    TECHNICAL GUIDE SPLIT -SYSTEM HEA T PUMPS 14.5 SEER – R-410A MODELS: YHJF18 THRU 60 (1.5 THRU 5 NOMINAL TONS, 1 PHASE) Due to continuous prod uct improvemen t, specifications are subject to chan ge without notice. Vi si t us on the web at ww w .york.com Additional rating informa tion can be found at www .ahridirectory.org W ARRANTY S tandard 5-ye ...

  • York YHJF18 THRU 60 - page 2

    510667-YTG-B-0509 2 Johnson Controls Unitary Products All dimensions are in inche s. They are su bject to change with- out notice. Certified dimensions will be provi ded upon request. Physical and Electrica l Data MODEL YHJF18 S41S1 YHJF24 S41S1 YHJF30 S41S1 YHJF36 S41S1 YHJF42 S41S1 YHJF48 S41S1 YHJF60 S41S1 Unit Supply V oltage 208-230V , 1 ? ...

  • York YHJF18 THRU 60 - page 3

    510667-YTG-B-0509 Johnson Controls Unitary Pro ducts 3 PROCEDURES: 1. Unit factory charge listed on the u nit nameplate includes re friger ant for the condenser, the smallest evaporator and 15 feet of interconnecting line tub ing. 2. V erify the TXV and additional charge required for specific evaporator coil in the system u sing the above table. 3. ...

  • York YHJF18 THRU 60 - page 4

    510667-YTG-B-0509 4 Johnson Controls Unitary Products — = Not applicable. COOLING CAP ACITY - With Air Handler Coils UNIT MODEL AIR HANDLER COIL MODEL 1 ST AGE COOLING MODEL W RA TED CFM NET MBH SEER EER TOT AL SENS. 14.5 SEER HP WITH MV - V ARIABLE SPEED YHJF18S41S1 MV12B 17 FC/MC35B – 600 18.0 13.0 15.00 12.50 MV12B 17 FC/MC43B – 600 18.0 1 ...

  • York YHJF18 THRU 60 - page 5

    510667-YTG-B-0509 Johnson Controls Unitary Pro ducts 5 COOLING CAP ACITY - With High Efficiency Motor Furnaces UNIT MODEL FURNACE MODEL COIL MODEL 1 WS T A G E COOLING RA TED CFM Net MBH SEER EER TOT AL SENS. 14.5 SEER HP WITH V ARIABLE SPEED FURNACES 2 YHJF18S41S1 T*(8,L)X*A12 FC/MC/PC32A 14 – 590 18.0 13.0 15.00 12.50 Y*(8,L)C*A12 FC/MC/PC32A 1 ...

  • York YHJF18 THRU 60 - page 6

    510667-YTG-B-0509 6 Johnson Controls Unitary Products YHJF36S41S1 T*(8,L)X*A12 FC/MC/PC37A 14 – 1290 35.8 27.4 14.50 12.00 T*(8,L)X*B12 FC/MC/PC43B 17 – 1300 35.8 27.4 14.50 12.00 T*(8,L)X*C16 FC/MC/PC43C 21 – 1 175 35.4 26.4 15.00 12.50 T*(8,L)X*C20 FC/MC/PC43C 21 – 1250 36.0 27.4 15.00 12.50 T*9X*B12 FC/MC/PC43B 17 – 1270 35.8 27.4 14.5 ...

  • York YHJF18 THRU 60 - page 7

    510667-YTG-B-0509 Johnson Controls Unitary Pro ducts 7 CP equals MBH output divided by (total KW input x 3.412). HSPF (Heating Seasonal Performance Factor) is the total heat ing output durin g a normal annual usage period for hea ting divided by th e total electric power input during the same period. — = Not Applicable. HEA TING PERFORMANCE - W ...

