    Part No. 312755-G Rev 00 May 2006 4655 Great America Parkway Santa Clara, CA 95054 Installing the Breaker Interface P anel f o r the Ethernet Routing Switch 8010co Chassis ...

  • Nortel Networks 8010co - page 2

    2 312755-G Rev 00 Copyright © 2006 Nortel Netw orks. All Rights Reserved. The information in this document is subj ect to change without notice. The statements, config urations, technical data, and recommendations in this docume nt are believ ed to be accura te and reliable, but are presen ted without e xpress or implied warranty . Users must take ...

  • Nortel Networks 8010co - page 3

    3 Installing the Breaker Interface Panel for th e Ethernet Routing Switch 8010co Chassis Règlement sur le br ouillage radioélectriq ue du ministère des Comm unications Cet appareil numérique (8000 Series cha ssis) respecte les limites de bruits r adioé lectriques visant les appareils numériques de classe A prescr ites dans le Règlement sur l ...

  • Nortel Networks 8010co - page 4

    4 312755-G Rev 00 Denan statement (Japan/Nippon only) National safety stat ements of compliance CE marking statement (Europe onl y) EN 60 950 statement This is to certify that the Nortel 8000 Se ries chassis and components installed within the chassi s are in compliance with the requirements of EN 60 950 in accordance with the Low V oltage Directiv ...

  • Nortel Networks 8010co - page 5

    5 Installing the Breaker Interface Panel for th e Ethernet Routing Switch 8010co Chassis re verse engineer or otherwise translat e the Softw are; c) create deri v ati v e w orks or modifications unless e xpressly authorized; or d) sublicense, rent or le ase the Software. Licensors of intellectual property to No rt el are beneficiaries of this provi ...

  • Nortel Networks 8010co - page 6

    6 312755-G Rev 00 ...

  • Nortel Networks 8010co - page 7

    7 Installing th e Breaker Interface P anel f or the Ether n et Routing Sw itch 8010c o Chassis Contents Preface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 Bef ore you begin . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 ...

  • Nortel Networks 8010co - page 8

    8 Contents 312755-G Re v 00 Mounting h ardware . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35 DC input elec trical requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35 Installing the breaker interf ace panel . . . . . . . . . . . . . . . . . . . . . . . . . . ...

  • Nortel Networks 8010co - page 9

    Contents 9 Installing th e Breaker Interface P anel f or the Ether n et Routing Sw itch 8010c o Chassis Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81 ...

  • Nortel Networks 8010co - page 10

    10 Contents 312755-G Re v 00 ...

  • Nortel Networks 8010co - page 11

    11 Installing th e Breaker Interface P anel f or the Ether n et Routing Sw itch 8010c o Chassis Figures Figure 1 Breaker interface panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 Figure 2 F ront panel compon ents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 Figure 3 Shelf circ ...

  • Nortel Networks 8010co - page 12

    12 Figures 312755-G Re v 00 Figure 30 La beling cables for the BIP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47 Figure 31 Ra ck grounding strip e xample . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48 Figure 32 Att aching power supply ca ble leads to the BIP . . . . . . . . . . . . . . . . . . . . ...

  • Nortel Networks 8010co - page 13

    13 Installing th e Breaker Interface P anel f or the Ether n et Routing Sw itch 8010c o Chassis Ta b l e s T able 1 Alar m module display LEDs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 T able 2 DC power requirem ents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35 T able 3 Single chassis ...

  • Nortel Networks 8010co - page 14

    14 Tables 312755-G Re v 00 ...

  • Nortel Networks 8010co - page 15

    15 Installing the Breaker Interface Panel for th e Ethernet Routing Switch 8010co Chassis Preface The breaker interf ace panel (BIP) provid es po wer distribution and alarm status indications for one or two 8010co cha ssis in an equipment rack. The status indications can be link ed to ot her BIPs to provide total sy stem status to the cent ral offi ...

  • Nortel Networks 8010co - page 16

    16 Preface 312755-G Rev 00 T ext con ventions This guide uses the follo wing te xt con v entions: How to get Help This section explains ho w to get help for Nortel products and services. Getting Help from the Nortel W eb site The best way to get techni cal support for Nortel products is from the Nortel T echnical Support W eb site: http://www .nort ...

