    FieldPoint ™ Operating Instructions FP-AI-110 and cFP-AI-110 Eight-Channel, 16-Bit Analog Input M odules These operating instructions descri be ho w to install and use the FP-AI-110 and cFP-AI-110 analog input modules (referred to inclusiv ely as the [c]FP-A I-110). F or information about configuring and accessing the [c]F P- AI-110 ov er a netwo ...

  • National Instruments FP-Al-110 - page 2

    FP-AI-110 and cFP-AI-110 2 ni.com T o install the FP- AI-110, refer to Figure 1 and complete the follow ing steps: 1. Slide the terminal base key to either position X (used for an y module) or position 1 (used for the FP- AI-110). 2. Align the FP- AI-110 alignmen t sl ots with the guide rails on the terminal base. 3. Press firmly to seat the FP- AI ...

  • National Instruments FP-Al-110 - page 3

    © National Instruments Corp. 3 FP-AI-110 and cFP-AI-110 (10 lb ⋅ in.) of torque. The nylon coating on the screws pre vents them from loosening. Figure 2. Installing the cFP-AI-110 Wiring the [c]FP-AI-110 The FP-TB- x terminal base ha s connections for each of the eight input channels and for an external power su pply to power field de vice s. Th ...

  • National Instruments FP-Al-110 - page 4

    FP-AI-110 and cFP-AI-110 4 ni.com is 2 A or less and the maximum current through any V SUP terminal is 1 A or less . Install a 2 A maximum, fast-acting fuse between t he external power supply and the V terminal on each channel. The wiring diagrams in this document sho w fuses where appropriate. T able 1 lists the terminal assign ments for the signa ...

  • National Instruments FP-Al-110 - page 5

    © National Instruments Corp. 5 FP-AI-110 and cFP-AI-110 T aking Measurements with the [c]FP-AI-110 The [c]FP- AI-110 has eight single- ended input cha nnels. All eight channels share a common ground referen ce that is isolated from other modules in the FieldPoint system. Figure 3 shows the analog input circuitry on one channel. Figure 3. FP- AI-11 ...

  • National Instruments FP-Al-110 - page 6

    FP-AI-110 and cFP-AI-110 6 ni.com Figure 5 sho ws how to connect a v oltage source with an extern al power supply to one channel of the [c]FP-AI-110. Figure 5. Voltage Source with Ex ternal Powe r Supply Measuring Current with the [c]FP-AI-110 The input ranges for current sources are 0 –20, 4 –20, and ± 20 mA. The module reads current flowing ...

  • National Instruments FP-Al-110 - page 7

    © National Instruments Corp. 7 FP-AI-110 and cFP-AI-110 Figure 6. Current Source without External Power Supply Figure 7 sho ws how to connect a cu rrent sour ce with an external power supply to one channel of the [c]FP-AI-110. Figure 7. Current Source with Ex ternal Power Supply Input Ranges T o prev ent inaccurate readings, c hoose an input range ...

  • National Instruments FP-Al-110 - page 8

    FP-AI-110 and cFP-AI-110 8 ni.com Overranging The [c]FP- AI-110 has an overranging feature that meas ures a little beyond the nominal values of each rang e. For example, the actual measurement limit of the ± 10 V range is ± 10.4 V . The overrang ing feature enables the [c]FP- AI-110 to compensate for field de vices with span errors of up to + 4% ...

  • National Instruments FP-Al-110 - page 9

    © National Instruments Corp. 9 FP-AI-110 and cFP-AI-110 sampling rate is faster than th e rate at which the network module polls the [c]FP-AI-110 for data. Status Indicators The [c]FP-AI-110 has tw o green status LEDs, POWER and READY . After you insert the [c] FP-AI-110 into a terminal base or backplane and apply po wer to th e connected network ...

