use the descriptions in the table below to configure the Status, Egress, and T amper inputs, the n click Submit Change s : T able 2-7: Configuration > Doors > In puts T ab Field Descriptions Setting Description Mode Normally Closed – Specifies that the do ...

  • Honeywell 800-04410 - page 55

    Configuring via the Web Serv er Configuring the System NetAXS™ Access Control Unit User ’s Guide , Document 800-04410, Revision A 45 2.5 Configuring Access Levels Every card is assigned an access level. The access level spe cifies the time zone, or time schedule, during which the card holder can be granted access at a specific door . For exampl ...

  • Honeywell 800-04410 - page 56

    46 www .hon eywell.com Configuring via the We b Server Configuring the System Step s to create an access level : 1. Select the door(s). The access level will allo w access only at the door(s) you select here. 2. Enter the name of the access level in the Nam e field. This should be a unique name th at identifies the general user group. 3. Select the ...

  • Honeywell 800-04410 - page 57

    Configuring via the Web Serv er Configuring the System NetAXS™ Access Control Unit User ’s Guide , Document 800-04410, Revision A 47 2.6 Maint aining Cards A card is encoded with a unique number and th e card holder ’ s rights to access NetAXS™ system resources. For example, in additio n to its unique number , a card wo uld allow the card h ...

  • Honeywell 800-04410 - page 58

    48 www .hon eywell.com Configuring via the We b Server Configuring the System – Use limits – Card holder note 1 – Card holder note 2 – Access levels Ste ps : Use the field descriptions in the following table to complete the card fields and click Add Card(s) : T able 2-8: Car ds > Add Car ds Field D escriptions Field Description Card Numb ...

  • Honeywell 800-04410 - page 59

    Configuring via the Web Serv er Configuring the System NetAXS™ Access Control Unit User ’s Guide , Document 800-04410, Revision A 49 2.6.2 Displaying and Modifying Cards Use this function to display sp ecified cards and modify them. Click Cards > Card Dat a to display the search scre en with which you can find and display specified cards. Fi ...

  • Honeywell 800-04410 - page 60

    50 www .hon eywell.com Configuring via the We b Server Configuring the System 2.6.3 Deleting Cards Click Cards > Delete Card(s) to display the Delete Cards screen: Figure 2-19: Car ds > Delete Car ds The Delete Card(s) screen enables y ou to: • Delete cards retrieved by any of th e following keys: – Card number – Range of card numbers ? ...

  • Honeywell 800-04410 - page 61

    Configuring via the Web Serv er Configuring the System NetAXS™ Access Control Unit User ’s Guide , Document 800-04410, Revision A 51 2.6.4 Displaying Report s Use this function to displa y a report of all cards and card data. Y ou can display the cards either by the cardholder ’ s last name or by the card number . Click Cards > Reports to ...

  • Honeywell 800-04410 - page 62

    52 www .hon eywell.com Configuring via the We b Server Configuring the System 2.7 Configuring Ot her I/O & Group s T ab The NetAXS™ panel provides up to 14 inputs and eight outputs. T wo of the inputs and four of the outputs are “other” inputs and outputs, because you can use them for other than door lock/unlock functions. This section ex ...

  • Honeywell 800-04410 - page 63

    Configuring via the Web Serv er Configuring the System NetAXS™ Access Control Unit User ’s Guide , Document 800-04410, Revision A 53 Click Input s to display the Inputs screen: Figure 2-20: Configuration > Other I/O & Gr oups > Inputs T ab The Input t ab enables you to: • Configure the mode, deboun ce time, and time zones for anothe ...

  • Honeywell 800-04410 - page 64

    54 www .hon eywell.com Configuring via the We b Server Configuring the System Ste ps : Use the descriptions in the following table to configure other panel inputs and downstream inputs: T able 2-10: Configuration > Other I/O & Gr oups > In puts T ab Field Descriptions Setting Description Name Enter a unique name to identify the device. Mo ...