  • Nortel Networks 8010co - page 17

    Preface 17 Installing t he Breaker Interf ace Panel for the Ethern et Routing Switch 8010co Chassis • sign up for automatic notification of ne w software and documentation for Nortel equipment • open and manage technical support cases Getting Help over the phone fr om a Nortel Solutions Center If you don’ t f ind the information you require o ...

  • Nortel Networks 8010co - page 18

    18 Preface 312755-G Rev 00 ...

  • Nortel Networks 8010co - page 19

    19 Installing the Breaker Interface Panel for th e Ethernet Routing Switch 8010co Chassis Chapter 1 Overview This chapter provides an o vervie w of t h e BIP and cov ers the follo wing topics: • Physical description • “ Accessing the alarm module” on page 30 • “Config uration example” on page 32 Ph ysical description The BIP provides ...

  • Nortel Networks 8010co - page 20

    20 Chapter 1 Overview 312755-G Rev 00 Fr ont panel Figure 2 sho ws the BIP front panel components. Figure 2 F ront panel components Shelf circuit breaker s (upper and lo wer shelves) T wo groups of three circuit break ers pro v ide input po wer to the po wer supplies for the upper and lo wer shelf 8010 co chassis ( Figure 3 on page 21 ): • The fi ...

  • Nortel Networks 8010co - page 21

    Chapter 1 Ove rview 21 Installing t he Breaker Interf ace Panel for the Ethern et Routing Switch 8010co Chassis Figure 3 Shelf circuit brea ker s 10372EA 1 1 = Upper shelf LEDs 2 = Lower shelf LEDs Front of rack Upper Shelf 123 123 Lower Shelf 2 Upper shelf power supplies PS 1 + DC – DC PS 2 + DC – DC PS 3 + DC – DC Lower shelf power supplies ...

  • Nortel Networks 8010co - page 22

    22 Chapter 1 Overview 312755-G Rev 00 Alarm module display panel The alarm module display panel ( Figure 4 ), located on the BIP front panel, provides visual status indications for one or tw o 8010co chassis in a single rack. Figure 4 Alar m module display panel See Ta b l e 1 for a description of th e LEDs. T able 1 Alar m modu le display LEDs Ite ...

  • Nortel Networks 8010co - page 23

    Chapter 1 Ove rview 23 Installing t he Breaker Interf ace Panel for the Ethern et Routing Switch 8010co Chassis The alarm module can also be linked to other BIPs, and can provide v isual and audible alarms to aisle alarms and to the central of f ice (see “Central of fice alarms” on page 26 ). Alarm support for the BIP is provided by the 8691SF ...

  • Nortel Networks 8010co - page 24

    24 Chapter 1 Overview 312755-G Rev 00 Front panel lo c king scre ws The front panel locking scre ws allo w yo u to open the front panel to access the alarm module. The alarm modu le contains jumpers that you use to conf igure your system alarm parameters. For information about configuring yo ur system alarm parameters, see “ Accessing the alarm m ...

  • Nortel Networks 8010co - page 25

    Chapter 1 Ove rview 25 Installing t he Breaker Interf ace Panel for the Ethern et Routing Switch 8010co Chassis Figure 6 sho ws the location of the shelf alar m connectors on the BIP and on two 8010co chassis (upper and lo wer shelves). Figure 6 Shelf alar m conn ections (uppe r and lower shelv es) 1 = J1 (BIP upper shelf alarm connector) 2 = J2 (B ...

  • Nortel Networks 8010co - page 26

    26 Chapter 1 Overview 312755-G Rev 00 Central office alarms The central of f ice alarm connectors allo w you to aggre gate alarms from multiple BIPs and route them to an aisle alarm and to the central off ice. Figure 7 sho ws three BIPs configured to aggregate alarms from three racks. Y ou can configure up to ten BIPs in a series configuration to a ...

  • Nortel Networks 8010co - page 27

    Chapter 1 Ove rview 27 Installing t he Breaker Interf ace Panel for the Ethern et Routing Switch 8010co Chassis This type of configuration allows you to independ en tly monitor and control the external audible and visual alarm status in dications of the BIP at the central off ice. Figure 8 Configuring standalone BIPs to report alar m status P o wer ...

  • Nortel Networks 8010co - page 28

    28 Chapter 1 Overview 312755-G Rev 00 Figure 9 P o wer term inal bloc k Figure 10 on page 29 shows an e xample of the BIP po wer terminal block cabling including ground connections for tw o 8010co chassis and installed po wer supplies. As shown in this example, both upper an d lower chassis are each fully configured with three po wer supplies (one ...

