Manuale per l’uso Ariston 41-116-04

44 pagine 4.52 mb
Scarica

Vai alla pagina of 44

Summary
  • Ariston 41-116-04 - page 1

    Installation Instructions T ype C Boilers G.C.N: 41-116-04 LEA VE THESE INSTRUCTIONS WITH THE END-USER Countr y of destination: GB ...

  • Ariston 41-116-04 - page 2

    This manual is an integr al and essential par t of the product. It should be kept with the appliance so that it can be consulted by the user and our authorised personnel. Please carefully read the instructions and notices about the unit contained in this manual, as the y provide important inf ormation regarding the safe installation, use and mainte ...

  • Ariston 41-116-04 - page 3

    3 1.1 G ENERAL I NSTRUCTIONS Read the instructions and recommendations in these Installation Instructions carefully to ensure proper installation, use and maintenance of the appliance. K eep this manual in a safe place . Y ou ma y need it for your o wn reference while our Ser vicing Centre technicians or your installer ma y need to consult it in th ...

  • Ariston 41-116-04 - page 4

    4 The technical inf ormation and instr uctions provided herein below are intended f or the installer so that the unit ma y be installed correctly and saf ely . The installation and initial star t up of the boiler must be by a CORGI Registered Installer in compliance with the installation standards currently in eff ect, as well as with any and all l ...

  • Ariston 41-116-04 - page 5

    F or saf ety pur poses, ha ve a competent person carefully check the electrical system in the proper ty , as the manufacturer will not be held liab le for damage caused b y the f ailure to ear th the appliance properly or b y anomalies in the supply of power . Make sure that the residential electrical system is adequate for the maximum po wer absor ...

  • Ariston 41-116-04 - page 6

    6 The boiler operates with alternating current, as indicated in the technical inf ormation table in section 7, where the maximum absorbed power is also indicated. Make sure that the connections f or the neutral and liv e wires correspond to the indications in the diagram. The appliance electr ical connections are situated on the re verse of the con ...

  • Ariston 41-116-04 - page 7

    7 C ENTRAL H EA TING Detailed recommendations are given in BS 6798:1987 and BS 5449-1:1990, the f ollowing notes are giv en for general guidance . P IPE W ORK : Copper tubing to BS EN 1057:1996 is recommended f or water pipes . Jointing should be either with capillar y soldered or compression fittings. Where possible pipes should ha ve a gradient t ...

  • Ariston 41-116-04 - page 8

    8 Ø 60/100 mm F IG . 2.6 A BC D E F G J K HI L G F The boiler is designed to be connected to a coaxial flue discharge system. 2.9 F LUE C ONNECTIONS F LUE S YSTEM The provision f or satisfactory flue ter mination must be made in accordance with BS 5440-1. The appliance must be installed so that the flue terminal is exposed to outside air . The ter ...

  • Ariston 41-116-04 - page 9

    Exhaust T ype C12 (xx) C32 (xx) C42 (xx) Restrictor ø 44 mm L min = 0.5 m L max = 1 m Maximum Extension Exhaust/Air L = 5 m Risk of Condensation Forming Coaxial Systems ø 60/100 Piping not insulated ø 44 restrictor NO restrictor NONE NONE Piping insulated ø 44 restrictor NO restrictor NONE NONE T ABLE 2.1 10 RFFI T o connect a room thermostat a ...

  • Ariston 41-116-04 - page 10

    2.11 E LECTRICAL D IA GRAM 10 F IG . 2.12 Legend: A - On/Off Switch B - On/Off L.E.D . C - Heating Switch D - Heating L.E.D . E - Reset Button F - Ignition F ailure (Lock out) L.E.D . A01 - Pump Pressure Switch A02 - F rost Thermostat A03 - Modulator A04 - Circulation Pump A05 - Regulation Thermostat A06 - Exter nal Control System A07 - Time Clock ...

  • Ariston 41-116-04 - page 11

    11 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 L EGEND : 1. F an 2. Main heat exchanger 3. Overheat thermostat 4. Bur ner 5. Ignition electrodes 6. Detection electrode 7. Regulation ther mostat 8. F rost ther mostat 9. Gas valv e 10. Pump pressure s witch 11. Saf ety valv e (3 bar) 12. Boiler drain v alve 13. A utomatic by-pass 14. Pressure gauge 15. ...