  • National Instruments FP-Al-110 - page 10

    FP-AI-110 and cFP-AI-110 10 ni.com working v oltages of 250 V rms 1 . Safety standards (such as those published by UL and IEC) requir e the use of double insulation between hazardous voltages and an y human-accessi ble parts or circuits. Never try to use any isolation produ ct between human-accessible parts (such as DIN rails or monito ring station ...

  • National Instruments FP-Al-110 - page 11

    © National Instruments Corp. 11 FP-AI-110 and cFP-AI-110 • Operate the [c]FP-AI-110 only at or belo w Pollution Degree 2. Pollution Degree 2 means th at only nonconductiv e pollution occurs in most case s. Occasionally , howe ver , a temporary conductivity caused by conde nsation must be e xpected. • Operate the [c]FP-AI-110 at or below Measur ...

  • National Instruments FP-Al-110 - page 12

    FP-AI-110 and cFP-AI-110 12 ni.com Safety Guidelines for Hazardous V oltages If hazardous voltages are connected to the module, take the follow ing precautions. A hazardous voltage is a v oltage greater than 42.4 V peak or 60 VDC to earth ground. Caution Ensure that hazardous voltage wiring is performed only by qualified personnel adhering to local ...

  • National Instruments FP-Al-110 - page 13

    © National Instruments Corp. 13 FP-AI-110 and cFP-AI-110 Effecti ve resolution by inpu t signal range and f ilter setting Input charac teristics by f ilter setting Normal-mode rejection .. .............. ..... 95 dB (with 50/60 Hz filter) Nonlinearity .......... ........... ......... ........ 0.0015% (monotonicity 1 guaranteed ov er the operating ...

  • National Instruments FP-Al-110 - page 14

    FP-AI-110 and cFP-AI-110 14 ni.com Input current 25 °C........... ...................... .......... 400 pA typ, 1 nA max 70 °C ............. ........... ........... ........ 3 nA typ, 15 nA max Input noise (with 50 or 60 Hz filter enabled) ± 60 mV range ...... ........... ........... . ± 3 LSB 1 peak-to-peak ± 300 mV range ...... ........... . ...

  • National Instruments FP-Al-110 - page 15

    © National Instruments Corp. 15 FP-AI-110 and cFP-AI-110 Note Full scale is the maximum value of the nominal input range. F or example, for the ± 10 V input range, full scale is 10 V and ± 0.01% of full scale is 1 mV . Gain error drift ........... ......... ........... ... ± 20 ppm/°C Offset error drift W ith 50 or 60 Hz filte r enabled ...... ...

  • National Instruments FP-Al-110 - page 16

    FP-AI-110 and cFP-AI-110 16 ni.com Physical Char acteristics Indicators ............ ........... ........... ........ Green POWER and READY indicators W eight FP-AI-110..... ............. .............. ... 140 g (4.8 oz) cFP-AI-110 ....... ............ .............. 110 g (3.7 oz) Power Requirements Power from network module ............ 350 mW S ...

  • National Instruments FP-Al-110 - page 17

    © National Instruments Corp. 17 FP-AI-110 and cFP-AI-110 Operating shock (IEC 60068-2-27)........... ........... ........ 50 g, 3 ms half sine, 18 shocks at 6 orientations; 30 g, 11 ms half sine, 18 shocks at 6 orientations Safety This product is designed to meet the requirements of the following standards of safety for electric al equipment for m ...

  • National Instruments FP-Al-110 - page 18

    FP-AI-110 and cFP-AI-110 18 ni.com CE Compliance This product meets the essentia l requirements of applicable European Directi ves, as amended for CE ma rking, as follows: Lo w-V oltage Directi ve (s afety). ..... ... 73/23/EEC Electromagnet ic Compatibility Directiv e (EMC) ... ........... ......... ........ 89/336/EEC Note Refer to the Declaratio ...