  • Nortel Networks 8010co - page 29

    Chapter 1 Ove rview 29 Installing t he Breaker Interf ace Panel for the Ethern et Routing Switch 8010co Chassis Figure 10 P ower and gro unding e xample 32 PS (+) Lower Shelf PS (+) Upper Shelf PS (-) Lower Shelf PS (-) Upper Shelf A/B Input Feed Returns – 48 VDC A/B Input Feeds 1321 321321 A 2 A 1 B 1 B 2 Power terminal block (BIP) Return Second ...

  • Nortel Networks 8010co - page 30

    30 Chapter 1 Overview 312755-G Rev 00 Accessing the alarm module The alarm module contains jumpers that you can configure to allo w the BIP to monitor the shelf alarm cables for a single or dual chassis installation. The BIP ships from the factory with default jumper conf igurations set for a single chassis in the lo wer shelf of the rack. If you i ...

  • Nortel Networks 8010co - page 31

    Chapter 1 Ove rview 31 Installing t he Breaker Interf ace Panel for the Ethern et Routing Switch 8010co Chassis 2 Gently lo wer the front panel to ex pose the alarm module ( Figure 12 ). Figure 12 Accessing the alarm module Figure 13 shows a close-up vie w of the alar m module with jumpers J8 and J9 configured to monitor the shelf alarm cabl e for ...

  • Nortel Networks 8010co - page 32

    32 Chapter 1 Overview 312755-G Rev 00 Configuration e xample Figure 14 shows a typical conf iguration u sing the optional breaker interface panel. Figure 14 8010co chassis configuration with BIP option 10420EB 1 = Breaker interf ace panel 2 = 8010co Chassis (upper shelf position) 3 = 8010co Chassis (lower shelf position) 2 1 3 ...

  • Nortel Networks 8010co - page 33

    33 Installing the Breaker Interface Panel for th e Ethernet Routing Switch 8010co Chassis Chapter 2 Installation This chapter describes how to install th e breaker interface panel and co vers the follo wing topics: • “Preparing to install the breaker interface panel ” ne xt • “Installing the breaker interface panel” on page 36 • “V ...

  • Nortel Networks 8010co - page 34

    34 Chapter 2 In stallation 312755-G Rev 00 Shipment contents Inspect all items for shipping d amage. If yo u detect any damage, do not install the BIP . Call the Nortel T e chnical Solutions Center in your area (see “Ho w to get Help” on page 16 ). Y our BIP shipment contains the follo wing items ( Figu re 15 ): Figure 15 Contents of the BIP sh ...

  • Nortel Networks 8010co - page 35

    Chapter 2 Inst allation 35 Installing t he Breaker Interf ace Panel for the Ethern et Routing Switch 8010co Chassis Additional equipment T o install the BIP , you might need items that are not part of the BIP installation kit. Before installing the BIP hardw are, ensure that you ob tain all the cables, tools, and other equipment th at you need. F o ...

  • Nortel Networks 8010co - page 36

    36 Chapter 2 In stallation 312755-G Rev 00 Installing the breaker interface panel This section cov ers the follo wing topics: • “Installing the hardware ” next • “Connect ing cables to the chass is po wer s upplies” on page 38 • “Routing po wer supply cables to the BIP” on page 47 • “Connecting the grou nd cables to the r ack ...

  • Nortel Networks 8010co - page 37

    Chapter 2 Inst allation 37 Installing t he Breaker Interf ace Panel for the Ethern et Routing Switch 8010co Chassis T o install the BIP: 1 Remov e the plastic back cov er from the BIP terminal block ( Figure 16 ). Figure 16 Removing t he plastic bac k cov er f rom the BIP 2 Position the BIP in the uppermost position in the rack and align the holes ...

  • Nortel Networks 8010co - page 38

    38 Chapter 2 In stallation 312755-G Rev 00 Connecting cables to the c hassis po wer supplies This section describes how to connect th e BIP po wer cables to the 8010co chassis 8004DC po wer supplies. These procedur es assume that all required po wer supplies were pre viously installed du ring the 8010co chassis installation. Before begi nning the p ...