  • York YHJF18 THRU 60 - page 8

    510667-YTG-B-0509 8 Johnson Controls Unitary Products HEA TING CAP ACIT Y - With High Efficiency Motor Fu rnaces MODEL FURNACE MODEL COIL 1 MODEL ARI HEA TING 2 47  F1 7  FH S P F MBH COP KW MBH COP KW STD 14.5 SEER HP WITH V ARIABLE SPEED FUR NACES 3 YHJF18S41S1 T*(8,L)X*A12 FC/MC/PC32A 17. 9 3.84 1.37 10.8 2.54 1 .25 9.00 Y*(8,L)C*A12 F C/M ...

  • York YHJF18 THRU 60 - page 9

    510667-YTG-B-0509 Johnson Controls Unitary Pro ducts 9 CP equals MBH output divided by (total KW input x 3.412). HSPF (Heating Seasonal Performance Factor) is the total heat ing output durin g a normal annual usage period for hea ting divided by th e total electric power input during the same period. — = Not Applicable. YHJF36S41S1 T*(8,L)X*A12 F ...

  • York YHJF18 THRU 60 - page 10

    510667-YTG-B-0509 10 Johnson Controls Unitary Products CP equals MBH output divided by (total KW input x 3.412). HSPF (Heating Seasonal Performance Factor) is the total heat ing output during a normal annual usage period for heating divided by the total electric power input during the same period. — = Not Applicable. ACCESSORIES Refer to Price Ma ...

  • York YHJF18 THRU 60 - page 11

    510667-YTG-B-0509 Johnson Controls Unitary Pro ducts 11 SOUND LEVEL - TYPICAL OCT A VE BAND SPE CTRUM (without tone adjustment) * Rated in accordance with ARI 270-200 8 S tandards. TYPICAL INST ALLA TION TYPICAL FIELD WIRING Size T est Condition 63 125 250 500 1000 2000 4000 8000 dBA SQI RSS Sound Power Calibration 1091 402 82.8 85.4 85.9 85.3 88.1 ...

  • York YHJF18 THRU 60 - page 12

    510667-YTG-B-0509 12 Johnson Controls Unitary Products Multipliers for determining the perfo rman ce with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (between 73- 87 F), sensible capacity incr eases by 1060 BTUH per 1000 CFM per degree above the listed temperature and decr eases by 1060 BTUH per 1000 CFM per ...

  • York YHJF18 THRU 60 - page 13

    510667-YTG-B-0509 Johnson Controls Unitary Pro ducts 13 Multipliers for determining the perform ance with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (between 73-87 F), se nsible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed temperature and decrease s by 1060 BTUH per 1000 CFM per d ...

  • York YHJF18 THRU 60 - page 14

    510667-YTG-B-0509 14 Johnson Controls Unitary Products Multipliers for determining the perfo rman ce with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (between 73- 87 F), sensible capacity incr eases by 1060 BTUH per 1000 CFM per degree above the listed temperature and decr eases by 1060 BTUH per 1000 CFM per ...

  • York YHJF18 THRU 60 - page 15

    510667-YTG-B-0509 Johnson Controls Unitary Pro ducts 15 Multipliers for determining the perform ance with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (between 73-87 F), se nsible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed temperature and decrease s by 1060 BTUH per 1000 CFM per d ...

  • York YHJF18 THRU 60 - page 16

    510667-YTG-B-0509 16 Johnson Controls Unitary Products Multipliers for determining the perfo rman ce with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (between 73- 87 F), sensible capacity incr eases by 1060 BTUH per 1000 CFM per degree above the listed temperature and decr eases by 1060 BTUH per 1000 CFM per ...

  • York YHJF18 THRU 60 - page 17

    510667-YTG-B-0509 Johnson Controls Unitary Pro ducts 17 Multipliers for determining the perform ance with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (between 73-87 F), se nsible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed temperature and decrease s by 1060 BTUH per 1000 CFM per d ...