  • Honeywell 800-04410 - page 65

    Configuring via the Web Serv er Configuring the System NetAXS™ Access Control Unit User ’s Guide , Document 800-04410, Revision A 55 2.7.2 Output s T ab This tab enables you to configure the four NetAXS™ auxiliary outputs (outputs 5-8) that are physically located on the panel board, and the outp uts on downs tream NX4OUT bo ards daisy-chained ...

  • Honeywell 800-04410 - page 66

    56 www .hon eywell.com Configuring via the We b Server Configuring the System Ste ps : Use the descriptions in the following table to configure each output device: T able 2-1 1: Configuration > Other I/O & Gr oups > Outputs T ab > Fields Setting Description Name Enter a unique name to identify the device. Pulse T ime Specifies the dura ...

  • Honeywell 800-04410 - page 67

    Configuring via the Web Serv er Configuring the System NetAXS™ Access Control Unit User ’s Guide , Document 800-04410, Revision A 57 2.7.3 Group s T ab This tab enables you to configu re outputs in groups. For example, you might want a group of horns in your facility to sound for the same duration or t o be enabled or disabled according to the ...

  • Honeywell 800-04410 - page 68

    58 www .hon eywell.com Configuring via the We b Server Configuring the System Ste ps : Use the descriptions in the followi ng table to configure each group: T able 2-12: Configuration > Other I/O & Gr oup s > Gr oups T ab Field Descriptions Setting Description Name Enter a unique name to identify the group. Pulse T ime Specifies the durat ...

  • Honeywell 800-04410 - page 69

    Configuring via the Web Serv er Configuring the System NetAXS™ Access Control Unit User ’s Guide , Document 800-04410, Revision A 59 2.8 Configuring Interlocks An interlock is a programmed co nnection between two points. The in terlock causes an input point, output point, or group of output points to act in a specified manner when an other inpu ...

  • Honeywell 800-04410 - page 70

    60 www .hon eywell.com Configuring via the We b Server Configuring the System Step s to create an interlock : 1. Click the New Interlock button to display the screen. 2. Use the descriptions in the followi ng table to configure the interlock: 3. Click the Add Interlock button to create the interlock. Step s to modify an interlock : 1. In the Int Lk ...

  • Honeywell 800-04410 - page 71

    Configuring via the Web Serv er Configuring the System NetAXS™ Access Control Unit User ’s Guide , Document 800-04410, Revision A 61 Step s to enable/disable an in terlock : 1. T o enable an interlock, click the Enable button. 2. T o disable an interlock, click the Disable button. 2.9 Configuring Users A user is one who will be using the NetAXS ...

  • Honeywell 800-04410 - page 72

    62 www .hon eywell.com Configuring via the We b Server Configuring the System .Click Users to display the User Configuration screen: Figure 2-24: Configuration > Users The User Configuration screen enables y ou to: • Create a user . • Modify a user . • Delet e a user . • Enable and disable a user account. • V iew the user ’ s current ...

  • Honeywell 800-04410 - page 73

    Configuring via the Web Serv er Configuring the System NetAXS™ Access Control Unit User ’s Guide , Document 800-04410, Revision A 63 5. Select the Account Status: – Enabled – Activates the user account (the user can log in). – Disabled – De-activates the user a ccount (the user cannot log in). 6. Select the user ’ s Language Prefe ren ...

  • Honeywell 800-04410 - page 74

    64 www .hon eywell.com Configuring via the We b Server Configuring the System ...

  • Honeywell 800-04410 - page 75

    NetAXS™ Access Control Unit User ’s Guide , Document 800-04410, Revision A 65 3 Configuring via WIN-P AK In this chapter ... 3.1 Overview This chapter explains the NetAXS™ conf iguration functions as accessed via the Quick Start W izard (QSW) in WIN-P AK 2005, WIN-P AK PRO 2005, WIN-P AK SE, and WIN-P AK PE. The QSW creates the AD V options a ...

  • Honeywell 800-04410 - page 76

    66 www .hon eywell.com Configuring via WIN-PAK Adding a New NetAXS™ Panel The NetAXS™ Gateway pane l’ s baud rate is se t configured via the NetAXS™ web se rver (see the NetAXS™ Access Contr ol Unit Installation Guide for instructions). When you set the Loop T ype in the QS W to 485 ACK-NAK, you define th e baud rate to be 19.2 kilobits p ...