  • Nortel Networks 8010co - page 39

    Chapter 2 Inst allation 39 Installing t he Breaker Interf ace Panel for the Ethern et Routing Switch 8010co Chassis T o connect cables to the chassis po wer supplies: 1 Remov e the 8010co chassis bottom bezels (if requi red). a Using a Phillips scre wdri ver , loosen the 2 captiv e scre ws securing the bezel to the chassis ( Figure 18 ). b Pull the ...

  • Nortel Networks 8010co - page 40

    40 Chapter 2 In stallation 312755-G Rev 00 2 Locate the po wer supplies ( Figure 19 ). W ith the bezel remo ved, you can see the power supplies. The chassis can contain up to three power supplies. (Power supplies reside in bay 1, bay 2, and bay 3, vie wed left to righ t from the front of the chassis.) Figure 19 Location of po wer su pplies Fail Pas ...

  • Nortel Networks 8010co - page 41

    Chapter 2 Inst allation 41 Installing t he Breaker Interf ace Panel for the Ethern et Routing Switch 8010co Chassis 3 Loosen the 2 retaining scre ws on the po wer supply located in bay 1 in the lo wer chassis ( Figure 20 ). Figure 20 Loosening the po wer sup ply retaining scre ws 4 Lift the e xtractor le ver to disconnect the po wer suppl y from th ...

  • Nortel Networks 8010co - page 42

    42 Chapter 2 In stallation 312755-G Rev 00 5 Remov e the Phillips scre w securing the plastic safety co v er to the power supply , and then remov e the cov er ( Figure 22 ). Sa ve the Phillips scre w and the co v er for replacement later . Figure 22 Removing t he plastic saf et y cov er from th e pow er supply 6 Note the position of the ground stud ...

  • Nortel Networks 8010co - page 43

    Chapter 2 Inst allation 43 Installing t he Breaker Interf ace Panel for the Ethern et Routing Switch 8010co Chassis 7 Locate the follo wing items in the shipping container ( Figure 24 ). • 125-inch po wer cables—for po wer supplies located in the lo wer chassis • 90-inch po wer cables—for power suppl ies located in the upper chassis • 90- ...

  • Nortel Networks 8010co - page 44

    44 Chapter 2 In stallation 312755-G Rev 00 9 Attach the lug end of a 125-inch po wer supply cabl e to the positi ve terminal on the power supply ( Figure 26 ). Use a 7/16-inch hex wrench to fasten the hardware in the correct order . Figure 26 Attaching the positiv e lead +DC 4 1 = T wo-hole crimp lug 2 = Lock w asher (x 2) 3 = Hex n ut (x 2) 4 = P ...

  • Nortel Networks 8010co - page 45

    Chapter 2 Inst allation 45 Installing t he Breaker Interf ace Panel for the Ethern et Routing Switch 8010co Chassis 10 Attach the lug end of a 125-inch po wer supply cable to the ne gati v e terminal on the power supply ( Figure 27 ). Use a 7/16-inch hex wrench to fasten the hardware in the correct order . Figure 27 Attaching the negativ e le ad 11 ...

  • Nortel Networks 8010co - page 46

    46 Chapter 2 In stallation 312755-G Rev 00 12 Secure the po wer supply in bay 1 of the lo wer chassis ( Figure 29 ). a Use the power supply handle to push the po wer supply fi rmly into bay 1. b Push the extractor le v er do wn to lock the po wer supply i n place. c T ighten the tw o po wer supply retaining scre ws. Figure 29 Replacing the po we r ...

  • Nortel Networks 8010co - page 47

    Chapter 2 Inst allation 47 Installing t he Breaker Interf ace Panel for the Ethern et Routing Switch 8010co Chassis Routing power suppl y cab les to the BIP After you connect all cables to the cha ssis po wer supplies, you must route the po wer supply cable leads from each chassis to the BIP . If you installed an upper and lo wer shelf chassis, and ...

  • Nortel Networks 8010co - page 48

    48 Chapter 2 In stallation 312755-G Rev 00 5 Route the remaining (black ) power supply cables from the back of the lo wer and upper shelf chassis to the back pane l of the BIP , loosely fastening them with tie-wraps along the path. 6 Loosely support the po wer supply cables with tie-wraps abov e the BIP po wer terminal block. 7 Proceed to, “Conne ...