  • York YHJF18 THRU 60 - page 18

    510667-YTG-B-0509 18 Johnson Controls Unitary Products Multipliers for determining the perfo rman ce with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (between 73- 87 F), sensible capacity incr eases by 1060 BTUH per 1000 CFM per degree above the listed temperature and decr eases by 1060 BTUH per 1000 CFM per ...

  • York YHJF18 THRU 60 - page 19

    510667-YTG-B-0509 Johnson Controls Unitary Pro ducts 19 Multipliers for determining the perform ance with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (between 73-87 F), se nsible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed temperature and decrease s by 1060 BTUH per 1000 CFM per d ...

  • York YHJF18 THRU 60 - page 20

    510667-YTG-B-0509 20 Johnson Controls Unitary Products Multipliers for determining the perfo rman ce with other indoor sections. HEA TING PE RFORMANCE DA T A CONDENSING UNIT MO DEL NO YHJF18S41S1 EV APORA TOR COIL MODEL NO AHX30 AIR TEMP . ENTERING OUTDOOR UNIT AIR TEMP . ENTERING INDOOR COIL ID CFM 450 600 750 MBTUH KW C.O.P . MBTUH KW C.O.P . MBT ...

  • York YHJF18 THRU 60 - page 21

    510667-YTG-B-0509 Johnson Controls Unitary Pro ducts 21 Multipliers for determining the perform ance with other indoor sections. HEA TING PERFORMANCE DA T A CONDENSING UNIT MODEL NO YHJF24S41S1 EV APORA TOR COIL MODEL NO AHX30 AIR TEMP . ENTERING OUTDOOR UNIT AIR TEMP . ENTERING INDOOR COIL ID CFM 600 800 1000 MBTUH KW C.O.P . MBTUH KW C.O.P . MBTU ...

  • York YHJF18 THRU 60 - page 22

    510667-YTG-B-0509 22 Johnson Controls Unitary Products Multipliers for determining the perfo rman ce with other indoor sections. HEA TING PE RFORMANCE DA T A CONDENSING UNIT MO DEL NO YHJF30S41S1 EV APORA TOR COIL MODEL NO AHX36 AIR TEMP . ENTERING OUTDOOR UNIT AIR TEMP . ENTERING INDOOR COIL ID CFM 800 1000 1200 MBTUH KW C.O.P . MBTUH KW C.O.P . M ...

  • York YHJF18 THRU 60 - page 23

    510667-YTG-B-0509 Johnson Controls Unitary Pro ducts 23 Multipliers for determining the perform ance with other indoor sections. HEA TING PERFORMANCE DA T A CONDENSING UNIT MODEL NO YHJF36S41S1 EV APORA TOR COIL MODEL NO AHX36 AIR TEMP . ENTERING OUTDOOR UNIT AIR TEMP . ENTERING INDOOR COIL ID CFM 1000 1200 1400 MBTUH KW C.O.P . MBTUH KW C.O.P . MB ...

  • York YHJF18 THRU 60 - page 24

    510667-YTG-B-0509 24 Johnson Controls Unitary Products Multipliers for determining the perfo rman ce with other indoor sections. HEA TING PE RFORMANCE DA T A CONDENSING UNIT MO DEL NO YHJF42S41S1 EV APORA TOR COIL MODEL NO AHX60 AIR TEMP . ENTERING OUTDOOR UNIT AIR TEMP . ENTERING INDOOR COIL ID CFM 1200 1400 1600 MBTUH KW C.O.P . MBTUH KW C.O.P . ...

  • York YHJF18 THRU 60 - page 25

    510667-YTG-B-0509 Johnson Controls Unitary Pro ducts 25 Multipliers for determining the perform ance with other indoor sections. HEA TING PERFORMANCE DA T A CONDENSING UNIT MODEL NO YHJF48S41S1 EV APORA TOR COIL MODEL NO F6FP060 AIR TEMP . ENTERING OUTDOOR UNIT AIR TEMP . ENTERING INDOOR COIL ID CFM 1400 1600 1800 MBTUH KW C.O.P . MBTUH KW C.O.P . ...