  • Honeywell 800-04410 - page 77

    Configurin g via WIN-PAK Adding a New NetAXS™ Panel NetAXS™ Access Control Unit User ’s Guide , Document 800-04410, Revision A 67 3.2.2 Configuring the Panel Manually Use the WIN-P AK Panel Configuration screen to complete the NetAXS™ panel configuration manually . All of the configuratio n screen options are supporte d for NetAXS™ panel ...

  • Honeywell 800-04410 - page 78

    68 www .hon eywell.com Configuring via WIN-PAK Adding a New NetAXS™ Panel 3. Add the ADV . 4. Click OK . 5. Display and complete the Card Format tab: Figure 3-3: WIN-P AK Panel Configuration Screen - Card Fo rmat T ab ...

  • Honeywell 800-04410 - page 79

    Configurin g via WIN-PAK Adding a New NetAXS™ Panel NetAXS™ Access Control Unit User ’s Guide , Document 800-04410, Revision A 69 6. Display and complete the T ime Zones tab: Figure 3-4: WIN-P AK Panel Configuration Screen - T ime Zones T ab Note: All T ime Zones and Holidays are supported for a NetAXS™ panel. ...

  • Honeywell 800-04410 - page 80

    70 www .hon eywell.com Configuring via WIN-PAK Adding a New NetAXS™ Panel 7. Display and complete the Options tab: Figure 3-5: WIN-P AK Panel Configuration Screen - Options T ab Notes: • All options are supported for a NetAXS™ pane l except the Advance d U option. When using Groups, you must select bo th AEP boards in the Hard ware Options bo ...

  • Honeywell 800-04410 - page 81

    Configurin g via WIN-PAK Adding a New NetAXS™ Panel NetAXS™ Access Control Unit User ’s Guide , Document 800-04410, Revision A 71 8. Click the Advanced button to display the Ad vanced Options screen, and se lect the desired advanced options. Note that the Advanced U option is not supported for the NetAXS™ panel. 9. Display and complete the ...

  • Honeywell 800-04410 - page 82

    72 www .hon eywell.com Configuring via WIN-PAK Adding a New NetAXS™ Panel 10. Use the following procedure to reassign the interlocks: a. Display the Readers tab, and then display th e first input’ s configuration window . Select None , and click OK . This dissolves all inpu t interlocks and changes the Shunt Time to 0. This allows the input to ...

  • Honeywell 800-04410 - page 83

    Configurin g via WIN-PAK Adding a New NetAXS™ Panel NetAXS™ Access Control Unit User ’s Guide , Document 800-04410, Revision A 73 The screen captures shown below sh ow the configuration for the defa ult interlocking for a single door: 12 Reader 4 tamper/auxiliary . 13 Primary power status - external (or General input). There is also a system ...

  • Honeywell 800-04410 - page 84

    74 www .hon eywell.com Configuring via WIN-PAK Adding a New NetAXS™ Panel 1 1. The configuration of a NetAXS™ panel via WIN-P AK is now complete. Configuration is optional on the Outputs and Groups tabs. ...

  • Honeywell 800-04410 - page 85

    NetAXS™ Access Control Unit User ’s Guide , Document 800-04410, Revision A 75 4 Monitoring NetAXS™ S t atus In this chapter ... 4.1 Overview This chapter is written for the NetAXS™ operator who will monitor the following NetAXS™ status: • Alarms – Alarms are events, or system transactions, that have been assigned alarm status. These o ...

  • Honeywell 800-04410 - page 86

    76 www .hon eywell.com Monitoring NetAXS™ Status Monitoring Alarms 4.2 Monitoring Alarms Alarms are viewed as system-gener ated messages that may indica te the need for user attention. Note: From the drop down menu at the upper -right corn er of each Alarms tab, you can configure the tab to display alarms in g roups of 10, 25, 50, or 75. Click St ...