  • Nortel Networks 8010co - page 49

    Chapter 2 Inst allation 49 Installing t he Breaker Interf ace Panel for the Ethern et Routing Switch 8010co Chassis Connecting the power suppl y cabl es to the BIP T o connect the po wer sup p ly cables to the BIP: 1 Locate one of the po wer supply cables. 2 Match the labeled tag on the po wer supp ly cable with the correct location on the po wer t ...

  • Nortel Networks 8010co - page 50

    50 Chapter 2 In stallation 312755-G Rev 00 4 Repeat steps 1 through 3 for each remaining po wer supply in your confi guration ( Figure 33 ). Figure 33 Upper and lo wer shelf power cabl es connected to the BIP 5 Locate the BIP ground cable (see Figure 30 on page 47 ). 10394FA 32 PS (+) Lower Shelf PS (+) Upper Shelf PS (-) Lower Shelf PS (-) Upper S ...

  • Nortel Networks 8010co - page 51

    Chapter 2 Inst allation 51 Installing t he Breaker Interf ace Panel for the Ethern et Routing Switch 8010co Chassis 6 Attach one end of the BIP ground cable to the po wer terminal block ( Figure 34 ). a Loosen the po wer terminal block scre w ju st enough to inser t the ground cable lead (item 1 in Figure 34 ). b Insert the lead and tighten the scr ...

  • Nortel Networks 8010co - page 52

    52 Chapter 2 In stallation 312755-G Rev 00 Connecting DC input power f eeds to the BIP Nortel does not supply the cables for c onn ecting the breaker int erface panel to the DC input po wer source. Y ou mu st select ca bles that comply with the electrical code of the country wh ere you intend t o use the DC-DC po wer supply . Y ou can connect up to ...

  • Nortel Networks 8010co - page 53

    Chapter 2 Inst allation 53 Installing t he Breaker Interf ace Panel for the Ethern et Routing Switch 8010co Chassis Figure 35 A and B f eed e xample Ta b l e 3 lists input power options for sing le and dual chassis installations. T able 3 Single chassis and dual chassis input options Single chassis input * * F or a single chassis installation, alwa ...

  • Nortel Networks 8010co - page 54

    54 Chapter 2 In stallation 312755-G Rev 00 T o connect the DC input feeds to the BIP: 1 Locate the DC po wer sour ce for the DC input feed. 2 Determine the po wer requirements for your co nf iguration (see Figure 35 on page 53 ). 3 Locate the A and B - 48 VDC in put feeds ( Figure 36 ). The -48 VDC input feed cables should be tagged with source lab ...

  • Nortel Networks 8010co - page 55

    Chapter 2 Inst allation 55 Installing t he Breaker Interf ace Panel for the Ethern et Routing Switch 8010co Chassis 4 Connect the -48 VDC input feeds according to your conf iguration requirements. a Match the tagged -48 VDC input feed cable l ead with th e correct po we r terminal block on the back o f the BIP ( Figure 37 ). a Loosen the po wer ter ...

  • Nortel Networks 8010co - page 56

    56 Chapter 2 In stallation 312755-G Rev 00 5 Connect the remaining -4 8 VDC input feeds and returns as requi red ( Figure 38 ). Figure 38 Connecting the A and B -48 VDC input f eeds to the BIP (2 of 2) Note: Figure 38 sho ws the a ttachment of t wo “ A” feeds and two “B” feeds to the BIP . Note that there is a primary and a secondary A feed ...

  • Nortel Networks 8010co - page 57

    Chapter 2 Inst allation 57 Installing t he Breaker Interf ace Panel for the Ethern et Routing Switch 8010co Chassis 6 Connect the A/B input feed returns. a Locate the A/B Input Feed Returns se ction of the po wer terminal block. b Loosen one of the four a v ailable A/B input feed return connection scre ws just enough to insert the cable lead (item ...

  • Nortel Networks 8010co - page 58

    58 Chapter 2 In stallation 312755-G Rev 00 7 Connect the remaining -48 VDC input ret urns as required ( Figure 40 ). Figure 40 shows the BIP with all po we r cables and returns installed. Figure 40 Connecting the A/ B input f eed r eturns (2 of 2) 8 Go to the ne xt section, “Replacing cov ers” on page 59 . Note: Be sure to properly support the ...