  • York YHJF18 THRU 60 - page 26

    Subject to change without notice. Publishe d in U.S.A. 510667-YTG-B-0509 Copyright © 2009 by Johnson Controls, Inc. All ri ghts reserved. Supersedes: 510667-YTG-A-0409 Johnson Controls Unitary Product s 5005 Y ork Drive Norman, OK 73069 Multipliers for determining the perfo rman ce with other indoor sections. HEA TING PE RFORMANCE DA T A CONDENSIN ...

Fabbricante York Categoria Heat Pump

I documenti che otteniamo dal fabbricante del dispositivoYork YHJF18 THRU 60 possono essere suddivisi in diversi gruppi. Questi sono tra gli altri:
- disegni tecnici York
- manuali per l’uso YHJF18 THRU 60
- schede prodotto York
- opuscoli
- o etichette energetiche York YHJF18 THRU 60
Tutti sono importanti, ma le informazioni più importanti dal punto di vista di utilizzo del dispositivo possono essere trovate nel manuale per l’uso York YHJF18 THRU 60.

Un gruppo di documenti denominato manuali per l’uso, è anche suddiviso in tipi più specifici, come: Manuali di installazione York YHJF18 THRU 60, manuali di manutenzione, brevi manuali o manuali utente York YHJF18 THRU 60. A seconda delle esigenze, si dovrebbe cercare il documento necessario. Nel nostro sito web, puoi visualizzare il manuale più popolare per l'uso del prodotto York YHJF18 THRU 60.

Manuali per l’uso simili

Manuale completo del dispositivo York YHJF18 THRU 60, come deve essere?
Il manuale per l’uso, denominato anche istruzioni per l’uso, o semplicemente il manuale è un documento tecnico progettato per aiutare ad utilizzare York YHJF18 THRU 60 dagli utenti. I manuali sono di solito scritti da uno scrittore tecnico, ma in un linguaggio accessibile a tutti gli utenti York YHJF18 THRU 60.

Il manuale per l’uso completo York, dovrebbe includere vari elementi di base. Alcuni di loro sono meno importanti, come ad esempio: copertina / pagina del titolo o pagina di autore. Tuttavia, la parte rimanente, dovrebbe fornire informazioni importanti dal punto di vista dell'utente.

1. Introduzione e la guida su come utilizzare il manuale York YHJF18 THRU 60 - All'inizio di ogni manuale, dovremmo trovare indizi su come utilizzare il documento. Dovrebbe contenere informazioni sulla posizione dell’indice York YHJF18 THRU 60, FAQ o i problemi più comuni : i punti che sono più spesso cercati dagli utenti di ogni manuale
2. Indice - elenco di tutti i suggerimenti per York YHJF18 THRU 60 che possono essere trovati nel documento corrente
3. Suggerimenti su come utilizzare le funzioni di base del dispositivo York YHJF18 THRU 60 - che ci dovrebbe aiutare nei primi passi durante l'uso York YHJF18 THRU 60
4. Troubleshooting - sequenza sistematica delle attività che vi aiuterà a diagnosticare e, successivamente, risolvere i problemi più importanti del York YHJF18 THRU 60
5. FAQ - domande più frequenti
6. Dettagli di contatto Informazioni su dove cercare il contatto con il fabbricante / servizio York YHJF18 THRU 60 in un dato paese, se il problema non può essere risolto da noi stessi.

Hai una domanda su York YHJF18 THRU 60?

Utilizza il modulo sottostante

Se non hai risolto il problema con York YHJF18 THRU 60 con l'aiuto del manuale che hai trovato, fai una domanda utilizzando il modulo sottostante. Se un utente ha avuto un problema simile con York YHJF18 THRU 60 è probabile che voglia condividere il modo di risolverlo.

Riscrivi il testo dall’immagine

Commenti (0)