  • Honeywell 800-04410 - page 87

    Monitoring NetAXS™ Status Monitoring Alarms NetAXS™ Access Control Unit User ’s Guide , Document 800-04410, Revision A 77 Click the Acknowledged tab to display the acknowledged alarms: Figure 4-2: S tatus > Alarms > Acknowledged T ab The following table describes the information displayed on both the Unacknow ledged alarms tab and Ackno ...

  • Honeywell 800-04410 - page 88

    78 www .hon eywell.com Monitoring NetAXS™ Status Monitoring Alarms Date/T ime (ID) Identi fies the date and time the alarm was generated. Device Name [ID] Identifies the device that generated the alarm. LN Logical device numb er – the unique name or number given to the alarm-generating device when th e device was configured in Configuration > ...

  • Honeywell 800-04410 - page 89

    Monitoring NetAXS™ Status Monitoring Events NetAXS™ Access Control Unit User ’s Guide , Document 800-04410, Revision A 79 4.3 Monitoring Event s The Events page monit ors both panel- and web-ge nerated ev ents. For exampl e, a panel event is the reading of a card by a reader . A web event example is a user logon. Click St atus > Event s to ...

  • Honeywell 800-04410 - page 90

    80 www .hon eywell.com Monitoring NetAXS™ Status Monitoring Ev ents The following table describes the informa tion displayed on the Panel events tab: T able 4-2: S tatus > Events > Panel T ab Field Descriptions Column Head Description Date/T ime [ID] Provides the date and exact time the event was generated, according to the panel’ s nam e ...

  • Honeywell 800-04410 - page 91

    Monitoring NetAXS™ Status Monitoring Events NetAXS™ Access Control Unit User ’s Guide , Document 800-04410, Revision A 81 Click St atus > Event s > Web to display the W eb events tab: Figure 4-4: S tatus > Events > W eb T ab Note: The number of active users is indicate d in the upper left co rner of the tab. ...

  • Honeywell 800-04410 - page 92

    82 www .hon eywell.com Monitoring NetAXS™ Status Monitoring Inputs 4.4 Monitoring Input s A NetAXS™ panel supports door , pa nel, and auxiliary inputs. The do or inputs provide egress and tamper status, the panel in puts provide power fail and tamper stat us, and the auxiliary inputs support any downstream status. Click St atus > Input s to ...

  • Honeywell 800-04410 - page 93

    Monitoring NetAXS™ Status Monitoring Inputs NetAXS™ Access Control Unit User ’s Guide , Document 800-04410, Revision A 83 Ste ps : 1. T o shunt or un-shunt an input, click th e input name to display a prompt. Click OK to complete the shunt or un-shun t. ...

  • Honeywell 800-04410 - page 94

    84 www .hon eywell.com Monitoring NetAXS™ Status Monitoring Inputs 2. T o restore the input to its shunt state based on its configured time zone, click the input’ s Restore to Time Zone button to display a prompt. Click OK to complete the restor ation to the configured time zone. Note: The Input Status screen dynamically refreshes when input st ...

  • Honeywell 800-04410 - page 95

    Monitoring NetAXS™ Status Monitoring Outputs NetAXS™ Access Control Unit User ’s Guide , Document 800-04410, Revision A 85 4.5 Monitoring Output s An output is an output d evice that changes its norm al state when it is ener gized, pulse d, or time-zone controlled. For example, a successful card read at a reader pulses a door lock. The lock c ...

  • Honeywell 800-04410 - page 96

    86 www .hon eywell.com Monitoring NetAXS™ Status Monitoring Outputs Click St atus > Outputs > Groups to display the Groups tab of the Output Status screen: Figure 4-7: S tatus > Outputs > Gr oups T ab The Output S tatus t ab enables you to: • V iew the current status of each output in the Discrete tab (Energized or De-ener gized). ? ...

  • Honeywell 800-04410 - page 97

    Monitoring NetAXS™ Status Monitoring System St atus NetAXS™ Access Control Unit User ’s Guide , Document 800-04410, Revision A 87 4.6 Monitoring System S t atus This feature provides ba sic monitoring of objects in the NetAXS™ system ot he r than alarms, events, inputs, and ou tputs. Click St atus > System to display the System S tatus s ...