  • Ariston 41-116-04 - page 12

    12 3. D .H.W . ST ORA GE CYLINDER The microSYSTEM can be connected to a storage cylinder (both open-v ented and unv ented) for the production of domestic hot w ater (D .H.W .). Cylinders of diff erent capacities can be used depending on site requirements (see T ABLE 3.1 f or a selection of ARIST ON unvented cylinders). F IG . 3.2 3 port valve insta ...

  • Ariston 41-116-04 - page 13

    13 T echnical Data Capacity Coil C.H.W . D .H.W . Max Heating Heat Ioss Surface Flow/rate Flo w/rate Output MODEL It. m 2 m 3 /h It/h kW kWh/24h Contract STI 125 Indirect 125 0.75 0.5 194 11.3 2 1 266 15.5 2 340 19.8 Comfort STI 125 Indirect 125 0.75 0.5 256 14.9 2.2 Contract STI 150 Indirect 150 0.93 1 353 20.5 2 451 26.2 Comfort STI 150 Indirect ...

  • Ariston 41-116-04 - page 14

    14 MTS (GB) Limited suppor t the initiative. Within the inf or mation pack you will find a cop y of the logbook. It is impor tant that this is completed in the presence of your customer , the y are shown ho w to use it, and it is signed by them. Please instruct your customer that they m ust have their logbook with them whene ver the y contact a ser ...

  • Ariston 41-116-04 - page 15

    B 4 5 In order to access the inside of the boiler , it is necessar y to unscrew the f astening screws “A” of the control panel located on the lower part of the panel itself. The control panel mov es downward and when pulled f orward rotates on two lateral hinges . The panel sta ys in a semi-horizontal position, which allows access to the inner ...

  • Ariston 41-116-04 - page 16

    16 The flue connector has two aper tures, readings can be tak en for the temperature of the comb ustion by-products and of the combustion air , as well as of the concentr ations of O 2 and CO 2 , etc. . T o access these intakes it is necessary to unscrew the front screw and remo ve the metal plate with sealing gasket. T o achie ve the best test con ...

  • Ariston 41-116-04 - page 17

    The boiler is fitted with the f ollowing de vices (see section 4.2 for ref erences). 1 - I GNITION F AILURE : This indicates ignition f ailure when a flame is not detected within 7 seconds of star ting an ignition sequence. The L.E.D . “F” will illuminate to signal the shutdown status . The system can be reset by pressing and releasing the b ut ...

  • Ariston 41-116-04 - page 18

    18 The boiler can be con ver ted to use either methane (natural) gas (G20) or LPG (G30 - G31) by an A uthorised Service Centre . The operations that must be perf or med are the follo wing: 1. Replace the jets on the main burner (see table in section 5); 2. P ay attention to put the gas restrictor if con vert the boiler from NG to GPL and to take it ...

  • Ariston 41-116-04 - page 19

    19 It is recommended that the follo wing inspections be carried out on the boiler at least once a year: 1 - Check the seals f or the water connections; replace any f aulty seals. 2 - Check the gas seals; replace any faulty gas seals . 3 - Visual check of the entire unit. 4 - Visual check of the comb ustion process or analysis of combustion by-produ ...

  • Ariston 41-116-04 - page 20

    Manuf acturer : Merloni T ermoSanitari SpA - Italy Commercial subsidiar y: MTS (GB) LIMITED MTS Building Hughenden A venue High Wycombe Bucks HP13 5FT T elephone: (01494) 755600 F ax: (01494) 459775 Internet: http://www .mtsgb.ltd.uk E-mail: inf o@mtsgb.ltd.uk T echnical Service Hot Line: (01494) 539579 23 99 84 1581 000 - Stampa: bief fe RECANA TI ...

  • Ariston 41-116-04 - page 21

    Servicing Instructions T ype C Boilers G.C.N: 41-116-04 LEA VE THESE INSTRUCTIONS WITH THE END-USER Countr y of destination: GB ...

  • Ariston 41-116-04 - page 22

    2 1. SER VICING INSTR UCTIONS 1.1 R EPLACEMENT OF P AR TS 1.2 T O G AIN G ENERAL A CCESS - Removing the front panel - Removing the sealed chamber front co ver - Removing the side panels 1.3 A CCESS T O THE C OMBUSTION C HAMBER - Removing the comb ustion cover - Removing the b ur ner and jets - Removing the electrodes - Removing the main heat e xcha ...