  • National Instruments FP-Al-110 - page 19

    © National Instruments Corp. 19 FP-AI-110 and cFP-AI-110 Where to Go for Support For more information about settin g up the FieldPoint system, refer to these National Instruments documents: • FieldPoint network module user manual • Other FieldPo int I/O m odule operating instructions • FieldPoint terminal base and connector block operating i ...

  • National Instruments FP-Al-110 - page 20

    © 2003–2005 Nati onal Instruments Corp. All rights reserved. 373280A-01 Jun05 National Instruments, NI, n i.com, and LabVIEW are trademarks of National I nstruments Corporation. Refer to the Terms of Use section on ni.com/legal for more information about National Instruments tra demarks. Other product and company names ment ioned herein are trad ...

Fabbricante National Instruments Categoria Music Mixer

I documenti che otteniamo dal fabbricante del dispositivoNational Instruments FP-Al-110 possono essere suddivisi in diversi gruppi. Questi sono tra gli altri:
- disegni tecnici National Instruments
- manuali per l’uso FP-Al-110
- schede prodotto National Instruments
- opuscoli
- o etichette energetiche National Instruments FP-Al-110
Tutti sono importanti, ma le informazioni più importanti dal punto di vista di utilizzo del dispositivo possono essere trovate nel manuale per l’uso National Instruments FP-Al-110.

Un gruppo di documenti denominato manuali per l’uso, è anche suddiviso in tipi più specifici, come: Manuali di installazione National Instruments FP-Al-110, manuali di manutenzione, brevi manuali o manuali utente National Instruments FP-Al-110. A seconda delle esigenze, si dovrebbe cercare il documento necessario. Nel nostro sito web, puoi visualizzare il manuale più popolare per l'uso del prodotto National Instruments FP-Al-110.

Manuale completo del dispositivo National Instruments FP-Al-110, come deve essere?
Il manuale per l’uso, denominato anche istruzioni per l’uso, o semplicemente il manuale è un documento tecnico progettato per aiutare ad utilizzare National Instruments FP-Al-110 dagli utenti. I manuali sono di solito scritti da uno scrittore tecnico, ma in un linguaggio accessibile a tutti gli utenti National Instruments FP-Al-110.

Il manuale per l’uso completo National Instruments, dovrebbe includere vari elementi di base. Alcuni di loro sono meno importanti, come ad esempio: copertina / pagina del titolo o pagina di autore. Tuttavia, la parte rimanente, dovrebbe fornire informazioni importanti dal punto di vista dell'utente.

1. Introduzione e la guida su come utilizzare il manuale National Instruments FP-Al-110 - All'inizio di ogni manuale, dovremmo trovare indizi su come utilizzare il documento. Dovrebbe contenere informazioni sulla posizione dell’indice National Instruments FP-Al-110, FAQ o i problemi più comuni : i punti che sono più spesso cercati dagli utenti di ogni manuale
2. Indice - elenco di tutti i suggerimenti per National Instruments FP-Al-110 che possono essere trovati nel documento corrente
3. Suggerimenti su come utilizzare le funzioni di base del dispositivo National Instruments FP-Al-110 - che ci dovrebbe aiutare nei primi passi durante l'uso National Instruments FP-Al-110
4. Troubleshooting - sequenza sistematica delle attività che vi aiuterà a diagnosticare e, successivamente, risolvere i problemi più importanti del National Instruments FP-Al-110
5. FAQ - domande più frequenti
6. Dettagli di contatto Informazioni su dove cercare il contatto con il fabbricante / servizio National Instruments FP-Al-110 in un dato paese, se il problema non può essere risolto da noi stessi.

Hai una domanda su National Instruments FP-Al-110?

Utilizza il modulo sottostante

Se non hai risolto il problema con National Instruments FP-Al-110 con l'aiuto del manuale che hai trovato, fai una domanda utilizzando il modulo sottostante. Se un utente ha avuto un problema simile con National Instruments FP-Al-110 è probabile che voglia condividere il modo di risolverlo.

Riscrivi il testo dall’immagine

Commenti (0)