  • Nortel Networks 8010co - page 59

    Chapter 2 Inst allation 59 Installing t he Breaker Interf ace Panel for the Ethern et Routing Switch 8010co Chassis Replacing co ver s After you complete all of th e cabling requirements as described in the pre viou s sections, you must replace the plastic ba ck cov er on the BIP and the 8010co chassis bezel(s) that were remove d earlier in these p ...

  • Nortel Networks 8010co - page 60

    60 Chapter 2 In stallation 312755-G Rev 00 2 Replace the 8010co chassis bezel. a Set the notch (on both ends of the 312096-A bezel) into the tabs on the chassis ( Figure 42 ). b Lift the top of the bezel up, and then align the capti v e scre ws with the holes in the chassis. c Using a Phillips scre wdri ver , tighten the 2 captiv e scre ws to secur ...

  • Nortel Networks 8010co - page 61

    Chapter 2 Inst allation 61 Installing t he Breaker Interf ace Panel for the Ethern et Routing Switch 8010co Chassis Installing shelf alarm cables 1 T o install the shelf alarm cable for a single chassis in the lo wer shelf: a Locate the shelf alarm cables in the shipping container . b Connect one end of the shelf alarm cable to the J2 connec tor on ...

  • Nortel Networks 8010co - page 62

    62 Chapter 2 In stallation 312755-G Rev 00 2 T o install the shelf alarm cable for a second chassis in the upper shelf: a Configure the jumpers on the alarm modu le to support a se cond chassis in the upper shelf as described in “ Accessing the alarm module” on page 30 . b Connect one end of the shelf alarm cable to the J1 connec tor on the bac ...

  • Nortel Networks 8010co - page 63

    Chapter 2 Inst allation 63 Installing t he Breaker Interf ace Panel for the Ethern et Routing Switch 8010co Chassis Initial power -up T o power up the 8010co chassis: 1 Set the six circuit breakers on the BIP front panel to the of f position (O = Of f). 2 Set the switches for all po wer supplies in the upper and lo wer chassis to the off position ( ...

  • Nortel Networks 8010co - page 64

    64 Chapter 2 In stallation 312755-G Rev 00 4 V erify the following LEDs on the 8010co chassis: — The (green) po wer supply LEDs fo r each po wer supply in bot h the upper and lo wer chassis are on. (If any of the po wer suppl y LEDs are not on, replace the po wer supply .) — The chassis f ans are po wering up. If any of the pre vious steps indi ...

  • Nortel Networks 8010co - page 65

    Chapter 2 Inst allation 65 Installing t he Breaker Interf ace Panel for the Ethern et Routing Switch 8010co Chassis 4 Continue with the insta llation of the 8010co cha ssis as described in the appropriate product chassis installation manual. Note: When you po wer off the 8010co chassis, wait at least 30 seconds before turning the po wer su pplies b ...

  • Nortel Networks 8010co - page 66

    66 Chapter 2 In stallation 312755-G Rev 00 ...

  • Nortel Networks 8010co - page 67

    67 Installing the Breaker Interface Panel for th e Ethernet Routing Switch 8010co Chassis Chapter 3 Pr ob lem solving This chapter describes ho w to isolate an d diagnose p roblems with your break er interface panel and associated 8010co chassis. This chapter cov ers the follo wing topics: • “Interpreting the LEDs ” (next) • “Diagnosing a ...

  • Nortel Networks 8010co - page 68

    68 Chapter 3 Problem solving 312755-G Rev 00 Interpreting the LEDs All BIP LEDs and indi cators are located on the front panel ( Figure 44 ). Figure 44 BIP LEDs and indicators Ta b l e 4 describes the BIP LEDs and indicators. T able 4 BIP LEDs and indicators Item Label/I con T ype Color/State Descript ion 1 Upper Sh elf/ Lower Shelf LED Red/On stea ...

  • Nortel Networks 8010co - page 69

    Chapter 3 Problem solving 69 Installing t he Breaker Interf ace Panel for the Ethern et Routing Switch 8010co Chassis If you need more help, go to t he next section , “Diagnosing and correcting the problem” on page 70 . 4 POWER Indicator White/On ste ady P ower indicator—The external DC p ower is av ailable to the BIP . 5 CRITICAL Indicator R ...