  • Ariston 41-116-04 - page 23

    2. The control panel mov es downward and when pulled f orward, rotates on two lateral hinges; the panel sta ys in a semi- horizontal position, which allows access to the inner parts of the boiler (F IG . 1.2); 3. In order to increase the manouvering space, it is possib le to raise the control panel and rotate it to a fully horizontal position (F IG ...

  • Ariston 41-116-04 - page 24

    4 1.2.2 Removing the sealed c hamber front cover 1. Remov e the screws “C” (F IG . 1.6); 2. Lift the sealed chamber front cov er from the locating pins (F IG . 1.7). F IG . 1.6 C C F IG . 1.7 1.2.3 Removing the side panels 1. Remov e the four scre ws “D” for each side panel (F IG .1.8); 2. Pull the panel aw ay from the boiler at the base, t ...

  • Ariston 41-116-04 - page 25

    1.3.3 Removing the electr odes Bef ore carr ying out this procedure, unscrew and slide the burner forw ard (see previous section). 1. Remov e r ubber gask et “G” (F IG . 1.12); 2. T o remove the detection electrode disconnect the cab le at its connection point close to the P .C.B . (F IG . 1.13); F IG . 1.12 G F IG . 1.13 1.3.2 Removing the b u ...

  • Ariston 41-116-04 - page 26

    6 3. Remov e screw “H” ( F IG . 1.14); 4. Gently slide the electrode downw ard (F IG . 1.15) . T o replace, repeat the steps in rev erse order , paying par ticular attention to the follo wing: a - Centre the electrode in the positioning hole carefully , otherwise the electrode ma y break; b - Ensure that the left hand and right hand electrodes ...

  • Ariston 41-116-04 - page 27

    1. Disconnect electrical connections “N” and silicon pipe “O” (F IG .1.22); 2. Remov e screw “P” and remove the f an collar clamp “Q” (F IG .1.23); 3. Remov e screws “R” (F IG .1.24); 4. Remov e fan and mounting plate (F IG .1.25). 1.3.6 Removing the fan 1. Disconnect the electrical connections “K” and silicone pipes “L ? ...

  • Ariston 41-116-04 - page 28

    8 1.4 S ER VICING AND R EMO V AL OF THE G AS V AL VE 1.4.1 Setting the gas pressures 1 2 3 A B C F D Setting the maximum po wer of the boiler 1. Check that the supply pressure to the gas v alve is a minim um of 20 mbar f or natural gas. T urn off the gas suppl y at the isolation point under the boiler 2. T o do this, slack en the screw “A” . Fi ...

  • Ariston 41-116-04 - page 29

    9 1.22 20 8.3 2.9 2.9 ---- ----- ----- 0.91 Kg/h ------ Kg/h 22.9 mbar ---- mbar 28 mbar 0.90 Kg/h ------ Kg/h 29.5 mbar ---- mbar 37 mbar 6 x 1.30 6 x 0.77 6 x 0.77 Gas restrictor ¿ 10 RFFI T ABLE A TB016A 6. Remov e the pipe from the pressure gauge and connect screw “ C ” to the pressure outlet in order to seal off the gas. 7 . Carefully che ...

  • Ariston 41-116-04 - page 30

    10 F IG . 1.28 F IG . 1.29 U V V 1.4.3 Removing the gas v alve Impor tant! Before removing the gas v alve , ensure the gas supply is tur ned off . 1. Disconnect all the cables from the solenoid and modureg; 2. Remov e the spar k generator (see pre vious section); 3. Release the top nut “ U ” (F IG . 1.28); 4. Remov e the screws “ V ” from t ...

  • Ariston 41-116-04 - page 31

    11 1. 5. 2 Removing the safety v alve 1. Loosen nut “ Y ” (F IG . 1.33); 2. Disconnect the discharge pipe work from below the boiler ; 3. Unscrew and remo ve the v alve. 1.5.3 Removing the automatic air vent 1. Unscrew v alve top “ Z ” (F IG . 1.34); 2. Remov e valv e complete with float (F IG 1.35). F IG . 1.33 F IG . 1.34 Y Z F IG . 1.35 ...

  • Ariston 41-116-04 - page 32

    12 1.5.4 Removing the pump 1. Remov e the U-clips “ A1 ” and “ B1 ” (F IG . 1.36); 2. Remov e the retaining clip “ C1 ” (F IG . 1.37); 3. Release the nut “ D1 ” (F IG . 1.38); 4. Remov e the pipe “ E1 ” (F IG . 1.39); 5. Remov e the screw “ F1 ” (F IG . 1.40); 6. Remov e the pump (F IG . 1.41). F IG .1 . 3 7 F IG .1 . 3 6 F ...