  • Honeywell 800-04410 - page 98

    88 www .hon eywell.com Monitoring NetAXS™ Status Monitoring Sy stem S tatus ...

  • Honeywell 800-04410 - page 99

    NetAXS Access Control Unit User’s Guide , 800-04410, R evision A 89 A Upgrading NetAXS™ Firmware A.1 Overview This appendix provides in structions for upgradin g Ne tAXS™ firmware to release 3.1.8. This version is a new release; it replaces a ll builds of releases 1 and 2, and it includes all functionality provided in Ne tAXS™ releases 1 an ...

  • Honeywell 800-04410 - page 100

    90 www .hon eywell.com Upgrading NetAXS™ Firmw are NetAXS™ Release 3.1.8 Upgrade Procedure Release 3 has a new access-le vel database; therefore, any release 3 access-leve l database changes will not take ef fect until the entire l oop is upgraded to release 3. A.2.3 Uploading Dat a from the Panel Note: Before you upgrade a web-based panel, we ...

  • Honeywell 800-04410 - page 101

    Upgrading NetAXS™ Firmw are NetAXS™ Release 3.1.8 Upgrade Procedure NetAXS Access Control Unit User ’s Guide , 800-04410, Revision A 91 Note: For WIN-P AK systems, we recommend that you stop the “communications server service” while upgrading, and then restart the servi ce after your panels are upgraded. 2. Connect to your gateway pan el ...

  • Honeywell 800-04410 - page 102

    92 www .hon eywell.com Upgrading NetAXS™ Firmw are NetAXS™ Release 3.1.8 Upgrade Procedure 8. Install the new application file, 3-Ne tAXSimage0 3.01.08.bin. T o do this: a. Select the Configuration > System > File Management tab. b. In the Download box, click Br owse to locate the file, 3- NetAXSimage03.01.08.bin . c. Select the file and ...

  • Honeywell 800-04410 - page 103

    Upgrading NetAXS™ Firmw are NetAXS™ Release 3.1.8 Upgrade Procedure NetAXS Access Control Unit User ’s Guide , 800-04410, Revision A 93 i. Click OK . j. Close the web brows er and re-open it. k. Enter the IP Address again into the URL box. The login screen appears without the certificate error A.2.6 Clearing the Cache in the Inter net Browser ...

  • Honeywell 800-04410 - page 104

    94 www .hon eywell.com Upgrading NetAXS™ Firmw are NetAXS™ Release 3.1.8 Upgrade Procedure ...

  • Honeywell 800-04410 - page 105

    NetAXS™ Access Control Unit User’s Guide , Document 800-04410, Revision A Index - 1 Index A Access level 2-45 Access mode 2-33 Acknowledged alarms 4-77 Administrator 2-61 Alarms 4-75, 4-76 acknowledged 4-77 monitoring 4-76 Anti-passback 2-15, 2-34 Auto-relock 2-44, 2-54 Auxiliary outputs 2-55 B Baud rate host 2-13 loop 2-13 C Card and PIN dures ...

  • Honeywell 800-04410 - page 106

    In d e x Index-2 www.honeywell.co m Downstream baud rate 2-13 force baud reset 2-13 inputs 2-52 outputs 2-55 Downstream devices 2-23 Duress detect 2-16 E Egress 2-42 Energizing 2-26 Events 4-75, 4-79 F File management 2-17 Firmware downloading 2-17 for WIN-PAK configuration 3-67 reverting to previous 2-17 First card rule 2-41 Force baud reset 2-13 ...

  • Honeywell 800-04410 - page 107

    Index NetAXS™ Access Control Unit User’s Guide , Document 800-04410, Revision A Index - 3 NX4IN/NX4OUT boards 2-55 NX4IN/NX4OUTboards 2-52 O Operator 2-61 Output relay 2-38 Outputs 2-38, 4-75 auxiliary 2-55 de-energizing 4-86 downstream 2-23 energizing 4-86 groups 2-57 interlock 2-56 interlocks 2-59 latching 2-56 monitoring 4-85 pulsing 4-86 re ...