  • Nortel Networks 8010co - page 70

    70 Chapter 3 Problem solving 312755-G Rev 00 Diagnosing and correcting the pr ob lem Before you perform the problem-sol ving steps in this section, compl ete the follo wing steps: 1 Set the switches for all po wer supplies in the upper and lo wer chassis to the off position ( O = Of f). 2 Set the six circuit breakers on the BIP front panel to the o ...

  • Nortel Networks 8010co - page 71

    Chapter 3 Problem solving 71 Installing t he Breaker Interf ace Panel for the Ethern et Routing Switch 8010co Chassis Corrective actions T o resolve problems with the BIP or th e 8010co chassis and components, follo w the correcti v e action s suggested in Ta b l e 5 . T able 5 Corrective actions Symptom Probable cause Corrective action The (red) s ...

  • Nortel Networks 8010co - page 72

    72 Chapter 3 Problem solving 312755-G Rev 00 The (red) CRITICAL indicator is on steady . F ailo v er from Master CPU to the second (redun dant) CPU . This action is preceded by the CRITICAL indicator blinking two times and then tur ning off after the redundant CPU becomes operational. After the Redundant CPU becomes op erational, the (red) MAJOR in ...

  • Nortel Networks 8010co - page 73

    73 Installing the Breaker Interface Panel for th e Ethernet Routing Switch 8010co Chassis Appendix A T echnical specifications This appendix lists the technical specif ications for the breaker interface panel. This appendix cov ers the fol lo wing topics: • “En vironmental ” (next) • “Electrical” on page 74 • “Physical dimensions ? ...

  • Nortel Networks 8010co - page 74

    74 Appendix A Technical specifications 312755-G Rev 00 Electrical Ph ysical dimensions Electr oma gnetic emissions Safety a gency cer tification P arameter Specifica tions Input V oltage (Nominal) -48 VDC Input Current Feed Rating 60 A per DC input feed Output Current Feed Rating 30 A per DC output feed P arameter Specifica tions Height 12.6 cm (4. ...

  • Nortel Networks 8010co - page 75

    75 Installing the Breaker Interface Panel for th e Ethernet Routing Switch 8010co Chassis Appendix B BIP e xternal cable pin assignments This appendix describes the br eaker interface panel connectors. This appendix cov ers the fol lo wing topics: • “Shelf alarm connectors (J1 and J2) , ” next • “Off ice alarm connectors (J3 and J4)” on ...

  • Nortel Networks 8010co - page 76

    76 Appendix B BIP external cable pin assignments 312755-G Rev 00 Figure 46 J1 and J2 shelf alar m co nnector pin outs Ta b l e 6 lists the pin assignments for the J1 and J2 shelf alarm connectors. T able 6 J1 and J2 shelf alarm connector pin assignment s Pin Signal Description 1 L+ABS Alarm batter y supply retur n. 2 VCRIT Visual critical ala rm. 3 ...

  • Nortel Networks 8010co - page 77

    Appendix B BIP extern al cable pin assign ments 77 Installing t he Breaker Interf ace Panel for the Ethern et Routing Switch 8010co Chassis Office alarm connectors (J3 and J4) The BIP of fice alarm connectors (J3 and J4) use high-density , 26 -pin D-sub connectors ( Figure 47 ). Figure 47 J3 and J4 hig h-density 26-pin D-sub connecto r Figure 48 sh ...

  • Nortel Networks 8010co - page 78

    78 Appendix B BIP external cable pin assignments 312755-G Rev 00 Ta b l e 7 lists the pin assignments for the J3 and J4 off ice alarm connectors. T able 7 J3 and J4 office alarm connector pin assignments Pin Signal Description 1 TT A V oice communications from telephone jacks. 2 TRB V oice communications from teleph one jacks. 3 D2A Data communicat ...

  • Nortel Networks 8010co - page 79

    Appendix B BIP extern al cable pin assign ments 79 Installing t he Breaker Interf ace Panel for the Ethern et Routing Switch 8010co Chassis Standalone office alarm connector (J5) The standalon e of f ice alarm connectors (J5) uses a hig h-density , 26-pin D-sub connector ( Figure 49 ). Figure 49 J5 high-den sity 26-pin D-su b connecto r Figure 50 s ...

  • Nortel Networks 8010co - page 80

    80 Appendix B BIP external cable pin assignments 312755-G Rev 00 Ta b l e 8 lists the pin assignments for the J5 standalone of f ice alarm connector . T able 8 J5 standalone office alarm connector pin assignmen ts Pin Signal Description 1 Critical a larm—Vi sual (NC) Visual alar m contact 2 Major alar m—Visual (NC) Visual alar m contact 3 Minor ...