  • Ariston 41-116-04 - page 33

    13 1.5.6 Removing the e xpansion vessel 1. Release nuts “ H1 ” and remov e the gas pipe (F IG . 1.44); 2. Release nut “ I1 ” (F IG . 1.45); 3. Remov e lock-nut “ J1 ” (F IG . 1.46); 4. Remov e the expansion v essel (F IG . 1.47). 1.5.5 Removing the pressure gauge 1. Remov e the U-clip “ G1 ” and remo ve the pressure gauge coupling ( ...

  • Ariston 41-116-04 - page 34

    14 1.5.6 Removing the o verheat thermostat 1. Disconnect the ov erheat ther mostat electrical connections “ K1 ” (F IG . 1.48); 2. Then remov e the ther mostat from its mounting by releasing the securing clip (F IG . 1.49). 1.5.7 Removing the fr ost thermostat 1. Disconnect the frost thermostat electr ical connection “ L1 ” (F IG . 1.50); 2 ...

  • Ariston 41-116-04 - page 35

    15 1.6.2 Removing the P .C.B.s 1. Isolate electricity; 2. Remov e the screws “ O1 ” (F IG . 1.56); 3. Separate the f acia panel from the rear of the control panel; 4. Unplug all electrical connections from the P .C .B. and remov e the screws “ P1 ” and remove the P .C.B . (F IG . 1.57). F IG . 1.56 O1 O1 O1 O1 O1 P1 P1 P1 P1 O1 F IG . 1.57 ...

  • Ariston 41-116-04 - page 36

    16 B063 2. F A UL T FINDING P RELIMINAR Y CHECKS MAKE SURE THA T : IS THE SUPPL Y L.E.D. ILLUMINATED? IS THE L.E.D. ILLUMINA TED? NO NO NO YES NO 1 - C HECK THE FUSES 2 - C HECK THERE IS POWER SUPPLIED TO THE P .C.B. S 3 - C HECK / REPLACE THE P. C . B . (CT1) 1 - C HECK THE INTEGRITY OF THE L.E.D. 2-C HECK / REPLACE THE P .C.B. (CT1) P RESS THE ON ...

  • Ariston 41-116-04 - page 37

    17 B063 IS THE PUMP RUNNING? NO YES PO WER T O THE PUMP? 1 - C HECK THE OPERA TION OF THE PUMP 2 - R ELEASE /R EPLA CE THE PUMP 1 - C HECK THE PUMP CABLE 2- C HECK /R EPLA CE P. C . B . (CT1) 3 - C HECK THE SYSTEM PRESSURE GA UGE IS A T 1.5 BAR A IS THE F AN RUNNING? BOILER SHUTDO WN? PO WER T O THE F AN? NO YES YES NO YES NO NO YES 1 - C HECK /R E ...

  • Ariston 41-116-04 - page 38

    18 B063 IS THE BURNER ALIGHT? YES NO YES YES BOILER WORKING? YES NO NO NO NO YES 5- C HECK /R EPLACE P .C . B . (CBM2) 4-C HECK /R EPLACE P .C .B. (CBM2) 4 - C HECK /R EPLA CE P .C.B . (CBM2) 1 - C HECK /R EPLACE IGNITION ELECTRODES 2 - C HECK THE CABLES 3 - C HECK SP ARK GENERA T OR 4 - C HECK IGNITION ELECTRODE CABLES 1 - C HECK POWER SUPPL Y T O ...

  • Ariston 41-116-04 - page 39

    19 B063 3. ELECTRICAL DIA GRAMS SE011A L EGEND : A - On/Off Switch B - On/Off L.E.D . C - Heating Switch D - Heating L.E.D . E - Reset Button F - Ignition F ailure (Lock out) L.E.D . A01 - Pump Pressure Switch A02 - F rost Ther mostat A03 - Modulator A04 - Circulation Pump A05 - Regulation Ther mostat A06 - Exter nal Control System A07 - Time Clock ...