  • Honeywell 800-04410 - page 108

    Index Index-4 www.honeywell.co m U Unsupervised 2-43, 2-44 Uploading card and configuration data 2-17 Use limits 2-48 Users 2-61 W Web mode monitoring and configurin g 2-11 Web server 1-1 Web server conn ection 1-2 direct 1-3 hub 1-2 Web session timeout 2-15 ...

  • Honeywell 800-04410 - page 109

    Honeywell Access Sy stems 135 W . Forest Hill Avenue Oak Creek, WI 53154 United S tates 800-323-4576 414-766-1798 Fax www .honeywellaccess.com S pecifications subject to change without notice. © Honeywell. All rights reserved. Document 800-04410, Revision A ...

Fabricant Honeywell Catégorie Home Security System

Les documents que nous recevons du fabricant de l'appareilHoneywell 800-04410 peuvent être divisés en plusieurs groupes. Ceux-ci sont, entre autres:
- dessins techniques Honeywell
- manuels d’utilisations 800-04410
- fiches produit Honeywell
- dépliants
- ou étiquettes-énergie Honeywell 800-04410
Tous sont importants, mais les informations les plus importantes du point de vue de l'utilisation de l'appareil se trouvent dans le manuel d’utilisation Honeywell 800-04410.

Un groupe de documents appelé manuels d’utilisation est également divisé en types plus spécifiques, tels que: Manuels d’installation Honeywell 800-04410, manuels d’entretien, brefs manuels ou manuels de l’utilisateur Honeywell 800-04410. Selon vos besoins, vous devriez chercher le document dont vous avez besoin. Sur notre site, vous pouvez voir le manuel le plus populaire d’utilisation du produit Honeywell 800-04410.

Manuels d’utilsiation similaires

Manuel d’utilisation complet de l’appareil Honeywell 800-04410, quelle devrait-elle être?
Le manuel d’utilisation, également appelé le mode d’emploi, ou tout simplement le manuel, est un document technique destiné à aider à utiliser Honeywell 800-04410 par les utilisateurs. Des manuels sont généralement écrits par un rédacteur technique, mais dans un langage accessible à tous les utilisateurs Honeywell 800-04410.

Le manuel d’utilisation complet Honeywell, devrait inclure plusieurs éléments de base. Certains d'entre eux sont moins importants, tels que: la couverture / page de titre ou pages d'auteur. Cependant, la partie restante, devrait nous fournir des informations importantes du point de vue de l'utilisateur.

1. Introduction et des conseils sur la façon d'utiliser le manuel Honeywell 800-04410 - Au début de chaque manuel, nous devrions trouver des indices sur la façon d'utiliser le document. Il doit contenir des informations sur l'emplacement de la table des matières Honeywell 800-04410, FAQ ou des problèmes les plus fréquents - les points qui sont les plus souvent recherchés par les utilisateurs de chaque manuel
2. Table des matières - index de tous les conseils pour lHoneywell 800-04410 qui peuvent être trouvés dans le document courant
3. Conseils sur la façon d'utiliser les fonctions de base de l’appareil Honeywell 800-04410 - qui devraient nous aider dans les premières étapes lors de l'utilisation Honeywell 800-04410
4. Troubleshooting - séquence systématique des activités qui nous aideront à diagnostiquer et ensuite résoudre les principaux problèmes de Honeywell 800-04410
5. FAQ - questions fréquemment posées
6. Détails du contact Informations sur l'endroit où chercher le contact avec le fabricant / service Honeywell 800-04410 dans un pays donné, si le problème ne peut être résolu par nous-mêmes.

Avez-vous une question à propos de Honeywell 800-04410?

Utiliser le formulaire ci-dessous

Si vous n’avez pas résolu votre problème avec Honeywell 800-04410, avec l'aide du manuel que vous avez trouvé, posez une question en utilisant le formulaire ci-dessous. Si un utilisateur a eu un problème similaire avec Honeywell 800-04410 il est probable qu’il a envie de partager la façon de le résoudre.

Réécrire le texte de l'image

Commentaires (0)