  • Nortel Networks 8010co - page 81

    Installing the Breaker Interface Panel for th e Ethernet Routing Switch 8010co Chassis 81 Inde x Numbers 8691omSF central processing unit (CPU) 23 8691SF central processing unit (CPU) 23 A alarm module alarm conditions 23 configuring jumpers 30 display panel 22 LEDs 22 alarms aisle 26 central of fice 26 B back panel 24 breaker interf ace panel (BIP ...

  • Nortel Networks 8010co - page 82

    82 Index 312755-G Rev 00 alarm module 22 BIP front panel 68 description 68 location 68 P pin assignments, cables 75 power DC input requirements 35 initial power -up 63 po wering of f t he system 64 power supplies cable routing 47 connecting cables 38 , 49 power terminal block 28 problem solving correcti ve actions 71 interpreting LED s 67 R require ...

Fabbricante Nortel Networks Categoria Switch

I documenti che otteniamo dal fabbricante del dispositivoNortel Networks 8010co possono essere suddivisi in diversi gruppi. Questi sono tra gli altri:
- disegni tecnici Nortel Networks
- manuali per l’uso 8010co
- schede prodotto Nortel Networks
- opuscoli
- o etichette energetiche Nortel Networks 8010co
Tutti sono importanti, ma le informazioni più importanti dal punto di vista di utilizzo del dispositivo possono essere trovate nel manuale per l’uso Nortel Networks 8010co.

Un gruppo di documenti denominato manuali per l’uso, è anche suddiviso in tipi più specifici, come: Manuali di installazione Nortel Networks 8010co, manuali di manutenzione, brevi manuali o manuali utente Nortel Networks 8010co. A seconda delle esigenze, si dovrebbe cercare il documento necessario. Nel nostro sito web, puoi visualizzare il manuale più popolare per l'uso del prodotto Nortel Networks 8010co.

Manuali per l’uso simili

Manuale completo del dispositivo Nortel Networks 8010co, come deve essere?
Il manuale per l’uso, denominato anche istruzioni per l’uso, o semplicemente il manuale è un documento tecnico progettato per aiutare ad utilizzare Nortel Networks 8010co dagli utenti. I manuali sono di solito scritti da uno scrittore tecnico, ma in un linguaggio accessibile a tutti gli utenti Nortel Networks 8010co.

Il manuale per l’uso completo Nortel Networks, dovrebbe includere vari elementi di base. Alcuni di loro sono meno importanti, come ad esempio: copertina / pagina del titolo o pagina di autore. Tuttavia, la parte rimanente, dovrebbe fornire informazioni importanti dal punto di vista dell'utente.

1. Introduzione e la guida su come utilizzare il manuale Nortel Networks 8010co - All'inizio di ogni manuale, dovremmo trovare indizi su come utilizzare il documento. Dovrebbe contenere informazioni sulla posizione dell’indice Nortel Networks 8010co, FAQ o i problemi più comuni : i punti che sono più spesso cercati dagli utenti di ogni manuale
2. Indice - elenco di tutti i suggerimenti per Nortel Networks 8010co che possono essere trovati nel documento corrente
3. Suggerimenti su come utilizzare le funzioni di base del dispositivo Nortel Networks 8010co - che ci dovrebbe aiutare nei primi passi durante l'uso Nortel Networks 8010co
4. Troubleshooting - sequenza sistematica delle attività che vi aiuterà a diagnosticare e, successivamente, risolvere i problemi più importanti del Nortel Networks 8010co
5. FAQ - domande più frequenti
6. Dettagli di contatto Informazioni su dove cercare il contatto con il fabbricante / servizio Nortel Networks 8010co in un dato paese, se il problema non può essere risolto da noi stessi.

Hai una domanda su Nortel Networks 8010co?

Utilizza il modulo sottostante

Se non hai risolto il problema con Nortel Networks 8010co con l'aiuto del manuale che hai trovato, fai una domanda utilizzando il modulo sottostante. Se un utente ha avuto un problema simile con Nortel Networks 8010co è probabile che voglia condividere il modo di risolverlo.

Riscrivi il testo dall’immagine

Commenti (0)