  • Ariston 41-116-04 - page 40

    20 B063 SF008A ...

  • Ariston 41-116-04 - page 41

    21 B063 MODELS CHARACTERISTICS SERIAL NO: VALIDITY REF. MICROSYSTEM 10 RFFI METHANE 2320021100001 A MICROSYSTEM 10 RFFI LPG 2320021100001 B MICROSYSTEM 15 RFFI METHANE 2320021100001 C MICROSYSTEM 15 RFFI LPG 2320021100001 D 13 24 30 31 37 13 19 20 16 14 17 15 6 4 3 5 57 56 55 54 53 49 1 41 43 47 48 46 45 35 34 32 31 44 50 42 13 96 85 88 21 23 22 19 ...

  • Ariston 41-116-04 - page 42

    22 B063 998616 573521 573520 570760 998612 573528 998447 569390 998627 999542 574279 999474 998809 999476 998424 998836 999578 999499 999245 998517 998484 997182 999538 998624 998622 998623 998893 999481 999686 999479 999685 998433 998434 999501 950030 999486 998487 998488 998644 998643 998738 998961 998716 998717 Key no. G.C. part no. ARISTON Part ...

  • Ariston 41-116-04 - page 43

    23 B063 NO TES ...

  • Ariston 41-116-04 - page 44

    23 99 84 1582 000 - Manuf acturer : Merloni T ermoSanitari SpA - Italy Commercial subsidiar y: MTS (GB) LIMITED MTS Building Hughenden A venue High Wycombe Bucks HP13 5FT T elephone: (01494) 755600 F ax: (01494) 459775 Inter net: http://www .mtsgb .ltd.uk E-mail: inf o@mtsgb.ltd.uk T echnical Service Hot Line: (01494) 539579 ...

Fabbricante Ariston Categoria Boiler

I documenti che otteniamo dal fabbricante del dispositivoAriston 41-116-04 possono essere suddivisi in diversi gruppi. Questi sono tra gli altri:
- disegni tecnici Ariston
- manuali per l’uso 41-116-04
- schede prodotto Ariston
- opuscoli
- o etichette energetiche Ariston 41-116-04
Tutti sono importanti, ma le informazioni più importanti dal punto di vista di utilizzo del dispositivo possono essere trovate nel manuale per l’uso Ariston 41-116-04.

Un gruppo di documenti denominato manuali per l’uso, è anche suddiviso in tipi più specifici, come: Manuali di installazione Ariston 41-116-04, manuali di manutenzione, brevi manuali o manuali utente Ariston 41-116-04. A seconda delle esigenze, si dovrebbe cercare il documento necessario. Nel nostro sito web, puoi visualizzare il manuale più popolare per l'uso del prodotto Ariston 41-116-04.

Manuali per l’uso simili

Manuale completo del dispositivo Ariston 41-116-04, come deve essere?
Il manuale per l’uso, denominato anche istruzioni per l’uso, o semplicemente il manuale è un documento tecnico progettato per aiutare ad utilizzare Ariston 41-116-04 dagli utenti. I manuali sono di solito scritti da uno scrittore tecnico, ma in un linguaggio accessibile a tutti gli utenti Ariston 41-116-04.

Il manuale per l’uso completo Ariston, dovrebbe includere vari elementi di base. Alcuni di loro sono meno importanti, come ad esempio: copertina / pagina del titolo o pagina di autore. Tuttavia, la parte rimanente, dovrebbe fornire informazioni importanti dal punto di vista dell'utente.

1. Introduzione e la guida su come utilizzare il manuale Ariston 41-116-04 - All'inizio di ogni manuale, dovremmo trovare indizi su come utilizzare il documento. Dovrebbe contenere informazioni sulla posizione dell’indice Ariston 41-116-04, FAQ o i problemi più comuni : i punti che sono più spesso cercati dagli utenti di ogni manuale
2. Indice - elenco di tutti i suggerimenti per Ariston 41-116-04 che possono essere trovati nel documento corrente
3. Suggerimenti su come utilizzare le funzioni di base del dispositivo Ariston 41-116-04 - che ci dovrebbe aiutare nei primi passi durante l'uso Ariston 41-116-04
4. Troubleshooting - sequenza sistematica delle attività che vi aiuterà a diagnosticare e, successivamente, risolvere i problemi più importanti del Ariston 41-116-04
5. FAQ - domande più frequenti
6. Dettagli di contatto Informazioni su dove cercare il contatto con il fabbricante / servizio Ariston 41-116-04 in un dato paese, se il problema non può essere risolto da noi stessi.